Factory-Mounted Unit Options
34
RT-SVX26K-EN
In order for the return air smoke detector to properly sense
smoke in the return air stream, the air velocity entering the
unit must be between 500 and 4000 feet per minute. Most
models of equipment covered by this instruction will
develop an airflow velocity that falls within these limits
over the entire airflow range specified in the evaporator
fan performance tables.
Certain models, however, if operated at low airflow, will
not develop an air velocity that falls within the required
500 to 4000 feet per minute range. For these models, the
design airflow shall be greater than or equal to the
minimum specified in
Table 10
.
Notes:
•
Airflow through the unit is affected by the amount of
dirt and debris accumulated on the indoor coil and
filters. To insure that airflow through the unit is
adequate for proper sampling by the return air smoke
detector, complete adherence to the maintenance
procedures, including recommended intervals
between filter changes and coil cleaning, is required.
•
Periodic checks and maintenance procedures must be
performed on the smoke detector to insure that it will
function properly. For detailed instructions concerning
these checks and procedures, refer to the appropriate
section(s) of the smoke detector Installation and
Maintenance Instructions provided with the literature
package for this unit.
Important:
Refer to the service literature provided for
testing and other information about the
smoke detector or if problems are
encountered.
Table 10.
Minimum allowable airflow
Unit Model Number
Minimum Allowable
Airflow with Return Air
Smoke Detector
YSD180F, YHD180F
5300 CFM
Figure 26.
Smoke detector wiring scheme