55
RT-PRC007-EN
Performance
Data
50 Hz
Note:
1. Static pressure drops of accessory components must be added to external static pressure to enter fan performance tables.
Table PD-27a – Component Static Pressure Drops — Pa
(SI)
Nominal
Std Tons
L/s
Throwaway
Inlet Guide
(kW)
Std Air
Low
High
1 Element
2 Element
Dry
Wet
Adder
50 mm 100 mm
Vanes
Economizer
3150
17
13
11
12
17
22
12
19
17
11
0.05
3540
21
16
14
15
19
24
17
26
24
14
0.07
80 (23)
3930
26
20
17
19
22
29
19
31
29
17
0.08
4320
31
24
21
23
29
34
22
36
34
21
0.1
4720
37
29
25
27
31
41
26
43
38
25
0.12
3540
21
16
14
15
19
24
17
26
24
14
0.07
3930
26
20
17
19
22
29
19
31
29
17
0.08
88 (25)
4320
31
24
21
23
29
34
22
36
34
25
0.12
5120
44
34
29
32
31
41
26
43
41
29
0.14
4130
29
22
19
21
38
48
22
36
31
19
0.09
4520
34
27
23
25
43
55
24
41
38
23
0.11
103 (29)
4920
41
32
27
29
58
72
29
50
46
27
0.13
5310
47
37
32
34
65
79
31
53
50
32
0.15
4720
2
7
18
27
36
46
26
43
38
8
0.12
5120
3
8
21
32
41
53
29
50
43
10
0.14
5510
3
10
24
37
48
58
31
55
48
11
0.16
118 (33)
5900
4
11
27
42
53
65
34
62
55
13
0.18
6290
4
12
31
48
58
72
36
67
60
15
0.21
6680
5
14
35
54
65
79
41
77
67
16
0.24
5900
4
11
27
42
70
86
34
62
55
13
0.18
6290
4
12
31
48
77
96
36
67
60
15
0.21
146 (42)
6680
5
14
35
54
86
106
41
82
72
16
0.24
7070
5
16
39
60
101
127
46
91
82
18
0.27
7470
6
18
44
67
110
137
48
98
86
21
0.3
High Eff. Filters
Electric Heat
Heating System
Gas Heat
Filters
ID Coil