43

RT-PRC007-EN

Performance
Data

50 Hz — Standard
Condenser Coil

Table PD-21 – 42 Ton Gross Cooling Capacities (MBh) — Standard Efficiency 2-Row Condenser Coil

(I-P)

Ambient Temperature – °F

85

95

105

115

Ent

Entering Wet Bulb Temperature – °F

DB

61

67

73

61

67

73

61

67

73

61

67

73

cfm

(°F)

TGC SHC

TGC SHC

TGC SHC

TGC SHC

TGC

SHC

TGC

SHC

TGC SHC

TGC SHC TGC SHC TGC SHC TGC SHC

TGC SHC

75

469

385

519

298

574

206

446

372

494

286

546

193

421

358

467

272

517

180

395

344

438

259

486

167

12500

80

476

459

521

369

576

279

454

446

495

355

548

267

428

428

469

342

519

254

406

406

441

328

488

240

85

498

498

525

440

578

351

477

477

500

427

550

338

455

455

474

413

521

325

432

432

446

399

489

311

90

526

526

533

513

580

421

504

504

508

500

552

408

482

482

481

481

523

394

458

458

458

458

493

380

75

476

402

526

309

582

209

453

388

500

296

553

196

428

374

472

283

523

183

401

360

444

269

491

170

13500

80

485

481

528

383

583

288

462

462

502

370

555

275

440

440

475

356

525

262

416

416

447

342

85

511

511

533

460

585

365

489

489

508

447

556

351

467

467

481

433

526

338

443

443

453

419

90

540

540

543

539

588

440

518

518

517

517

560

427

494

494

494

494

530

413

470

470

469

469

75

483

418

532

319

588

211

459

404

506

306

558

199

434

390

478

293

528

186

407

375

448

279

14500

80

494

494

535

398

590

296

472

472

509

384

561

283

449

449

481

371

530

270

425

425

452

356

85

523

523

541

480

591

378

501

501

515

467

562

364

477

477

488

453

532

351

453

453

459

439

90

553

553

552

552

595

458

530

530

530

530

567

445

506

506

506

506

537

431

480

480

480

480

75

489

433

538

329

593

214

465

420

511

316

563

202

439

406

482

302

532

189

412

391

452

289

15500

80

504

504

541

412

595

304

482

482

514

399

566

291

458

458

486

385

535

278

434

434

457

370

85

534

534

548

500

597

390

511

511

522

487

568

377

487

487

494

473

537

363

462

462

465

458

90

564

564

564

564

602

476

541

541

541

541

573

463

516

516

516

516

542

449

490

490

490

490

75

495

449

543

339

598

217

470

435

515

326

568

204

444

421

486

312

536

191

417

406

456

295

16500

80

513

513

546

426

600

312

491

491

519

413

570

299

467

467

491

399

539

286

441

441

461

384

85

544

544

554

520

603

403

521

521

528

506

573

390

496

496

500

492

542

376

470

470

470

470

90

575

575

575

575

608

494

551

551

551

551

578

481

526

526

526

526

548

467

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total gross capacity.
3. SHC = Sensible heat capacity.

Table PD-21a – 148 kW (42 Ton) Gross Cooling Capacities —  Standard Efficiency 2-Row Condenser Coil

(SI)

Ambient Temperature – °C

29.4

35.0

40.6

46.1

Ent

Entering Wet Bulb Temperature – °C

DB

16.1

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

L/s

(°C)

TGC SHC

TGC SHC

TGC SHC

TGC SHC

TGC

SHC

TGC

SHC

TGC SHC

TGC SHC TGC SHC TGC SHC TGC SHC

TGC SHC

75

137

113

152

87

168

60

131

109

145

84

160

57

123

105

137

80

152

53

116

101

128

76

142

49

5900

80

140

135

153

108

169

82

133

131

145

104

161

78

125

125

137

100

152

74

119

119

129

96

143

70

85

146

146

154

129

169

103

140

140

147

125

161

99

133

133

139

121

153

95

127

127

131

117

143

91

90

154

154

156

150

170

123

148

148

149

147

162

120

141

141

141

141

153

115

134

134

134

134

144

111

75

140

118

154

91

171

61

133

114

147

87

162

57

125

110

138

83

153

54

118

106

130

79

144

50

6370

80

142

141

155

112

171

84

135

135

147

108

163

81

129

129

139

104

154

77

122

122

131

100

85

150

150

156

135

171

107

143

143

149

131

163

103

137

137

141

127

154

99

130

130

133

123

90

158

158

159

158

172

129

152

152

152

152

164

125

145

145

145

145

155

121

138

138

137

137

75

142

123

156

93

172

62

135

118

148

90

164

58

127

114

140

86

155

55

119

110

131

82

6840

80

145

145

157

117

173

87

138

138

149

113

164

83

132

132

141

109

155

79

125

125

132

104

85

153

153

159

141

173

111

147

147

151

137

165

107

140

140

143

133

156

103

133

133

135

129

90

162

162

162

162

174

134

155

155

155

155

166

130

148

148

148

148

157

126

141

141

141

141

75

143

127

158

96

174

63

136

123

150

93

165

59

129

119

141

89

156

55

121

115

132

85

7320

80

148

148

159

121

174

89

141

141

151

117

166

85

134

134

142

113

157

81

127

127

134

108

85

156

156

161

147

175

114

150

150

153

143

166

110

143

143

145

139

157

106

135

135

136

134

90

165

165

165

165

176

140

159

159

159

159

168

136

151

151

151

151

159

132

144

144

144

144

75

145

132

159

99

175

64

138

127

151

96

166

60

130

123

142

91

157

56

122

119

134

86

7790

80

150

150

160

125

176

91

144

144

152

121

167

88

137

137

144

117

158

84

129

129

135

113

85

159

159

162

152

177

118

153

153

155

148

168

114

145

145

147

144

159

110

138

138

138

138

90

169

169

169

169

178

145

161

161

161

161

169

141

154

154

154

154

161

137

Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total gross capacity.
3. SHC = Sensible heat capacity.

Summary of Contents for Voyager 23 to 42 Ton

Page 1: ...Packaged Rooftop Air Conditioners 27 to 50T on 60 Hz 23 to 42T on 81 148 kW 50 Hz Voyager Commercial with ReliaT el Controls RT PRC007 EN November 2006...

Page 2: ...flexibility TheVoyager Commercial line offers 27 to 50 ton 60 Hz and 23 to 42 ton 50 Hz models Both 50 and 60 Hz models come in a choice of five sizes to meet the changing demands of the commercial r...

Page 3: ...d Benefits Application Considerations Selection Procedure Model Number Description General Data Performance Data Performance Adjustment Factors Controls Electric Power Dimension andWeights Mechanical...

Page 4: ...ef High Efficiency 2 Throwaway Filters High Efficiency 4 Throwaway Filters High Efficiency supply fan motors High Efficiency condenser coil Manual fresh air damper Economizer with dry bulb control Eco...

Page 5: ...3 D Scroll compressor is that slugging will not cause failure In a reciprocating compressor however the liquid or dirt can cause serious damage Low Torque Variation The 3 D Scroll compressor has a ver...

Page 6: ...nections to the unit and the zone sensors is as easy as 1 1 2 2 and 3 3 This simplified system makes it easier for the installer to wire ReliaTel MakesTesting Easy ReliaTel requires no special tools t...

Page 7: ...ion on LonMark visit www lonmark org or Echelon www echelon com Variable Frequency Drives VFD Variable Frequency Drives are factory installed and tested to provide supply fan motor speed modulation VF...

Page 8: ...exceed all California seasonal efficiency requirements They also perform better than required to meet the California NOx emission requirements High Efficiency Condenser Coil Increased capacity and ene...

Page 9: ...d for high static motor conversion is minimized and saves the time normally spent changing to high static oversized motors Single Point Power A single electrical connection powers the unit Trane facto...

Page 10: ...f may be used to provide relief for single story buildings with no return ductwork and exhaust requirements less than 25 percent Altitude Corrections The rooftop performance tables and curves of this...

Page 11: ...itude Corrections The rooftop performance tables and curves of this catalog are based on standard air 075 lb ft 034 kg cm If the rooftop airflow requirements are at other than standard conditions sea...

Page 12: ...cities The satisfactory distribution of air throughout the system requires that there be an unrestricted and uniform airflow from the rooftop discharge duct This discharge section should be straight f...

Page 13: ...12 000 total peak supply cfm is 30 0 tons Thus a nominal 30 ton unit is selected Step 2 Having selected a nominal 30 ton unit the supply fan and exhaust fan motor bhp must be determined Supply Air Fan...

Page 14: ...x 12 000 cfm 1 6 F Mixed air temperature entering heat module 64 8 1 6 66 4 F Total winter heating load peak heating ventilation load total fan motor heat 225 87 2 20 6 291 6 MBh Electric Heating Syst...

Page 15: ...Pa Economizer Table PD 27 07 inches 17 Pa Unit total static pressure 1 50 inches 374 Pa Using total cfm of 10 000 4720 L s and total static pressure of 1 50 inches 38 mm enterTable PD 25 Table PD 25 s...

Page 16: ...7 3 F for 10 000 cfm through heating module Unit supply temperature design heating conditions mixed air temperature air temperature rise 66 7 37 3 104 0 F Air Delivery Procedure Supply air fan bhp and...

Page 17: ...d Low Leak Fresh Air Damper G D Option and Low Leak Fresh Air Damper H E Option and Low Leak Fresh Air Damper 5 The service digit for each model number contains 31 digits all 31 digits must be referen...

Page 18: ...rowaway Filters Digit 13 Supply Fan Motor HP 1 7 5 Hp Std Eff 5 6 kW 2 10 Hp Std Eff 7 5 kW 3 15 Hp Std Eff 11 2 kW 4 20 Hp Std Eff 14 9 kW Digit 14 SupplyAir Fan Drive Selections See Note 3 A 458 H 4...

Page 19: ...FC No Used 1 1 Diameter Width in 22 38 22 00 22 38 22 00 DriveType No Speeds Belt 1 Belt 1 No Motors HP 1 7 50 10 00 1 7 50 10 00 Motor RPM 1760 1760 Motor Frame Size 213 215T 213 215T Exhaust FanType...

Page 20: ...FC No Used 1 1 Diameter Width in 22 38 22 00 25 00 25 00 DriveType No Speeds Belt 1 Belt 1 No Motors HP 1 7 50 10 00 15 00 1 10 00 15 00 Motor RPM 1760 1760 Motor Frame Size 213 215 254T 215 254T Exha...

Page 21: ...ct 2 2 Motor HP RPM 1 0 1075 Motor Frame Size 48 Filters Type Furnished Throwaway No Recommended Size in 6 17 16 x 20 x 2 Refrigerant Charge Std Hi Eff Cond Coil Lbs of R 22 4 Std 30 7 54 3 per circui...

Page 22: ...ce Area sq ft sq m 31 7 2 9 31 7 2 9 Rows Fins Per Foot 2 180 2 180 Refrigerant Control TXV TXV PVC Drain Connect No Size in mm 1 1 25 1 32 1 1 25 1 32 Outdoor FanT ype Propeller Propeller No Used 3 3...

Page 23: ...ws Fins Per Foot 2 180 3 180 Refrigerant Control TXV TXV PVC Drain Connect No Size in mm 1 1 25 1 32 1 1 25 1 32 Outdoor FanT ype Propeller Propeller No Used 3 4 Diameter in mm 28 0 711 28 0 711 Drive...

Page 24: ...200 12 400 No Motors rpm 4 940 Motor hp kW 0 75 0 56 Indoor FanT ype No Used FC 1 Diameter in mm 25 0 635 Width in mm 25 0 635 DriveType Belt No Speeds No Motors 1 1 Motor hp 10 0 7 5 kW Motor rpm Fra...

Page 25: ...4500 4501To 5500 5501To 6500 6501To 7500 Sea LevelTo 609 6 609 9To 762 0 762 3To 1066 8 1067 1To 1674 4 1371 9To 1675 4 1676 7To 1981 2 1981 5To 2286 0 Capacity Multiplier 1 00 92 88 84 80 76 72 Note...

Page 26: ...s 1 All capacities shown are gross and have not considered indoor fan heat To obtain net cooling subtract indoor fan heat 2 TGC Total gross capacity 3 SHC Sensible heat capacity AmbientTemperature Deg...

Page 27: ...3 464 390 425 425 425 425 442 381 406 406 406 406 419 371 Notes 1 All capacities shown are gross and have not considered indoor fan heat To obtain net cooling subtract indoor fan heat 2 TGC Total gros...

Page 28: ...633 386 696 252 548 491 602 371 663 239 520 476 570 356 629 224 491 460 538 340 18000 80 591 591 636 482 698 355 566 566 606 467 666 342 541 541 575 451 632 327 514 514 543 436 85 626 626 644 583 699...

Page 29: ...ot considered indoor fan heat To obtain net cooling subtract indoor fan heat 2 TGC Total gross capacity 3 SHC Sensible heat capacity Table PD 5A 30 Ton Gross Cooling Capacities Mbh High Efficiency 3 R...

Page 30: ...414 429 377 Notes 1 All capacities shown are gross and have not considered indoor fan heat To obtain net cooling subtract indoor fan heat 2 TGC Total gross capacity 3 SHC Sensible heat capacity Table...

Page 31: ...2 612 61 1 61 1 651 518 75 589 516 648 394 714 259 561 501 617 380 681 245 533 485 585 365 646 230 504 470 553 350 18000 80 604 604 651 491 716 364 579 579 621 476 683 350 553 553 590 461 649 335 527...

Page 32: ...600 volts HeatInputMBH HeatingOutputMBH T ons Unit Model No See Note 1 See Note 1 AirTemp Rise F YCD YCH330 L 27 35 YCD YCH360 L 350 000 250 000 283 500 202 500 10 40 YCD YCH420 L YCD YCH330 H 27 35 Y...

Page 33: ...13500 445 4 39 479 4 92 526 5 73 569 6 53 604 7 26 638 7 98 673 8 82 705 9 68 733 10 38 14000 459 4 85 490 5 39 535 6 19 579 7 04 614 7 81 647 8 56 680 9 35 713 10 26 742 11 09 14500 473 5 35 503 5 90...

Page 34: ...726 16 78 751 17 77 774 18 81 19000 690 16 29 71 1 17 27 734 18 29 758 19 34 782 20 41 20000 701 17 83 724 18 91 745 19 94 765 20 99 788 22 12 Static Pressure in wg 1 Table PD 13 Supply Fan Performan...

Page 35: ...450 RPM 400 RPM 350 RPM 300 RPM Volumetric Airflow Rate CFM Supply Fan Performance 40 and 50 Ton Static Presure InWC 0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 26000 0 0 0 5...

Page 36: ...0 12 0 07 13000 0 21 0 16 0 14 0 15 0 2 0 25 0 15 0 26 0 23 0 14 0 09 10500 0 14 0 11 0 09 0 1 0 22 0 27 0 11 0 18 0 16 0 09 0 06 11500 0 17 0 13 0 11 0 12 0 25 0 31 0 13 0 21 0 19 0 11 0 07 35 12500...

Page 37: ...RPM No 550 A 600 B 27 T 650 C 700 700 D 750 750 E 550 A 600 B 30T 650 C 700 700 D 750 750 E 600 B 650 650 C 35T 700 700 D 790 790 F 800 800 G 500 500 H 525 525 J 575 575 K 40T 625 625 L 675 675 M 725...

Page 38: ...5 0 255 0 120 9500 0 320 0 210 0 070 10000 0 255 0 165 0 020 10500 0 190 0 125 11000 0 125 0 060 11500 0 065 0 000 12000 0 005 Notes 1 Performance in table is with both motors operating 2 High speed b...

Page 39: ...ringWet BulbTemperature C DB 16 1 19 4 22 8 16 1 19 4 22 8 16 1 19 4 22 8 16 1 19 4 22 8 L s C TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 23 9 72 4...

Page 40: ...Wet BulbTemperature C DB 16 1 19 4 22 8 16 1 19 4 22 8 16 1 19 4 22 8 16 1 19 4 22 8 L s C TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 23 9 79 1 62...

Page 41: ...TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 23 9 93 2 76 2 103 2 59 8 114 0 41 3 89 1 73 9 98 5 57 7 108 7 39 0 84 4 71 5 93 5 55 4 103 2 36 6 79 7 68 9 88...

Page 42: ...SHC TGC SHC TGC SHC 23 9 114 0 90 0 126 9 70 9 140 7 50 1 108 4 86 7 120 7 67 7 133 9 46 9 102 6 83 2 114 3 64 5 126 9 43 7 96 1 79 7 107 3 61 0 119 3 40 4 4720 26 7 115 5 106 1 127 2 86 5 141 0 66 5...

Page 43: ...oss and have not considered indoor fan heat To obtain net cooling subtract indoor fan heat 2 TGC Total gross capacity 3 SHC Sensible heat capacity Table PD 21a 148 kW 42 Ton Gross Cooling Capacities S...

Page 44: ...19 4 22 8 16 1 19 4 22 8 16 1 19 4 22 8 L s C TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 23 9 72 7 57 2 80 6 46 3 89 7 32 2 69 5 55 4 77 1 44 8 85...

Page 45: ...16 1 19 4 22 8 16 1 19 4 22 8 L s C TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 23 9 82 1 64 2 91 1 52 2 101 1 36 6 78 3 62 1 87 0 50 4 96 7 34 6 74...

Page 46: ...C TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 23 9 94 7 77 4 104 9 60 7 116 1 41 9 90 3 75 0 99 9 58 6 110 8 39 9 85 9 72 4 95 0 56 3 105 2 37 5 80 9 69 8 89 7 53 9 99 4 35 2 4130 26 7 95 8 91 7 1...

Page 47: ...1 6 111 4 88 8 124 3 69 5 138 0 48 4 105 5 85 3 117 5 66 2 131 0 45 1 99 1 81 8 110 8 62 7 123 4 41 9 4720 26 7 118 4 108 7 130 7 88 8 145 1 68 3 112 8 105 5 124 6 85 3 138 3 65 1 107 3 102 0 118 1 82...

Page 48: ...6 163 8 58 0 126 3 107 0 140 1 81 5 155 3 54 2 118 7 102 9 131 9 77 7 146 2 50 4 5900 26 7 142 4 136 9 155 9 110 2 172 6 83 5 136 0 133 1 148 6 106 4 164 4 79 7 128 4 128 4 140 7 102 3 155 9 75 9 121...

Page 49: ...4 2 53 8 13 6 11 9 10 5 9 5 8 6 7 9 7 3 6 8 6 3 5 9 5 6 67 3 17 0 14 8 13 2 11 9 10 8 9 9 9 1 8 5 7 9 7 4 7 0 80 7 14 2 13 0 11 9 11 0 10 2 9 5 8 9 8 4 Notes 1 Air temperature rise in this table are...

Page 50: ...9 31 812 10 21 11235 742 8 74 778 9 63 812 10 55 11650 745 9 11 778 9 96 812 10 89 12065 747 9 47 779 10 34 81 1 11 24 Table PD 25a Supply Fan Performance 82 105 kW SI Static Pressure Pascals 62 9 124...

Page 51: ...600 RPM 500 RPM 400 RPM Volumetric Airflow Rate CFM Static Presure InWC Table PD 25a Supply Fan Performance 23 29 Ton kW SI Continued Static Pressure Pascals 620 9 683 0 745 1 L s rpm kW rpm kW rpm kW...

Page 52: ...1 584 5 90 614 6 49 642 7 10 6683 344 2 57 387 3 09 424 3 62 459 4 14 495 4 70 527 5 28 557 5 84 589 6 43 619 7 05 648 7 69 7076 358 2 97 401 3 56 437 4 09 470 4 65 503 5 21 538 5 84 565 6 42 594 7 02...

Page 53: ...00 s 0 94 1 89 2 83 3 78 4 72 5 66 6 61 7 55 8 5 9 44 10 38 11 33 12 27 13 22 90 WOCFM 80 WOCFM 70 W O CFM 60 W O CFM 5 0 W O C F M 4 0 W O C F M 2 0 H P 1 5 H P 1 0 H P 7 5 H P 800 RPM 750 RPM 700 RP...

Page 54: ...9 0 1 0 18 0 23 0 1 0 17 0 16 0 11 0 065 11200 0 19 0 15 0 13 0 14 0 24 0 3 0 12 0 21 0 19 0 13 0 077 12100 0 22 0 17 0 15 0 16 0 27 0 33 0 13 0 22 0 21 0 15 0 091 10000 0 01 0 03 0 07 0 11 0 15 0 19...

Page 55: ...0 17 19 22 29 19 31 29 17 0 08 88 25 4320 31 24 21 23 29 34 22 36 34 25 0 12 5120 44 34 29 32 31 41 26 43 41 29 0 14 4130 29 22 19 21 38 48 22 36 31 19 0 09 4520 34 27 23 25 43 55 24 41 38 23 0 11 103...

Page 56: ...static pressure drop than the maximum shown in the table for each motor speed tap Table PD 29a Power Exhaust Fan Performance SI External Static Pressure Pa Exhaust High Med Low Airflow Speed Speed Spe...

Page 57: ...red to provide full nominal airflow in the event of drive failure 2 Supply Air Temperature Controls Cooling Economizer During occupied cooling mode of operation the economizer if available and primary...

Page 58: ...Sequence of Operation 1 Occupied Zone Temperature Control Cooling Economizer During occupied cooling mode the economizer if provided and primary cooling are used to control zone temperature If the ent...

Page 59: ...tain Unoccupied zone temperature setpoints For Unoccupied periods heating or primary cooling operation can be selectively locked out at the remote panels or TRACER ConventionalThermostat Interface Con...

Page 60: ...itches from night setback to occupied mode all heating cooling functions begin normal operation When using the night setback options with aVAV heating cooling rooftop airflow must be maintained throug...

Page 61: ...DE values as if the unit was in the heating mode as follows Keep in mind when determining LOADS that the compressors and condenser fans don t run while the unit is in the heating mode and crankcase he...

Page 62: ...7 5 19 6 18 8 7 0 6 7 10 0 26 4 25 2 15 0 38 6 36 0 460 60 3 414 506 27 3 142 7 5 9 8 9 4 3 5 2 9 10 0 13 2 12 6 15 0 19 3 18 0 575 60 3 517 633 21 8 114 7 5 7 8 7 5 2 8 2 3 10 0 10 3 10 1 15 0 15 4 1...

Page 63: ...Ea No HP Ea MCA Fuse Size TC TE YC 275 380 415 50 3 1 10 1 15 18 1 27 3 110 174 5 13 1 3 75 4 4 2 75 2 9 79 100 TC TE YC 305 380 415 50 3 2 15 27 3 174 5 13 1 3 75 4 4 2 75 2 9 93 110 TC TE YC 350 380...

Page 64: ...the three Horizontal Fresh Air Hoods are located side by side The Fresh Air Hoods not shown extend only 23 15 16 from the end of the unit SIDE VIEW SHOWING FRESH AIR AND POWER EXHAUST HOODS FORDOWNFLO...

Page 65: ...65 RT PRC007 EN Dimensional Data 60 50 Hz Figure DD 2 60 Hz 27 35 50 Hz 23 29 Tons TC TE YC Low Heat Note Dimensions in are mm 1 25 4 mm...

Page 66: ...RT PRC007 EN 66 Dimensional Data 60 50 Hz Figure DD 3 60 Hz 27 35 50 Hz 23 29 Tons YC High Heat Note Dimensions in are mm 1 25 4 mm...

Page 67: ...67 RT PRC007 EN Dimensional Data 60 50 Hz Figure DD 4 60 Hz 40 50 50 Hz 33 42Tons TC TE YC Low High Heat Note Dimensions in are mm 1 25 4 mm...

Page 68: ...lable for use with all zone sensors to provide remote sensing capabilities SINGLE SETPOINT SENSOR WITH SYSTEM FUNCTION LIGHTS BAYSENS021 PROGRAMMABLE NIGHT SETBACK SENSOR BAYSENS020 Dimensional Data F...

Page 69: ...CHANGEOVER SENSOR WITH SYSTEM FUNCTION LIGHTS BAYSENS010 WITHOUT LED STATUS INDICATORS BAYSENS008 SINGLE SETPOINT WITHOUT LED STATUS INDICATORS BAYSENS006 Note 1 Remote sensors are available for use...

Page 70: ...ensing capabilities REMOTE MINIMUM POSITION POTENTIOMETER CONTROL BAYSTAT023 TEMPERATURE SENSOR BAYSENS016 ZONE TEMPERATURE SENSOR W TIMED OVERRIDE BUTTON AND LOCAL SETPOINT ADJUSTMENT BAYSENS014 1 ZO...

Page 71: ...addition to the standard 2 row coil weight included in the basic unit weight see component weights TableW 3 Model A B C D E F D330 275 899 408 693 314 717 325 723 328 571 259 471 214 H330 275 920 417...

Page 72: ...Man Guide W O With Serv base Discon Discon Cond Curb Model Relief Exhaust FanMotor2 Damper Econ Vanes Bypass Valves Elec Switch Switch Coil3 Lo Hi D330 275 110 50 165 74 20 9 50 23 260 117 55 25 85 39...

Page 73: ...s Evaporator and Condenser Coils Condenser coils shall have 3 8 copper tubes mechanically bonded to lanced aluminum plate fins Evaporator coils shall be 1 2 internally finned copper tubes mechanically...

Page 74: ...munication link The following alarm and diagnostic information shall be available RTRM Originated Data Unit operating mode Unit failure status Cooling failure Heating failure Emergency service stop in...

Page 75: ...l have 3 8 copper tubes mechanically bonded to lanced aluminum plate fins DischargeAir Sensing Provides true discharge air sensing in heating and cooling models This sensor is a status indicator reada...

Page 76: ...temperature adjustment control and timed override buttons used withTracer Integrated Comfort system May also be used for MorningWarm up setpoint and sensor BAYSENS016 Temperature Sensor is a bullet or...

Page 77: ...77 RT PRC007 EN...