![Trane UniTrane Installation, Operation And Maintenance Manual Download Page 61](http://html.mh-extra.com/html/trane/unitrane/unitrane_installation-operation-and-maintenance-manual_1149050061.webp)
Installation - Electrical
UNT-SVX07J-EN
61
Recommendation: Do not bundle or run interconnection
wiring in parallel with or in the same conduit with any
high-voltage wires (110 V or greater). Exposure of
interconnection wiring to high voltage wiring, inductive
loads, or RF transmitters may cause radio frequency
interference (RFI). In addition, improper separation may
cause electrical noise problems. Therefore, use shielded
wire (Belden 83559/83562 or equivalent) in applications
that require a high degree of noise immunity. Connect the
shield to the chassis ground and tape at the other end.
Note:
Do not connect any sensor or input circuit to an
external ground connection.
MCA and MOP Calculations
Minimum circuit ampacity (MCA) and Maximum
Overcurrent Protection (MOP) calculations for units with
single-phase electric heat:
Heater amps = (heater kW x 1000)/heater voltage
Note:
Use 120 V heater voltage for 115 V units. Use 240 V
heater voltage for 230 V units.
Table 25. Maximum wiring distances for low voltage
controls (ft)
Device
Wire Size
Range
Fan Control Switch
14–22 AWG
500
Zone Sensor
16–22 AWG
200
Table 26. Free discharge and high static ECMs
programmed to standard ECM mode
Unit
Size
115 Volt
208–230 Volt
277 Volt
FLA
HP
FLA
HP
FLA
HP
1
2
1
2
1
2
1
2
1
2
1
2
2
2.2
0.13
1.4
0.13
1.6
0.24
3
2.2
0.13
1.4
0.13
1.6
0.24
4
2.2
0.13
1.4
0.13
1.6
0.24
6
3.1
0.22
1.8
0.22
1.6
0.24
8
3.1
0.22
1.8
0.22
1.6
0.24
10
3.1 2.2 0.22 0.13 1.8 1.4 0.22 0.13 1.6 1.6 0.24 0.24
12
3.1 2.2 0.22 0.13 1.8 1.4 0.22 0.13 1.6 1.6 0.24 0.24
Table 27.
Free discharge ECMs programmed to reduced
FLA mode
Unit
Size
115 Volt
208–230 Volt
277 Volt
FLA
HP
FLA
HP
FLA
HP
1
2
1
2
1
2
1
2
1
2
1
2
2
0.6
0.13
0.4
0.13
0.3
0.24
3
0.6
0.13
0.4
0.13
0.3
0.24
4
0.8
0.13
0.6
0.13
0.4
0.24
6
1.1
0.22
0.8
0.22
0.6
0.24
8
1.6
0.22
1.1
0.22
0.8
0.24
10
0.7 1.2 0.22 0.13 0.5 0.8 0.22 0.13 0.4 0.6 0.24 0.24
12
0.7 1.3 0.22 0.13 0.5 0.9 0.22 0.13 0.4 0.7 0.24 0.24
Table 28. High static ECMs programmed to reduced FLA
mode
Unit
Size
115 Volt
208–230 Volt
277 Volt
FLA
HP
FLA
HP
FLA
HP
1
2
1
2
1
2
1
2
1
2
1
2
2
1.3
0.13
0.9
0.13
0.7
0.24
3
1.3
0.13
0.9
0.13
0.7
0.24
4
1.7
0.13
1.2
0.13
0.9
0.24
6
2.3
0.22
1.6
0.22
1.2
0.24
8
3.1
0.22
1.8
0.22
1.5
0.24
10
1.4
2
0.22 0.13 1 1.4 0.22 0.13 0.7 1.1 0.24 0.24
12
1.5 2.8 0.22 0.13 1.1 1.8 0.22 0.13 0.8 1.4 0.24 0.24
Table 29. Low vertical free discharge ECMs
Unit Size
115 Volt
RPM
FLA
HP
H
M
L
3
3.1
0.22 1090
770
560
4
3.1
0.22
1090
750
560
6
3.1
0.22
1115
760
560
Note:
Actual rpm will vary with application and configuration.
Table 30. Lowboy vertical free discharge ECMs
programmed with reduced FLA mode
Unit Size
115 Volt
RPM
FLA
HP
H
M
L
3
0.5
0.22
1090
770
560
4
0.8
0.22
1090
750
560
6
1
0.22
1115
760
560
Note:
Actual rpm will vary with application and configuration.
Table 31.
Unit RPM
Unit
Size
Free Discharge—Units
with 2-Row Coils
Free Discharge—Units with
3- and 4-Row Coils
H
M
L
H
M
L
2
980
840
655
980
840
655
3
980
780
580
1080
800
600
4
1050
780
580
1080
800
600
6
1030
780
580
1080
800
600
8
1080
800
600
1080
800
600
10
1050
780
580
1080
800
600
1030
780
580
1080
800
600
12
1050
780
580
1080
800
600
1080
800
600
1080
800
600
Unit
Size
High Static—Units with
2-Row Coils
High Static—Units with 3-
and 4-Row Coils
H
M
L
H
M
L
2
1480
1110
865
1480
1110
865
3
1400
1175
860
1500
1355
1110
4
1475
1315
1070
1580
1375
1240
6
1400
1070
855
1475
1285
975
8
1475
1285
975
1475
1285
975
10
1475
1315
1070
1580
1375
1240
1400
1070
855
1475
1285
975
12
1475
1315
1070
1580
1375
1240
1475
1285
975
1475
1285
975
Note:
Actual rpm will vary with application and configuration.
Table 32. Electric heat kW, low vertical fan-coil
Unit Size Unit Voltage
kW
kW
kW
kW
3.0
115
1.00
1.50
2.00
4.0
115
1.00
1.50
2.00
2.50
6.0
115
1.00
1.50
2.00
2.50
Note:
Low vertical units are only available with electric heat in combination
with the two-row cooling coil.
Summary of Contents for UniTrane
Page 163: ......