15
Refrigerant Piping Connection
Cautions before connection tubes tightly
1.
2.
Be sure to apply a sealing cap or waterproof tape to prevent
dust or water from getting into the tubes before they are used.
Be sure to apply refrigerant lubricant to the matching surfaces
of the flare and union before connection them together. This is
effective forreducing gas leaks.
3. For proper connection, align the union tube and flare tube
straight with each other, then screw in the flare nut lightly at
first to obtain a smooth match.
4.
5.
Tighten the flare nut to the specified tightening torque with
torque wrench and adjustable wrench.
Repeat the process above for the remain line.
Do not open service valve at liquid pipe and gas pipe until
finish installation and vacuum.
Tightening torque and size of L-Wrench
Tightening torque for valve cap 10-15 lb-in (11.52-17.3 kg-cm)
Caution
6.35 mm.
Millimeter
Millimeter
Inch
Tube Diameter
Tightening torque
Size of
L-Wrench
N - m
lb - in
f
(1/4”)
25-30
4
9.53 mm.
(3/8”)
25-30
4
12.70 mm.
(1/2”)
60-70
5
15.88 mm.
(5/8”)
60-70
5
19.05 mm.
(3/4”)
2.82-3.39
28.9-34.6
6.68-7.91
69.1-80.7
11.30-13.56 100-120
6
Flare nut / Piping size Tightening torque
Tube Diameter
Thickness
Tightening torque
1/4”
Ø 6.35
Ø 12.70
Ø 15.88
Ø 19.05
Ø 9.53
3/8”
1/2”
5/8”
3/4”
15-20
132-177
31-35
274-310
50-55
443-487
60-65
531-575
70-75
620-664
N-m
mm
mm
inch
ib
ƒ
- in
1/4" (6.35)
3/8" (9.53)
1/2" (12.70)
5/8" (15.88)
3/4" (19.05)
1.0 - 2.0
1.0 - 3.0
1.0 - 2.0
1.0 - 3.0
1.0 - 3.0
8.6 - 9.7
12.4 - 13.9
15.7 - 16.1
19.0 - 20.3
22.4 - 22.7
Flaring copper tube
Outside diameter
Inch (mm.)
H, (mm.)
D, (mm.)
Flaring Procedure
1.
2.
Cut the copper tube to the recommend to cut aprox. 30-50 cm
longer than the tubing length you estimate.
Hold each tube downward when cutting, remove burrs at
the end of the copper tube with a tube reamer or file.
This process is important and should be done carefully
to make a good flare.
3.
4.
Remove the flare nut from the service valve and be sure
to insert the flare nut onto tube.
Make a flare at the end of copper tube with a flare tool.
A good flare should have the following characteristics:
•
•
•
Inside surface is glossy and smooth.
Edge is smooth.
Tapered sides are of uniform length.
When reaming, hold the tube end downward and be sure
that no copper scraps fall into the tube.
Summary of Contents for TTKE12SB5EAA
Page 7: ...MCXE IOM 7 9M 9M 9 G 9M 5 8 M 9M 9 5 5 5 M 52 H H 5 055 8 25 L N 1 2 3 4 5 MC MC 6 7...
Page 38: ...38 MCXE IOM 9 D H 5 D L A Series 5 Model TTKE12SB5EAA TTKE18SB5EAA...
Page 39: ...MCXE IOM 39 9 D H 5 D L A Series 5 Model TTKE24SB5EAA...
Page 40: ...40 MCXE IOM 9 D H 5 D L A Series 5 Model TTKE30SB5EAA...
Page 41: ...MCXE IOM 41 9 D H 5 D L A Series 5 Model TTKE36SB5EAA...
Page 87: ...38 MCXE IOM Wiring Diagram Outdoor Unit Series 5 Model TTKE12SB5EAA TTKE18SB5EAA...
Page 88: ...MCXE IOM 39 Wiring Diagram Outdoor Unit Series 5 Model TTKE24SB5EAA...
Page 89: ...40 MCXE IOM Wiring Diagram Outdoor Unit Series 5 Model TTKE30SB5EAA...
Page 90: ...MCXE IOM 41 Wiring Diagram Outdoor Unit Series 5 Model TTKE36SB5EAA...
Page 98: ...MCXE IOM 49 MEMO...
Page 99: ...50 MCXE IOM MEMO...