Appendix - Unit
Operation
Application
Heat/cool mode input
Effective heat/ cool
Unit Operation
mode input
(nviHeatCool)
mode output
(nviApplicMode)
(nvoHeatCool)
Cool
Any state
Cool
Fan—Enabled
Heating—Disabled
Cooling—Enabled
Damper—Enabled
Pre-cool
Any state
Pre-cool
Fan—Enabled
Heating—Disabled
Cooling—Enabled
Damper—Disabled
Off
Any state
Off
Fan—Disabled
Heating—Disabled
Cooling—Disabled
Damper—Disabled
Test
Any state
Determined by controller
Fan—Enabled
Heating—Enabled
Cooling—Enabled
Damper—Enabled
Fan only
Any state
Fan only
Fan—Enabled
Heating—Disabled
Cooling—Disabled
Damper—Enabled
Note: Night purge, Emergency heat, and Nul modes are not supported by the Tracer ZN524 Unit Controller. If one of these
modes is received by the controller, it is interpreted as Auto.
Table 30:
Unit operation based on H
EAT
/C
OOL
ouput - continued