CNT-SVX11A-EN
21
Configuration
Fan configuration
Default
Valid range
Fan operation in heating
Continuous
Continuous
1
Cycling with capacity
Fan operation in cooling
Continuous
Continuous (during occupied)
Cycling with capacity (unoccupied)
Number of fan speeds
One
1
Configurable fan speed heating
High
Off, high, auto
Configurable fan speed cooling
High
Off, high, auto
Zone sensor fan switch
Enable
Disable or enable
Table 8:
Fan configuration ranges
Setpoint
Default
Valid range
Occupied heating setpoint
71°F
40 to 115°F
Occupied cooling setpoint
74°F
40 to 115°F
Occupied standby heating setpoint
67°F
40 to 115°F
Occupied standby cooling setpoint
78°F
40 to 115°F
Unoccupied heating setpoint
60°F
40 to 115°F
Unoccupied cooling setpoint
85°F
40 to 115°F
Heating setpoint low limit
1
40°F
40 to 115°F
Cooling setpoint low limit
1
40°F
40 to 115°F
Heating setpoint high limit
1
105°F
40 to 115°F
Cooling setpoint high limit
1
110°F
40 to 115°F
Thumbwheel setpoint
Enable
Disable or enable
Economizer setpoint
50°F
40 to 100°F
Humidity setpoint
60%
0 to 100%
Table 9:
Setpoint defaults
1. The heating and cooling setpoint high and low limits only apply to the occupied and occupied standby setpoints and are not applied to the
unoccupied setpoints.
Table 10:
Discharge air limit ranges
Default
Valid Range
Low Limit
1
45°F
30 to 50°F
1. The low limit is the temperature at which the controller shuts down the unit to prevent the coil from frosting.
1. Fan will cycle when unoccupied