20
CNT-SVX07D-EN
Input/output functions and wiring for typical applications
Figure 7.
Two-pipe hydronic-cooling unit
LonTalk
in
Entering water
temperature
Outdoor air or
generic temperature
24 V
†
Exhaust (or fan, medium speed)
24 V
†
Fan, low speed
24 V
†
Cooling valve
24 V
†
Fan, high speed
Low-coil-temperature detection
(closed=normal)*
Condensate overflow (closed=normal)*
Occupancy (open=occupied)*
LonTalk
H
N
24 Vac
24 V
†
Generic/baseboard heat
24 V
†
Electric heat, stage 1 (optional)
out
Fan status (closed=on)*
24 V
†
Electric heat, stage 2 (optional)
24 V
†
Outdoor air damper actuator
AI4 input: See
Figures
and
for wiring
options
Discharge air
temperature
Open
Clos
e
O
pen
Cl
o
s
e
* All binary inputs are configurable.
†
Connect 24 V to an AC POWER (24V) terminal.
Summary of Contents for Tracer ZN521
Page 59: ......