background image

13

Unit Operation

Space Temperature

ZN510 controls the space 
temperature according to the active 
space temperature, the active 
heating/cooling setpoint, and the 
space temperature control 
algorithm. The ZN510 controller 
receives the space temperature 
from either a wired zone sensor or 
as a communicated value. When 
neither a zone sensor nor 
communicated space temperature is 
present, the ZN510 controller 
generates a space temperature 
failure diagnostic.

Note:
The ZN510 controller cannot oper-
ate without a valid space tempera-
ture value (either hardwired or 
communicated).

The space temperature input can 
communicate timed override 

ON

 or 

CANCEL

 requests to the ZN510 

controller. If the 

ON

 button is 

temporarily pressed, the zone 
sensor sends a signal to the 
controller. This signal is then 
interpreted as a timer override 
request which places the unit into 
occupied.

The controller uses the timed 
override request (while the zone is 
unoccupied) as a request to switch 
to the Occupied Bypass mode 
(occupied bypass). This Occupied 
Bypass mode lasts for the duration 
of the occupied bypass time, 
typically 120 minutes.
or
The controller’s Occupancy mode is 
determined from either a system 
level controller or another peer 
controller.

The 

CANCEL

 button cancels the timed 

override request and returned the 
unit to unoccupied mode. If the 

CANCEL

 button is temporarily 

pressed, the zone sensor sends a 
signal to the controller. This signal is 
then interpreted as a timed override 
cancel which places the unit into 
unoccupied.

Local Setpoint

The local setpoint analog input is 
designed as the local (hardwired) 
setpoint input. This input cannot be 
used for any other function. The 
local input is a resistance input 
intended for use with Trane zone 
sensors.

If neither a hardwired nor 
communicated setpoint is present, 
the controller uses the stored default 
setpoints:

z

Occupied setpoints:

In the occupied mode, the unit 
attempts to maintain the space 
temperature at the active 
occupied heating or cooling 
setpoint based on the measured 
space temperature, the active 
setpoint, and the proportional/
integral control algorithm.

z

Occupied standby setpoints

:

In occupied standby mode, the 
controller uses the occupied 
standby cooling and heating 
setpoints. Because the occupied 
standby setpoints typically 
cover a wider range than the 
occupied setpoints, the ZN510 
controller reduces the demand 
for heating and cooling the 
space. Also, the outdoor air 
damper is normally closed 
during occupied standby mode 
to further reduce the heating 
and cooling demands.

z

Unoccupied

 

setpoints

:

In unoccupied mode, the unit 
attempts to maintain the space 
temperature at the stored unoc-
cupied heating or cooling 
setpoint based on the measured 

space temperature, the active 
setpoint, and the proportional/
integral control algorithm, 
regardless of the presence of a 
hardwired or communicated 
setpoint.

Once a valid setpoint is established 
(through the hardwired input or 
through communication) and when 
neither a local setpoint or 
communicated setpoint is present, 
the controller generates a setpoint 
failure diagnostic.

When a setpoint failure diagnostic 
occurs, the controller operates using 
the default heating and cooling 
setpoints. These setpoints are 
factory-configured, but may be 
changed using the Trane service 
tool, Rover.

The ZN510 controller uses the 
following validation sequence for 
the setpoints:

1.

Check for a communicated 
setpoint. If present, validate this 
setpoint.

2.

Check for a hardwired setpoint 
and validate the setpoint.

3.

Use the default setpoint and 
validate this setpoint.

Fan Mode Input

The fan mode analog input (Fan) is 
designed to operate as the fan mode 
switch input. This input cannot be 
used for any other function. The fan 
switch on a Trane zone sensor 
generates the fan mode signal.

The ZN510 controller detects the 
unique resistance corresponding to 
each position of the fan switch. By 
measuring the resistance, the 
controller determines the requested 
fan mode.

Summary of Contents for Tracer ZN510

Page 1: ...WSHP IOP 2 May 1998 Installation Operation and Programming Tracer ZN510 Controller...

Page 2: ...Related Literature z CNT IOP 1 ZN510 1 Controller Installation Operation and Pro graming z WSHP PD 1 Water Source Heat Pump Controller Product Data Sheet z WMCA PD 1 ZN510 Loop Con troller Product Dat...

Page 3: ...on 7 Power 8 Binary Outputs 8 Analog Outputs 9 Binary Inputs 9 Analog Inputs 12 Zone Sensors 15 Heating or Cooling Control Mode Operation 18 Single or Dual Compressor Operation 19 Data Sharing 20 Conf...

Page 4: ...place in the ZN510 IOP on a copy of Sheet 6 of this document or on building plans for future location use The actual room location on the tag may be hand written Zone Sensor Placement Zone sensor loc...

Page 5: ...l minutes to check for the presence of a com municated value 3 A random start time is hard coded on every board and cannot be disabled The board generates a random time delay between 0 and 25 seconds...

Page 6: ...mber The NID is similar to the serial number of the unit but is specific to the identification of the ZN510 Board The location identification is a customer defined clear English description of the uni...

Page 7: ...system Communication is also possible with Trane s service tool Rover ZN510 provides a total of six 1 4 inch quick connect terminals for connection to the Comm5 communication link These connections in...

Page 8: ...air damper It may be field modified to control a generic output for control by a building automation system If set up as a generic output the controller does not use BOP 6 as part of the normal contr...

Page 9: ...ion Circuit 2 Table 2 Binary input configurations Binary Input Description Configuratio n Contact Closure Contact Open BI 1 Low Temperature Detection Cir 2 Normally closed Normal Diagnostic BI 2 Conde...

Page 10: ...to page 28 on how to reset a unit z If BOP 6 is configured as a generic binary output the state of the output is not affected by the low temperature detection diagnostic or by other diagnostics Conden...

Page 11: ...or the status of the generic binary input This input does not affect controller operation High and Low Pressure Switches The high and low pressure cutout switches are wired in series with the compress...

Page 12: ...roller includes an automatic diag nostic reset function that allows the controller to automatically recover after a high or low pres sure cutout diagnostic After 30 minutes the con troller will reset...

Page 13: ...In the occupied mode the unit attempts to maintain the space temperature at the active occupied heating or cooling setpoint based on the measured space temperature the active setpoint and the proporti...

Page 14: ...ing water temperature is less than the leaving water temperature low limit the controller generates a Low Temp Detect diagnostic If the Leaving Water Temp Sensor fails to open or close the controller...

Page 15: ...operation Table 5 Methods of setpoint operation Method Situation used Zone Sensor with an adjustable hardwired setpoint A hardwired adjustable setpoint is connected to the controller Local setpoints a...

Page 16: ...t signal of OFF or AUTO If the fan control request is communicated to the controller the controller ignores the hardwired fan switch input and uses the communicated value The zone sensor fan switch si...

Page 17: ...ion z External setpoint z ON and CANCEL buttons z Communication jack z Vertical case with Trane logo Part Number X13510635010 Description z Space temperature 0 2 C resolution z External setpoint z Fan...

Page 18: ...only changes state when the controller turns on compressor 1 When a power failure occurs the reversing valve output defaults to the heating de energized state To reduce noise due to refrigeration mig...

Page 19: ...verride the controller applies the occupied heating and cooling setpoint but reports the effective occupancy mode as occupied bypass mode In the occupied bypass mode a building automation system can d...

Page 20: ...setpoint For this application each communicating controller uses the same setpoint ON CANCEL ZONE SET COMMMUNICATION 24V SERVICE ZONE SENSOR POWER BINARY IN PUTS FAN Actual Size 4 0 x5 5 ANALOG INPUT...

Page 21: ...switch hardwired Enabled Setpoints Unoccupied cooling setpoint 85 F Occupied standby cooling 78 F Occupied cooling setpoint 74 F Occupied heating setpoint 71 F Occupied standby heating 67 F Unoccupie...

Page 22: ...usly The controller is not detecting any communication Normal for standalone applications LED blinks The controller detects communication normal for communicating applications including data sharing L...

Page 23: ...h ZN510 Loop Controller During Unoccupied the pumps will be OFF but should be energized to test compressor operation The user must override the pumps either at the ZN510 Loop Controller or by pushing...

Page 24: ...heating or cooling to the space Fan mode off When a local fan mode switch determines the fan operation the off position controls the unit fan off Requested mode off The desired operating mode such as...

Page 25: ...ressor may not work correctly No power to the controller If the controller does not have power the compressor does not operate For the ZN510 controller to operate normally a voltage input of 24 VAC mu...

Page 26: ...anual output test sequence that may be used to verify output operation and associated output wiring However based on the current step in the test sequence the outdoor air damper may not be open Refer...

Page 27: ...p failure Enabled Compressor 1 Off Compressor 2 See note below Damper See note below Discharge air temp failure Enabled Compressor s No action Damper No Action Maintenance required example Filter Stat...

Page 28: ...al operation until another diagnostic occurs If a special diagnostic occurs within 24 hours after an automatic diagnostic reset the diagnostic must be manually reset Cycling Power When the 24 VAC powe...

Page 29: ...29 Wiring Diagram...

Page 30: ...30 Wiring Diagram...

Page 31: ...s 18 to 32 VAC 24 VAC nominal 50 or 60 Hz 300 mA Agency Listings UL and CUL 916 Energy Management System Agency Compliance IEC 1000 4 2 ESD IEC 1000 4 4 EFT IEC 1000 4 5 Surge FCC Part 15 Class A Inpu...

Page 32: ...ure 40 to 212 F 40 to 100 C J3 4 Analog ground NA Table 19 Binary Outputs Description Terminals Output Rating Load Energized Load De energized Binary Output 1 J1 1 12 VA 1 VAC RMS typical 24 VAC RMS t...

Reviews: