Auto-commissioning 
sequence

Tracer VV550/551 VAV controllers 
provide an automatic commissioning 
sequence. With a discharge air 
temperature sensor installed, this 
feature exercises the air valve, fan, and 
heat in the box and records the 
discharge air temperature before and 
after the action. This allows the installer 
to easily checkout the operation of the 
box and commission by exception. The 
data from this test is retained in the 
controller for immediate reports or 
retrieval at a later date (for comparison 
purposes).

Manual test function

A Tracer VV550/551 VAV controller 
includes a manual test button, which 
enables a technician to easily exercise 
the outputs of the controller. On 
consecutive button presses, the 
controller steps through a predefined 
sequence that exercises all of the 
controller outputs.

Drive minimum and 
maximum from zone sensor

When applied with a Trane zone sensor 
module that includes a thumbwheel 
setpoint, a Tracer VAV VV550/551 
controller can easily be overridden to 
minimum and maximum flow. By simply 
turning the thumbwheel to 

, the 

controller drives the air valve to the 
minimum cooling flow setpoint. 
Similarly, turning the thumbwheel to 

∗∗

 

drives the air valve to the maximum 
cooling flow setpoint. This simple 
override feature is most useful during 
the checkout and balancing phases of a 
project.

Trane controller 
compatibility

Tracer VV550/551 VAV controllers are 
compatible with the latest generation of 
Trane control products. The controllers 
communicate over a LonTalk

®

 

communications link. This allows Tracer 
VV550/551 VAV controllers to exist on 
the same communication wire as other 
Trane controllers and to share data with 
them as required.

Interoperability

Tracer VV550/551 VAV controllers are 
designed with LonWorks

®

 technology 

and are LonMark

®

 certified. They follow 

the guidelines of the LonMark

®

 Space 

Comfort Controller (SCC) profile. As 
such, the Tracer VV550/551 controllers 
enable control system integration 
flexibility.

Wiring diagram

See Figure 3 on page 6.

Wiring diagram 2

Summary of Contents for Tracer VV550

Page 1: ...CNT PRC003 EN October 2005 Tracer Controls Tracer VV550 551 VAV Controllers...

Page 2: ...other manufacturer or as a standalone device When it is part of a Trane ICS a Tracer VV550 551 VAV controller enables the building automation system BAS to perform functions such as scheduling trendin...

Page 3: ...Auto commissioning sequence 5 Manual test function 5 Drive minimum and maximum from zone sensor 5 Trane controller compatibility 5 Interoperability 5 Wiring diagram 5 Wiring diagram for Tracer VV550...

Page 4: ...to a floor area With this feature the installer can quickly configure the flow control boxes and set up the system without the need for custom programming Local versus remote reheat flexibility Tracer...

Page 5: ...hat includes a thumbwheel setpoint a Tracer VAV VV550 551 controller can easily be overridden to minimum and maximum flow By simply turning the thumbwheel to the controller drives the air valve to the...

Page 6: ...3 Tracer VV550 551 wiring diagram 3 2 1 On Cancel Binary input Trane zone sensor In Out Rover service tool Analog inputs Binary outputs LonTalk communication link 24V GND Wiring diagram for Tracer VV...

Page 7: ...nication link Figure 4 Cancel ON 85 80 75 70 65 60 55 50 o o o TM ROVER Cancel ON 85 80 75 70 65 60 55 50 Cancel ON 85 80 75 70 65 60 55 50 Figure 4 Network architecture with Tracer VV551 VAV controll...

Page 8: ...e 5 Contact your Trane sales office about other compatible zone sensors Figure 5 Zone sensors for use with Tracer VV550 551 GCC order number Zone Timed override buttons LCD Comm jack Setpoint thumbwhe...

Page 9: ...stor 10 k 77 F 25 C From 14 to 122 F 10 to 50 C Space setpoint potentiometer 1 k From 50 to 90 F 10 to 32 2 C Primary discharge air temperature thermistor 10 k 77 F 25 C From 40 to 212 F 40 to 100 C P...

Page 10: ...10 CNT PRC003 EN Figure 6 Tracer VV551 dimensions 7 5 in 19 2 cm 6 5 in 16 7 cm 6 5 in 16 7 cm 7 5 in 19 2 cm 5 5 in 14 0 cm Cover off Cover on...

Page 11: ...nvoStatus SNVT_obj_status Space CO2 nviSpaceCO2 SNVT_ppm Alarm message nvoAlarmMessage SNVT_str_asc Clear alarms diagnostics nviRequest SNVT_obj_request Part of the node object Air flow setpoint input...

Page 12: ...and specifications without notice Literature Order Number CNT PRC003 EN File Number PL ES CNT PRC003 1005 Supersedes CNT PRC003 EN April 2004 Stocking Location Inland Trane A business of American Stan...

Reviews: