Startup Test Log
AFDK-SVU01C-EN
53
Water-Cooled CenTraVac Chiller with
CH530/CH531 Control and Adjustable
Frequency Drive (AFD) Starter
Job Name
AFD Serial Number
Job Location
AFD Model Number
Sales Order Number
Ship Date
Chiller Serial Number
Start Date
Chiller Model Number
Starter Date:
TechView™: Setpoint View: AFD
Default
Setting
Manufacture
AFD Control
Auto
Type
AFD Re-Optimization Sensitivity
10%
Vender ID
Model Number
TechView: Configuration View:
Starter Type: AFD
Trane
Default
Setting
Volts & Hz
Amps
Surge Detections
enable
Motor Data:
Surge Sensitivity
20
Manufacturer
Power Loss Reset Time
60
Type & Frame
Motor NP Volts
460
Drawing #
Motor NP FLA (TVA)
0
Serial Number
Motor NP RLA
1
Nameplate Data:
Motor NP Power
0
RLA
Motor NP Hertz
60
KW
Motor NP PRM (TRPM)
3600
Volts & Hz
Stator Resistance (SRES)
0
Prestart Checks
Date Checked
Flux Current Ref. (FAMP)
0
Motor Grounded
Acceleration Time
30
Motor Rotation
Deceleration Time
30
Drive Chassis Grounded
Current Limit
1
Control Wiring Tight
Current Limit Gain
10
Drive Connections are Tight
Power Loss Mode
Decel
Verified Settings
Power Loss Time
0
Flying Start Enable
disable
Comments:
Flying Start Gain
2000
Use Trane Defaults (for all other AFD
parameters not accessible via TechView)
Test Log Date:
TechView Status View: Motor
Log 1
Log 2
% RLA Average
Amps Average
Volts Average
Load PF
Power KW
Winding #1 temp
Winding #2 temp
Winding #3 temp
AFD Speed
AFD Freq
AFD Transistor temp