If the normal pump and fi lter system fl ow rate exceeds 125 gpm then a manual bypass valve must be in-
stalled as shown in Figure 12. Damage caused by fl ow rates outside this range will void the manufacturer’s
warranty.
The installation is as follows:
1.
Install a fl ow meter on the outlet line of the heater.
2.
Adjust the manual bypass valve until the fl ow
rate is within the fl ow rate range specifi ed for the
heater.
3.
Once the valve is set, note the position and remove
the valve handle to prevent further adjustment.
ATTENTION:
Improperly adjusted manual bypass valves will result in damage to the heater if the
fl ow rates are not maintained as specifi ed in Table 14 under all operating conditions. The heat exchang-
er will fail and this damage will not be covered under warranty.
Table 14: Allowable Water Flow Rate Range
Model
Minimum Flow
Rate (GPM)
Maximum Flow
Rate (GPM)
TR250
25
125
TR400
30
125
Return to
Pool / Spa
Bypass Valve
Heater Inlet
Heater Outlet
Flow Meter
Figure 12: Manual Bypass valve