Trane XR202  Programmable Thermostat

Pub. No. 18HD51D1-1C-EN

     

09/2020    

Part No. 

37-7769005 9

4.6  Installer Menu

To prevent changes that may affect system performance, this thermostat has an INSTALLER MENU and a

 

USER MENU. The 

INSTALLER MENU provides access to every option, while the USER MENU provides access to items that will not affect system 
performance. To access the INSTALLER MENU

 

press the 

Menu

 button for 8 seconds. The display will show item 30 in the table below. 

Use 

Next

 and 

back

 to navigate through menu items. Press 

 or   or 

to change a menu setting.

INSTALLER MENU

(HOLD MENU  8 SECONDS)

DESCRIPTION

DEFAULT 

(FLASHING ICONS)

SETTINGS

(PRESS 

 OR 

)

30    

CR

Heat Cycle Rate (how often the heat will turn on)

MEd

SLO – slow
MEd – medium
FAS – fast

35    

CR

Cool Cycle Rate (how often the cooling will turn on)

MEd

SLO – slow
MEd – medium
FAS – fast

50   

CL

Compressor Lockout / Minimum Off Time 
(protects the compressor from short cycling) 

On

On – 5 minute delay 
OFF – no delay 

65

Maximum Heat Limit 
(maximum set point for heat mode) 

99

47 to 99

66

Minimum Cool Limit (minimum set point for cool mode) 

45

45 to 97

74        

Schedule Type  
(set as either 7-Day, 5-1-1 Day or NonProgrammable) 

5

7 – 7 Day
5 – 5-1-1 Day
0 – Non Programmable 

76   

E

Early Start (starts heating or cooling early so your programmed 
temperature is reached by the programmed time)

OFF

On – start early 
OFF – start at program period time 

79

Fahrenheit or Celsius 

°F

°F – Fahrenheit
°C – Celsius 

81

       

Temperature Display Adjustment (adjust the displayed “Room 
Temperature”)

0

-5 to +5 

83   

dL

Continuous Display Light  
(keep the backlight always on – “C” wire required)

OFF

On  – always on
OFF – momentarily 

86

Change Air Filter (set up a monthly reminder)

OFF

1 to 12 – reminder time (months)
OFF – no filter reminder 

99     

Keypad Lock (prevent unwanted changes to the thermostat)

OFF

On  – disable buttons
OFF – all buttons are active  

5.  Test Modes

Turn on power to the system.

 

5.1  Fan Operation 

If your system does not have a G terminal connection, skip to 
Heating System. 

1.)  Press the fan button to select the On position. The blower 

should begin to operate. 

2.)  Press the fan button to select the Auto position. The blower 

should stop immediately. 

5.2  Heating System

1.)  Move System Switch to Heat position.
2.) Press  to adjust thermostat setting to 1° above room 

temperature. The system should begin to operate and the 
thermostat will indicate Heat On.

3.) Press  to adjust thermostat setting to 1° below room 

temperature. The heating system should stop operating and 
the thermostat should indicate Heat.

5.3   Cooling System

1.)  Move System Switch to Cool position.
2.)   Press   to adjust thermostat setting 1° below room 

temperature. The blower should come on immediately on 
high speed, followed by cold air circulation The thermostat 
will indicate Cool On. There can be up to a 5 minute delay, 
(see INSTALLER MENU, item 50).

3.)  Press to adjust thermostat setting to 1° above room 

temperature. The cooling system should stop operationg and 
the thermostat will indicate Cool.

Note: If Starting Soon is shown on the display, the compressor lock-

out feature is operating. There will be up to a 5 minute delay before 

the compressor turns on (see INSTALLER MENU, item 50).

CAUTION

!

To prevent compressor and/or property damage, if the outdoor temperature is below 55°F, 

DO NOT operate the cooling system. 

Do not allow the compressor to run unless the compressor oil heaters have been operational 

for 6 hours and the system has not been operational for at least 5 minutes. 

Summary of Contents for TCONT202

Page 1: ...his Document is customer property and is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the i...

Page 2: ...erty damage if the outdoor temperature is below 55 F DO NOT operate the cooling system Do not allow the compressor to run unless the compressor oil heaters have been operational for six hours and the...

Page 3: ...GUIDE Thermostat Applications Maximum Stages Heat Cool Gas Oil Electric mV and 24V Heat Only Cool Only or Heat Cool Systems 1 1 2 Product Specifications 3 General Information 3 1 Overview The 202 is a...

Page 4: ...s 4 3 Battery Location Figure 2 LevelingThermostat Leveling is for appearance only and will not affect thermostat operation Battery Location Premium AA alkaline batteries are required when C wire is n...

Page 5: ...ard 2 X2 is required to energize aux heat during defrost Cooling with TAM7 TAM9 24V Mode Indoor Unit Outdoor Unit Thermostat Rc Rh O B Y G W C R G W1 B B Y0 Y Y1 O NOTES 1 Wire third party condensate...

Page 6: ...is required to energize aux heat during defrost Heat Cool Package with Variable Speed Blower Thermostat Rc Rh O B Y G W C R G W1 B Y1 NOTES 1 Wire third party condensate overflow switches between Y o...

Page 7: ...rd 2 X2 is required to energize aux heat during defrost Heat Cool Package Thermostat Rc Rh O B Y G W C R G W1 B Y1 NOTES 1 Wire third party condensate overflow switches between Y of the thermostat and...

Page 8: ...005 NOTES 1 Wire third party condensate overflow switches between Y of the thermostat and Y1 of the airflow control board 2 X2 is required to energize aux heat during defrost Cooling with GAT2 GAM2 TE...

Page 9: ...ange Air Filter set up a monthly reminder OFF 1 to 12 reminder time months OFF no filter reminder 99 Keypad Lock prevent unwanted changes to the thermostat OFF On disable buttons OFF all buttons are a...

Page 10: ...indicator 6 Cancels Hold Returns to Programmed Schedule 15 Day of the week used when programming a schedule 7 Raises Temperature Setting 16 Permanent hold bypassing the schedule 8 Access Menu Options...

Page 11: ...momentarily press the Hold button Hold will be displayed Use or to adjust the temperature The thermostat will hold the room temperature at the selected setting until you press Run to start program op...

Page 12: ...ic Set System Switch to Cool and lower setpoint below room temperature Same procedures as diagnostic for No Heat condition except set the thermostat to Cool and lower the setpoint below the room tempe...

Reviews: