Trane XR103 Non-Programmable Thermostat

Pub. No. 18HD55D1-1C-EN    09/2020    

Part No. 37-7790003 

 9

6.  OPERATING FEATURES

NOTE

To prevent static discharge problems, touch side of 
thermostat to release static build-up before touching any 
keys.

If at any time during testing your system does not operate properly, 
contact a qualified serviceperson.

6.1  Fan Operation

If your system 

does not

 have a 

G

 terminal connection, skip to 

Heating System

.

1. 

Turn on power to the system.

2. 

Move fan switch to

 ON

 position. The blower should begin to 

operate.

3. 

Move fan switch to 

AUTO

 position. The blower should stop 

immediately.

CAUTION

!

Do not allow the compressor to run unless the compressor 
oil heaters have been operational for 6 hours and the system 
has not been operational for at least 5 minutes.

6.2  Heating System

1. 

Move SYSTEM switch to HEAT position. If the auxiliary 
heating system has a standing pilot, be sure to light it.

2. 

Press 

 to adjust thermostat setting to 1° above room 

temperature. The heat pump system should begin to operate. 
However, if the 

Flame icon

 ( ) and 

Snowflake icon

 ( ) are 

flashing, the compressor lockout feature is operating (see 
Configuration menu, item 3.)

3. 

Adjust temperature setting to 4° above room temperature. 
The auxiliary heat system should begin to operate and the 

Flame icon

 ( ) will be flashing.

4. 

Press 

 to adjust thermostat setting below room 

temperature. The heating system should stop operating.

6.3  Emergency System

EMER bypasses the Heat Pump to use the heat source wired  
to terminal E on the thermostat. EMER is typically used when 
compressor operation is not desired, or you prefer back-up 

 

heat only.

1. 

Move SYSTEM switch to EMER position. EMER will flash on 
the display.

2. 

Press 

 to adjust thermostat setting above room 

temperature. The Aux heating system will begin to operate. The 

 

Flame icon

 ( ) will display flashing to indicate that the Aux 

system is operating.

3. 

Press 

 to adjust the thermostat below room temperature. 

The Aux heating system should stop operating.

CAUTION

!

To prevent compressor and/or property damage, if the 
outdoor temperature is below 55°F, DO NOT operate the 
cooling system

6.4  Cooling System

1. 

Move SYSTEM switch to COOL position.

2. 

Press 

 to adjust thermostat setting below room 

temperature. The blower should come on immediately on 
high speed, followed by cold air circulation.

3. 

Press 

 to adjust temperature setting above room 

temperature. The cooling system should stop operating.

6.5  Configuration Menu

The configuration menu allows you to set certain thermostat 
operating characteristics to your system or personal requirements. 
To enter the configuration menu, with SYSTEM switch in OFF 
position, hold 

 and 

 for at least two seconds. To exit the 

configuration menu, move the SYSTEM switch from the OFF 
position.

1

  Step 

Press Button(s) 

Displayed  

Press         or

  

 

(Factory Default) 

to select:

2

OFF

4

Configuration Menu

3

CL

(ON)

3 LO TO

3 HI

Set SYSTEM

switch to OFF

6

Move SYSTEM

switch from OFF

FA

(ON)

and

for at least 2 seconds

and

momentarily

and

momentarily

OFF

0 HI

(0)

5*

OFF

and

momentarily

dL

(ON)

* Not available on earlier models

Return to normal operation

2. 

In the run mode, if the setpoint temperature is manually 
raised by 3°F (2°C) or more above the actual temperature 
with the 

TEMPERATURE UP

 key, and the fast second stage 

feature is enabled, FA on, the second stage will energize 
immediately. With FA off, second stage will not energize 
until the setpoint temperature is 1°F or more above actual 
temperature for more than ten minutes.

3.  Select Compressor Lockout CL OFF or ON

 – Selecting CL 

ON will cause the thermostat to wait 5 minutes before turning 
on the compressor if the heating and cooling system loses 
power. It will also wait 5 minutes minimum between cooling 
and heating cycles. This is intended to help protect the 
compressor from short cycling. Some newer compressors 
already have a time delay built in and do not require this 
feature. Your compressor manufacturer can tell you if the 
lockout feature is already present in their system. When the 
thermostat compressor time delay occurs it will flash the 

Snowflake 

and 

Flame Icons

 for about five minutes.

4.  Select Temperature Display Adjustment 3 LO to 3 HI 

– 

Allows you to adjust the room temperature display up to 3° 
higher or lower. Your thermostat was accurately calibrated 
at the factory but you have the option to change the display 
temperature to match your previous thermostat. The current 
or adjusted room temperature will be displayed on the left side 
of the display.

5.  Select Backlit Display 

– (Not available on earlier models) 

The display backlight improves display contrast in low lighting 
conditions. Selecting backlight ON will keep the light on 
continuously. Selecting Backlight OFF will keep the light off.

Summary of Contents for TCONT103

Page 1: ...NT This Document is customer property and is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with t...

Page 2: ...he compressor oil heaters have been operational for six hours and the system has not been operational for at least five minutes ATTENTION MERCURY NOTICE This product does not contain mercury However t...

Page 3: ...oduct Specifications 3 General Information 3 1 Overview The 103 is a non programmable HP 2H 1C thermostat with a digital display for use with HP applications only 3 2 Contents 1 Thermostat 2 Phillips...

Page 4: ...cy or auxiliary heat system requires that the thermostat energize the fan circuit do not cut jumper W906 If you are unsure of your application contact a qualified service person F or C Selection The f...

Page 5: ...heat during defrost Heat Pump with TAM Series 24V Indoor Unit Outdoor Unit Thermostat R O B Y G E C L W2 R R O O Y1 G W1 B Y0 Y2 W2 W2 W2 W3 W2 BK B X2 Y Y1 NOTES 1 Wire third party condensate overfl...

Page 6: ...it Outdoor Unit Thermostat R O B Y G E C L W2 R R O Y G W1 B W2 W2 B X2 Y NOTES 1 Wire third party condensate overflow switches between Y of the thermostat and Y1 of the airflow control board 2 X2 is...

Page 7: ...eat during defrost Heat Pump with GAT2 GAM2 TEM3 TEM4 Indoor Unit Outdoor Unit Thermostat R O B Y G E C L W2 R O G W B B X2 Y Y1 R W2 W3 NOTES 1 Wire third party condensate overflow switches between Y...

Page 8: ...en 2nd stage heat Aux or Emergency is energized Snowflake icon is displayed non flashing when the SYSTEM switch is in theCOOLposition SnowflakeandFlameiconsaredisplayed flashing if the thermostat is i...

Page 9: ...on high speed followed by cold air circulation 3 Press to adjust temperature setting above room temperature The cooling system should stop operating 6 5 Configuration Menu The configuration menu allo...

Page 10: ...ace manufacturer or a service person to verify the heating is operating correctly No Cool 1 System Switch not set to Cool 2 Loose connection to thermostat or system 3 Cooling System requires service o...

Page 11: ...Pub No 18HD55D1 1C EN 09 2020 Part No 37 7790003 11 NOTES...

Page 12: ...plications For more information please visit trane com or tranetechnologies com Trane has a policy of continuous data improvement and it reserves the right to change design and specifications without...

Reviews: