28
CG-SVX039C-GB
Table 7 – General data CXAF 080-110 High Efficiency
CXAF
CXAF
CXAF
CXAF
CXAF
CXAF
CXAF
80
90
100
80
90
100
110
SHE
SHE
SHE
HE
HE
HE
HE
Net Cooling / Heating Capacity (1)
(kW)
262/290
287/321
315/352
276/294
305/326
336/359
376/400
Net Total Power input in cooling/
heating (1)
(kW)
91/86
106/97
121/106
88/86
102/98
116/107
133/120
Unit electrical data (2) (3) (4)
Short Circuit Unit Capacity
(kA)
15
15
15
15
15
15
15
Power Cable Cross Section (max)
mm²
1*240
1*240
1*240
1*240
1*240
1*240
1*240
Disconnect switch size
(A)
315
400
400
315
400
400
500
Digit 56=1
Maximum Power input
(kW)
122.8
142.0
161.1
123.4
142.6
161.8
178.1
Max. amps
(A)
205.0
233.4
261.9
205.8
234.2
262.7
295.3
Unit start up amps (w/o soft starter
-digit 54=A) (4)
(A)
418.4
466.6
495.1
419.2
467.4
495.9
633.6
Unit start up amps (with soft starter
-Digit 54=B) (4)
(A)
314.4
349.0
377.5
315.2
349.8
378.3
468.4
Displacement power factor
(dpf)
0.86
0.88
0.89
0.87
0.88
0.89
0.87
Digit 56=2
Maximum Power input
(kW)
123.7
142.9
162.0
126.8
146.0
165.1
179.3
Max. amps
(A)
203.2
231.6
260.1
208.2
236.6
265.1
292.9
Unit start up amps (w/o soft starter -
Digit 54=A) (4)
(A)
416.6
464.8
493.3
421.6
469.8
498.3
631.2
Unit start up amps (with soft starter -
Digit 54=B) (4)
(A)
312.6
347.2
375.7
317.6
352.2
380.7
466.0
Displacement power factor
(dpf)
0.88
0.89
0.90
0.88
0.89
0.90
0.88
Digit 56 =3
Maximum Power input
(kW)
125.3
144.5
163.6
128.9
148.1
167.3
181.5
Max. amps
(A)
205.6
234.0
262.5
211.4
239.8
268.3
296.1
Unit start up amps (w/o soft starter -
Digit 54=A) (4)
(A)
419.0
467.2
495.7
424.8
473.0
501.5
634.4
Unit start up amps (with soft starter -
Digit 54=B) (4)
(A)
315.0
349.6
378.1
320.8
355.4
383.9
469.2
Displacement power factor
(dpf)
0.88
0.89
0.90
0.88
0.89
0.90
0.88
Compressor
Compressor Number per Circuit
#
2
2
2
2
2
2
2
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Model Circuit 1 / Circuit 2
kW
25+25/
25+25
25+30/
25+30
30+30/
30+30
25+25/
25+25
25+30/
25+30
30+30/
30+30
30+40/
30+40
Max Comp Power input Circuit 1 /
Circuit 2
kW
28.4+28.4/
28.4+28.4
28.4+38.2/
28.4+38.2
38.2+38.2/
38.2+38.2
28.4+28.4/
28.4+28.4
28.4+38.2/
28.4+38.2
38.2+38.2/
38.2+38.2
38.2+45.2/
38.2+45.
Rated Amps Circuit 1 / Circuit 2
(A)
47+47/
47+47
47+61/
47+61
61+61/
61+61
47+47/
47+47
47+61/
47+61
61+61/
61+61
61+75/
61+75"
Locked Rotor Amps Circuit 1 / Circuit
2 (direct start - Digit 54=A)
(A)
260+260/
260+260
260+294/
260+294
294+294/
294+294
260+260/
260+260
260+294/
260+294
294+294/
294+294
294+413/
294+413
Locked Rotor Amps Circuit 1 / Circuit
2 (Soft starter - Digit 54=B)
(A)
156+156/
156+156
156+176/
156+176
176+176/
176+176
156+156/
156+156
156+176/
156+176
176+176/
176+176
176+248/
176+248
Motor RPM
(rpm)
2900
2900
2900
2900
2900
2900
2900
Oil sump heater Circuit 1 / Circuit 2
(W)
90+90/
90+90
90+90/
90+90
90+90/
90+90
90+90/
90+90
90+90/
90+90
90+90/
90+90
90+90/
90+90
Evaporator
Quantity
#
1
1
1
1
1
1
1
Type
Micro Plate Heat Exchanger
Stainless steel Copper Brazed plate Heat exchanger
Evaporator model
C262X138
C262X138
C262X166
DFX650X138
DFX650X138 DFX650X166 DFX650X194
Evaporator Water Content volume
(l)
37
37
39
40.4
40.4
48.6
56.7
Nominal water connection size
(Grooved coupling) - Without HYM
(in)
-(mm)
4" - 114.3
4" - 114.3
4" - 114.3
4" - 114.3
4" - 114.3
4" - 114.3
4" - 114.3
Nominal water connection size
(Grooved coupling) - With HYM
(in)
-(mm)
4" - 114.3
4" - 114.3
4" - 114.3
4" - 114.3
4" - 114.3
4" - 114.3
4" - 114.3
Maximum pressure on water side
without pump package
(BarA)
10
10
10
10
10
10
10
Hydraulic Module Components
Single pump - Standard head pressure
option
Max available Head Pressure
(kPa)
153
141
137
153
141
137
166
Motor Power
(kW)
5.5
5.5
5.5
5.5
5.5
5.5
7.5
Rated Amps
(A)
11.0
11.0
11.0
11.0
11.0
11.0
14.4
General Data
Summary of Contents for Sintesis Advantage CGAF 100 SE
Page 34: ...34 CG SVX039C GB Top view Typical CGAF CXAF Components location ...
Page 35: ...CG SVX039C GB 35 Typical CGAF CXAF Components location ...
Page 36: ...36 CG SVX039C GB Typical CGAF CXAF Components location ...
Page 85: ......
Page 86: ......
Page 87: ......