16
CG-SVX039C-GB
Table 3 – General data CGAF 080-190 Extra Efficiency
CGAF
CGAF
CGAF
CGAF
CGAF
CGAF
CGAF
CGAF
CGAF
CGAF
80
90
100
110
130
140
150
165
180
190
XE
XE
XE
XE
XE
XE
XE
XE
XE
XE
Net Cooling Capacity (1)
(kW)
297.5
337.4
376.4
426.6
477.2
522.5
561.5
608.0
660.3
708.8
Net Total Power input (1)
(kW)
87.1
98.5
110.8
126.4
143.0
155.3
169.4
186.0
197.4
213.9
Unit electrical data (2) (3) (4)
Short Circuit Unit Capacity (kA)
15
15
15
15
15
15
15
15
15
15
Power Cable Cross Section
(max)
mm²
1*240
1*240
1*240
1*240
1*240
2*300
2*300
2*300
2*300
2*300
Disconnect switch size
(A)
315
400
400
500
500
630
630
630
800
800
Maximum Power input
(kW)
125.30
148.12
167.29
181.49
195.70
227.82
246.99
261.19
279.04
293.24
Unit rated amps
(A)
205.58
239.84
268.3
296.08
323.86
367.24
395.7
423.48
457.06
484.84
Unit start up amps
(w/o soft starter -
Digit 54=A) (4)
(A)
419.01
473.04
501.5
634.39
662.17
600.44
628.9
761.79
795.37
823.15
Unit start up amps
(with soft starter -
Digit 54=B) (4)
(A)
315.01
355.44
383.9
469.19
496.97
482.84
511.3
596.59
630.17
657.95
Displacement power factor
(dpf)
(dpf)
88%
89%
90%
88%
87%
90%
90%
89%
88%
87%
Compressor
Compressor Number per
Circuit
#
2
2
2
2
2
3
3
3
3
3
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Model Circuit 1 / Circuit 2
kW
25+25/
25+25
25+30/
25+30
30+30/
30+30
30+40/
30+40
40+40/
40+40
25+30
+30/25
+30+30
30+30
+30/30
+30+30
30+30
+40/30
+30+40
30+40
+40/30
+40+40
40+40
+40/40
+40+40
Max Comp Power input
Circuit 1 / Circuit 2
kW 28.4+28.4/
28.4+28.4
28.4+38.2/
28.4+38.2
38.2+38.2/
38.2+38.2
38.2+45.2/
38.2+45.2
45.2+45.2/
45.2+45.2
28.4+38.2
+38.2/28.4
+38.2+38.2
38.2+38.2
+38.2/38.2
+38.2+38.2
38.2+38.2
+45.2/38.2
+38.2+45.2
38.2+45.2
+45.2/38.2
+45.2+45.2
45.2+45.2
+45.2/45.2
+45.2+45.2
Rated Amps Circuit 1 /
Circuit 2
(A)
47+47/
47+47
47+61/
47+61
61+61/
61+61
61+75/
61+75
75+75/
75+75
47+61
+61/47
+61+61
61+61
+61/61
+61+61
61+61
+75/61
+61+75
61+75
+75/61
+75+75
75+75
+75/75
+75+75
Locked Rotor Amps Circuit
1 / Circuit 2 (direct start -
Digit 54=A)
(A)
260+260/
260+260
260+294/
260+294
294+294/
294+294
294+413/
294+413
413+413/
413+413
260+294
+294/260
+294+294
294+294
+294/294
+294+294
294+294
+413/294
+294+413
294+413
+413/294
+413+413
413+413
+413/413
+413+413
Locked Rotor Amps Circuit
1 / Circuit 2 (Soft starter -
Digit 54=B)
(A)
156+156/
156+156
156+176/
156+176
176+176/
176+176
176+248/
176+248
248+248./
248+248
156+176
+176/156
+176+176
176+176
+176/176
+176+176
176+176
+248/176
+176+248
176+248.
+248/176
+248+248
248+248
+248/248
+248+248
Motor RPM
(rpm)
2900
2900
2900
2900
2900
2900
2900
2900
2900
2900
Oil sump heater Circuit 1 /
Circuit 2
(W)
90+90/
90+90
90+90/
90+90
90+90/
90+90
90+90/
90+90
90+90/
90+90
90+90
+90/90
+90+90
90+90
+90/90
+90+90
90+90
+90/90
+90+90
90+90
+90/90
+90+90
90+90
+90/90
+90+90
Evaporator
Quantity
#
1
1
1
1
1
1
1
1
1
1
Type
Stainless steel Copper Brazed plate Heat exchanger
Evaporator model
DFX650
x138
DFX650
x138
DFX650
x166
DFX650
x194
DFX650
x222
DFX650
x250
DFX650
x278
DFX650
x278
DFX650
x278
DFX650
x294
Evaporator Water Content
volume
(l)
40.4
40.4
48.6
56.7
64.9
73.1
81.3
81.3
81.3
86
Nominal water connection
size (Grooved coupling) -
Without HYM
(in) -
(mm) 4" -114.3 4" -114.3 4" -114.3 4" -114.3 4" -114.3 5" -139.7
5" -139.7
5" -139.7
5" -139.7
5" -139.7
Nominal water connection
size (Grooved coupling) -
With HYM
(in) -
(mm) 4" - 114.3 4" - 114.3 4" - 114.3 4" - 114.3 4" - 114.3 5" -139.7
5" -139.7
5" -139.7
5" -139.7
5" -139.7
Hydraulic Module Components
Single pump - Standard head
pressure option
Max available Head
Pressure
(kPa)
155
136
119
102
87
141
137
115
159
146
Motor Power
(kW)
5.5
5.5
5.5
7.5
7.5
7.5
7.5
11
11
11
Rated Amps
(A)
11
11
11
14.4
14.4
14.4
14.4
20.8
20.8
20.8
Single pump - High head
pressure option
Max available Head
Pressure
(kPa)
280
266
254
241
232
252
257
245
229
218
Motor Power
(kW)
11
11
11
11
11
15
15
15
15
15
Rated Amps
(A)
20.8
20.8
20.8
20.8
20.8
28
28
28
28
28
General Data
Summary of Contents for Sintesis Advantage CGAF 100 SE
Page 34: ...34 CG SVX039C GB Top view Typical CGAF CXAF Components location ...
Page 35: ...CG SVX039C GB 35 Typical CGAF CXAF Components location ...
Page 36: ...36 CG SVX039C GB Typical CGAF CXAF Components location ...
Page 85: ......
Page 86: ......
Page 87: ......