20
PTAC-SVX01C-EN
Installation
Table 14. PTEE manual test sequence
Step
Indoor
Fan High
Indoor
Fan Low
Remote
Fan
Outdoor
Fan
Condensate
Pump
Comp
Reversing
Valve
Aux. Heat
Ventilation
Door/Fan
Time in
Step
1
All off
Off
Off
Off
Off
N/A (Off)
Off
N/A (Off)
Off
Off
10 sec
2
Fan high
On
Off
Off
Off
N/A (Off)
Off
N/A (Off)
Off
Off
20 sec
3
Fan Low
Off
On
Off
Off
N/A (Off)
Off
N/A (Off)
Off
Off
20 sec
4 Remote
Fan
Off
On
On
Off
N/A (Off)
Off
N/A (Off)
Off
Off
20 sec
5 Outdoor
Fan
Off
On
Off
On
N/A (Off)
Off
N/A (Off)
Off
Off
20 sec
6 Compres
sor
Off
On
Off
On
N/A (Off)
On
N/A (Off)
Off
Off
60 sec
7
Aux Heat
Off
On
Off
OnOff
N/A (Off)
Off
N/A (Off)
On
Off
60 sec
8
Vent
Door
Off
On
Off
OnOff
N/A (Off)
Off
N/A (Off)
Off
On
20 sec
Exit
Table 15. PTHE manual test sequence
Step
Indoor
Fan High
Indoor
Fan Low
Remote
Fan
Outdoor
Fan
Condensate
Pump
Comp
Reversing
Valve
Aux
Heat
Ventilation
Door/Fan
Time in
Step
1 All
off
Off
Off
Off
Off
Off
Off
Off
Off
Off
10 sec
2 Fan
High
On
Off
Off
Off
Off
Off
Off
Off
Off
20 sec
3
Fan Low
Off
On
Off
Off
Off
Off
Off
Off
Off
20 sec
4
Remote Fan
Off
On
On
Off
Off
Off
Off
Off
Off
20 sec
5
Outdoor Fan
Off
On
Off
On
Off
Off
Off
Off
Off
20 sec
6 Condensate
Pump
Off
On
Off
On
On1
Off
Off
Off
Off
20 sec
7 Compressor
on Cooling
Off
On
Off
On
Off
On
OffOn
Off
Off
60 sec
8 Compressor
Off
Off
Off
On
Off
On
Off
Off
OffOn
Off
60 sec
9 Compressor
on Heating
Off
On
Off
On
Off
On
OnOff
Off
Off
60 sec
10
Aux Heat
Off
On
Off
OnOff
Off
Off
OnOff
On
Off
60 sec
11
Vent Door
Off
On
Off
OnOff
Off
Off
Off
Off
On
20 sec
Exit