PTAC-SVX002A-EN
29
Troubleshooting
Issue
Possible Causes
Resolution
Unit does not
start.
•
Unit may have become unplugged.
•
Fuse may be blown.
•
Circuit breaker may be tripped.
•
Unit may be OFF or in wall thermostat
mode.
•
Unit may be in a protection or diagnostic
failure mode. (Refer to the section,
Intelligent Self-checking Control.)
•
Ensure that the plug is securely in the wall
receptacle.
•
Replace the fuse.
(a)
•
Turn ON the unit. The unit shows green
when ON and red when OFF. If the LED is
not lit, there may be a problem with power
or damage to the control.
Unit not cooling
or heating the
room.
•
Unit air discharge section is blocked.
•
Temperature setting is not high or low
enough. Setpoint limits may not allow the
unit to heat or cool the room to the desired
temperature.
•
Unit air filters are dirty.
•
Room is excessively hot or cold when unit
is started.
•
Vent door left open.
•
Unit may be in a protection of diagnostic
failure mode. (Refer to the section,
Intelligent Self-checking Control.)
•
Compressor is in time delay mode. There
is a protective time delay (approximately
3 seconds) on starting the compressor
after a power outage (or restarting after it
has been turned OFF) to prevent tripping
of the compressor overload.
•
Ensure that curtains, blinds, or furniture
are not restricting or blocking unit airflow.
•
Reset to a lower or higher temperature
setting.
•
Remove and clean filters.
•
Allow a sufficient amount of time for the
unit to heat or cool the room. Start
heating/cooling early before outdoor
temperatures, cooking heat, or
gatherings of people begin to make the
room uncomfortable.
•
Close the vent door.
•
Check the dip switch settings for the
desired comfort level.
•
Wait approximately three (3) minutes for
the compressor to start.
Unit display
shows strange
numbers/
characters.
•
The unit may be in a diagnostic condition.
(Refer to the section, Intelligent Self-
checking Control.)
•
The unit may be set for Celsius instead of
Fahrenheit.
Unit makes
noises.
•
Clicking, gurgling, and whooshing sounds
are normal during the operation of the
unit.
Water dripping
outside.
•
If a drain kit has not been installed,
condensation run-off during very hot and
humid weather is normal.
(b)
•
If a drain kit has been installed and is
connected to a drain system, check
gaskets and fitting around the drain for
leaks or clogs.
Water dripping
inside.
•
Wall sleeve is not installed level.
•
Wall sleeve must be installed level for
proper drainage of the condensation.
Check that the installation is level and
make any necessary adjustments.