background image

3

WARNING

The  first  6  inches  of  supply  air  plenum  and  ductwork  must  be 
constructed of sheet metal as required by NFPA 90B. The supply 
air plenum or duct must have a solid sheet metal bottom directly 
under  the  unit  with  no  openings,  registers  or  flexible  air  ducts 
located  in  it.  If  flexible  supply  air  ducts  are  used

,

  they  may  be 

located only in the vertical walls of rectangular plenum, a minimum 
of 6 inches from the solid bottom. Metal plenum of duct may be 
connected  to  the  combustible  floor  base,  if  not,  it  must  be 
connected to the unit supply duct exposed to the supply air opening 
from the downflow unit. Exposing combustible (non-metal) material 
to the supply opening of a downflow unit can cause a fire resulting 
in property damage, personal injury or death.

Exception warning to downflow:
Installations  on  concrete  floor  slab  with  supply  air  plenum  and 
ductwork completely encased must be not less than 2 inches of 
concrete (See NFPA  90A).

The unit can be positioned for bottom return air in the upflow  position, 
left and right return in the horizontal position, top return in downflow 
position.

This Air Handler provides the flexibility for installation in any upflow or 
downflow horizontal application. The  direct drive motors provide a 
selection  of  air  volume  to  match  any    application.  3-Speed  motors 
provide selections of air flow to meet desired applications.

Top and side power  and control wiring, accessible screw terminals for 
control wiring  all combine to make the installation easy, and minimize 
installation cost.  See Fig.6.

2. GENERAL

CAUTION

Make sure the blower motor 
support is tight (3-motor mount 
bolts) then check to see if 
wheel is secured to motor 
shaft before operating unit.

To ensure the proper installation, select a solid and level site. 
Ensure enough space maintained for installation and maintenance.   

    ≥40’’

25’’

    ≥40’’

≥0

≥0

  ≥0

AIRFLOW

Front of unit

Fig.2 CLEARANCES IN THE HORIZONTAL POSITION

Fig.3 CLEARANCES IN THE VERTICAL POSITION

Do not install unit in an area where flammable materials are present 
due to the risk of an explosion resulting in serious injury or death.

WARNING 

If the supporting structural members are not strong enough to take 
the unit’s weight, the unit could fall out of place and cause serious 
injury.
If  a  return-air  duct  is  not  installed,  carefully  select  the  place  and 
method of product installation so that air flow into the product will not 
be blocked.
The  unit  should  be  installed  in  a  level  position  to  ensure  proper 
condensation drainage. Up to an additional ¼" rise over the width or 
depth of the unit is allowed to create additional sloping towards the 
drain.  Unit  must  be  positioned  between  level  and  ¼"  rise,  sloping 
toward the drain connections.
Install  the  indoor  and  outdoor  unit,  power  supply  wiring  and 
connecting  wires  at  least  3.5  ft.  away  from  televisions  or  radios  in 
order to prevent image interference or noise.

Fig.1 CHECKING MOTOR FIX STATUS 

See Fig.2 and Fig.3.

Summary of Contents for Oxbox J4AC4018A1

Page 1: ...tion or operation Failure to follow these instruction may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock property damage personal injury...

Page 2: ...orizontal left or downflow Multiple electrical entry locations Field installed electric heater kits 5 7 5 10 15 20 kW available as an accessory Dual front panel design for ease of maintenance Blower a...

Page 3: ...e possibly resulting in fire electrical shock property damage personal injury or death The unit must be permanently grounded Failure to do so can result in electrical shock causing personal injury or...

Page 4: ...lications Top and side power and control wiring accessible screw terminals for control wiring all combine to make the installation easy and minimize installation cost See Fig 6 2 GENERAL CAUTION Make...

Page 5: ...as insulation so that the thickness is more than 2 in and fits inside the installation space opening Respectively condensation may form on the surface of the insulation Be sure to use insulation that...

Page 6: ...5 8 500 21 5 8 550 18 456 UPFLOW UNIT SHOWN UNIT MAY BE INSTALLED UPFLOW DOWNFLOW HORIZONTAL RIGHT OR LEFT AIR SUPPLY Fig 6 DIMENSIONS SUPPLY AIR FLANGES ARE PROVIDED FOR FIELD INSTALLATION ELECTRICA...

Page 7: ...ay from breaker while setting that side of breaker into opening When breaker is in place release tab locking circuit breaker into location in opening Repeat above operation for remaining breaker s if...

Page 8: ...ont service panel removed view AIRFLOW AIRFLOW Fig 9 INDOOR COIL AND DRAIN PAN SET UP HORIZONTAL ADAPTER KIT VAPOR LINE CONNECTION LIQUID LINE CONNECTION PRIMARY DRAIN CONNECTION VERTICAL DRAIN PAN AU...

Page 9: ...en installed in accordance with electrical codes to the unit cabinet Grounding may also be accomplished by attaching ground wire s to ground lug s provided in the unit wiring compartment Ground lug s...

Page 10: ...W Heat Strip 24 36 60 24 36 60 24 36 60 2 7 5kW Heat Strip 3 10kW Heat Strip 4 5 15kW Heat Strip double Breaker panel 20kW Heat Strip double Breaker panel 36 60 36 60 240 208 240 208 5 29 9 26 4 30 30...

Page 11: ...32 1 38 1 43 1 47 1 54 1 59 1 64 SCFM 1103 1073 1036 998 967 934 896 855 814 Power W 233 241 249 258 265 275 281 286 291 Current A 1 97 2 03 2 09 2 16 2 22 2 29 2 34 2 37 2 41 SCFM 898 752 603 511 405...

Page 12: ...1284 1226 1151 1076 946 904 893 869 Power W 143 151 159 168 177 191 197 195 194 Current A 1 23 1 26 1 33 1 41 1 50 1 61 1 63 1 61 1 62 SCFM 1531 1477 1418 1366 1299 1239 1138 1064 1001 Power W 200 211...

Page 13: ...return ductwork grills special filters accessories etc are accounted for in total resistance See airflow performance tables in this manual Design the duct system in accordance with ACCA Manual D Desig...

Page 14: ...recommended that a professional installation technician is contacted to ensure installation of these such filtration systems are installed correctly IMPORTANT Do not double filter the return air duct...

Page 15: ...R MANUAL BOLT 9 FILTER INSTALLATION DIMENSIONS AIR FILTER REMOVAL DIMENSIONAL DATA 1 Remove bolts manually remove air filter recover see in Fig 12 2 Hold the edge of the air filter and extract out 3 C...

Page 16: ...the air conditioner with the ground observe the local codes 5 If necessary use the power fuse or the circuit breaker or the corresponding scale ampere Fig 13 AIR FILTER CLEAN Fig 14 CONTROL WIRING FO...

Page 17: ...ings CAUTION NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND ATTENTION NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE FM NOTES 1 Use Copper Wire 75 Min Only Between Disconnect Swi...

Page 18: ...CK FL FL BLUE BLUE 4 1 3 2 CB1 60A W1 WHITE L1 L2 L1 L2 BLUE RED LS LS ELEMENTS ELEMENTS BROWN BLACK 1 2 3 4 5 6 0 15kW HEAT KIT 10kW 5kW HEATER KIT PLUG 4 8 2 6 C 1 0 1 BLACK YELLOW 4 8 2 6 RELAY2 YE...

Page 19: ...60A1C00A 090 factory installed This coil comes with a factory installed piston metering device See Table 1 for factory installed piston size Some system combinations will require a different sized pis...

Page 20: ...19 13 7 70 37 32 26 21 16 10 65 38 34 29 24 19 13 60 40 36 31 27 22 17 55 41 37 34 30 26 21 Superheat F Indoor Temperature F Dry Bulb wet Bulb Outdoor Temp F Charge the system by superheat when using...

Reviews: