background image

SSA-SVX06H-EN

7

Pre-Installation

The final position for the air handler must be dictated
by required service access to it, weight distribution
over structural supports, and by the locations of
electrical, refrigerant and condensate drainage
connections. After this is determined, the following
preparations should be made.

Unit Inspection

Inspect material carefully for any shipping damage. If
damaged, it must be reported to, and claims made
against the transportation company. Compare the
information that appears on the unit nameplate with
ordering and submittal data to ensure the proper unit
was shipped. Available power supply must be
compatible with electrical characteristics specified on
component nameplates. Replace damaged parts with
authorized parts only.

IIm

mp

po

orrtta

an

ntt:: Units ordered with a VFD cannot be field

converted to 460 V from 208-230 or from
208-230 V to 460 V.

Inspection Checklist

To protect against loss due to damage incurred in
transit, complete the following checklist upon receipt of
the unit.

Inspect individual pieces of the shipment before
accepting the unit. Check for obvious damage to the
unit or packing material.

Inspect the unit for concealed damage before it is
stored and as soon as possible after delivery.
Concealed damage must be reported within 15
days. If concealed damage is discovered, stop
unpacking the shipment. Do not remove damaged
material from the receiving location. Take photos of
the damage if possible. The owner must provide
reasonable evidence that the damage did not occur
after delivery.

Notify the carrier’s terminal of damage immediately
by phone and by mail. Request an immediate joint
inspection of the damage by the carrier and the
consignee.

Notify the sales representative and arrange for
repair. Do not repair the unit until the damage is
inspected by the carrier’s representative.

Testing for Leaks

All TWE units are shipped with a holding charge of
nitrogen in each circuit and should be leak tested
before installation.

1. Remove the access panel.

2. Locate the liquid line or suction line access valve for

each circuit.

3. Install gauges to determine if the circuits are still

pressurized. If not, the charge has escaped and
should be repaired as required to obtain a leak-free
circuit.

Lifting Recommendations

W

WA

AR

RN

NIIN

NG

G

IIm

mp

prro

op

pe

err U

Un

niitt L

Liifftt!!

F

Fa

aiillu

urre

e tto

o p

prro

op

pe

errlly

y lliifftt u

un

niitt iin

n a

a L

LE

EV

VE

EL

L p

po

ossiittiio

on

n

cco

ou

ulld

d rre

essu

ulltt iin

n u

un

niitt d

drro

op

pp

piin

ng

g a

an

nd

d p

po

ossssiib

blly

y

ccrru

ussh

hiin

ng

g o

op

pe

erra

atto

orr//tte

ecch

hn

niicciia

an

n w

wh

hiicch

h cco

ou

ulld

d rre

essu

ulltt iin

n

d

de

ea

atth

h o

orr sse

erriio

ou

uss iin

njju

urry

y,, a

an

nd

d e

eq

qu

uiip

pm

me

en

ntt o

orr

p

prro

op

pe

errtty

y--o

on

nlly

y d

da

am

ma

ag

ge

e..

T

Te

esstt lliifftt u

un

niitt a

ap

pp

prro

ox

xiim

ma

atte

elly

y 2

24

4 iin

ncch

he

ess ((6

61

1 ccm

m)) tto

o

v

ve

erriiffy

y p

prro

op

pe

err cce

en

ntte

err o

off g

grra

av

viitty

y lliifftt p

po

oiin

ntt.. T

To

o a

av

vo

oiid

d

d

drro

op

pp

piin

ng

g o

off u

un

niitt,, rre

ep

po

ossiittiio

on

n lliiffttiin

ng

g p

po

oiin

ntt iiff u

un

niitt iiss

n

no

ott lle

ev

ve

ell..

N

NO

OT

TIIC

CE

E

E

Eq

qu

uiip

pm

me

en

ntt D

Da

am

ma

ag

ge

e!!

U

Usse

e ssp

prre

ea

ad

de

err b

ba

arrss tto

o p

prre

ev

ve

en

ntt ssttrra

ap

pss ffrro

om

m

d

da

am

ma

ag

giin

ng

g tth

he

e u

un

niitt.. IIn

nsstta

allll tth

he

e b

ba

arrss b

be

ettw

we

ee

en

n lliiffttiin

ng

g

ssttrra

ap

pss,, b

bo

otth

h u

un

nd

de

errn

ne

ea

atth

h tth

he

e u

un

niitt a

an

nd

d a

ab

bo

ov

ve

e tth

he

e

u

un

niitt tto

o p

prre

ev

ve

en

ntt tth

he

e ssttrra

ap

pss ffrro

om

m ccrru

ussh

hiin

ng

g tth

he

e u

un

niitt

cca

ab

biin

ne

ett o

orr d

da

am

ma

ag

giin

ng

g tth

he

e ffiin

niissh

h..

Before preparing the unit for lifting, estimate the
approximate center of gravity for lifting safety. Because
of placement of internal components, the unit weight
may be unevenly distributed. See

“Weights,” p. 21

for

approximate unit weights.

The crated unit can be moved using a forklift of suitable
capacity. For lifting the unit into an elevated mounting
position, run lifting straps or slings under the unit and
attach securely to the lifting device.

Repositioning Drain Pan

Air handlers come with one drain pan that can be
installed in any one of four positions; this allows for
vertical or horizontal application and right or left
condensate line connection.

N

No

otte

e:: Important! All air handlers are shipped with the

drain pan installed in the horizontal position and
the connection on the left side (as shown in

Figure 1, p. 8

. If an alternate position is required,

the drain pan should be repositioned before
setting the air handler. Ensure there is enough
clearance to the sides of the unit for
repositioning the drain pan after installation.

1. Remove the access plate at the opposite end of the

drain connection. This plate secures and lifts the
back end of the drain pan for sloping. It must be
removed before the drain pan can be removed. This

Summary of Contents for Odyssey TWE0514DA

Page 1: ...th or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment March 2020 S SS SA A S SV VX X0 06 6H H E EN N Installation Operation and Maintenance Split System Air Conditioners Odyssey with Symbio Controls Air Handler 5 to 25 Tons M Mo od de el l 6 60 0 H Hz z TWE0604 A B TWE0724 B TWE0904 A B TW...

Page 2: ...r r p pr ro op pe er r P PP PE E f fo or r t th he e j jo ob b b be ei in ng g u un nd de er rt ta ak ke en n c co ou ul ld d r re es su ul lt t i in n d de ea at th h o or r s se er ri io ou us s i in nj ju ur ry y T Te ec ch hn ni ic ci ia an ns s i in n o or rd de er r t to o p pr ro ot te ec ct t t th he em ms se el lv ve es s f fr ro om m p po ot te en nt ti ia al l e el le ec ct tr ri ic ca ...

Page 3: ...re ef fr ri ig ge er ra an nt t t to o r re el li ie ev ve e p pr re es ss su ur re e b be ef fo or re e o op pe en ni in ng g t th he e s sy ys st te em m S Se ee e u un ni it t n na am me ep pl la at te e f fo or r r re ef fr ri ig ge er ra an nt t t ty yp pe e D Do o n no ot t u us se e n no on n a ap pp pr ro ov ve ed d r re ef fr ri ig ge er ra an nt ts s r re ef fr ri ig ge er ra an nt t s s...

Page 4: ...Supply 27 Symbio Controls 28 Installation Checklist 28 Low Voltage Wiring 29 Field Wiring 30 Pairing A Symbio Condenser or Heat Pump with Constant Volume Air Handler 30 Pairing B Symbio Condenser or Heat Pump with SZVAV 2 Speed Air Handler 30 Pairing C Legacy Electromechanical Condenser with 2 Speed Air Handler 31 Field Control Wiring 31 EDC Switch Wiring 32 Checkout Procedure 32 Startup 33 Heatin...

Page 5: ... Digit 8 Voltage 1 208 230VAC 1 PH 60Hz 3 208 230VAC 3 PH 60Hz 4 460VAC 3 PH 60Hz W 575VAC 3 PH 60Hz D 380 415VAC 3 PH 50Hz K 380VAC 3 PH 60Hz Digit 9 Refrigeration Circuit Stage A Single Circuit B Dual Circuit Digit 10 Major Design Sequence A Rev A Digit 11 Minor Design Sequence A Rev A Digit 12 13 Service Digits Digit 14 Efficiency Generation A Generation A 2018 DOE Digit 15 Controls 1 Constant ...

Page 6: ... they appear in this manual Do not destroy or remove the manual from the unit The manual should remain weather protected with the unit until all installation procedures are complete N No ot te e It is not the intention of this manual to cover all possible variations in systems that may occur or to provide comprehensive information concerning every possible contingency that may be encountered durin...

Page 7: ...t i in n u un ni it t d dr ro op pp pi in ng g a an nd d p po os ss si ib bl ly y c cr ru us sh hi in ng g o op pe er ra at to or r t te ec ch hn ni ic ci ia an n w wh hi ic ch h c co ou ul ld d r re es su ul lt t i in n d de ea at th h o or r s se er ri io ou us s i in nj ju ur ry y a an nd d e eq qu ui ip pm me en nt t o or r p pr ro op pe er rt ty y o on nl ly y d da am ma ag ge e T Te es st t ...

Page 8: ...he drain pan is being moved to the vertical position install the other access plates over the horizontal position opening Figure 1 Drain pan location Figure 2 Drain pan relocation N NO OT TI IC CE E S Sy ys st te em m C Co om mp po on ne en nt t D Da am ma ag ge e T Th he es se e a ai ir r h ha an nd dl le er rs s a ar re e s sh hi ip pp pe ed d w wi it th h a a d dr ry y n ni it tr ro og ge en n ...

Page 9: ...un nd de ed d f fi ie el ld d w wi ir ri in ng g p po os se es s F FI IR RE E a an nd d E EL LE EC CT TR RO OC CU UT TI IO ON N h ha az za ar rd ds s T To o a av vo oi id d t th he es se e h ha az za ar rd ds s y yo ou u M MU US ST T f fo ol ll lo ow w r re eq qu ui ir re em me en nt ts s f fo or r f fi ie el ld d w wi ir ri in ng g i in ns st ta al ll la at ti io on n a an nd d g gr ro ou un nd d...

Page 10: ...ect adjacent surfaces from heat damage when brazing in and around the air handler See p 12 Installations Limitations and Recommendations N NO OT TI IC CE E S Sy ys st te em m C Co om mp po on ne en nt t D Da am ma ag ge e P Pr ro op pe er rl ly y i in ns su ul la at te e a al ll l r re ef fr ri ig ge er ra an nt t g ga as s p pi ip pi in ng g t to o p pr re ev ve en nt t p po os ss si ib bl le e w...

Page 11: ...o the unit additional clearances must be considered for the overall space needed For installation of accessories available for this air handler follow the installation instructions that are shipped with each accessory Clearances Allow the following minimum clearances for serviceability Front and Back 24 in 610 mm Sides 22 in 559 mm for 5 10 ton units and 32 in 813 mm for 12 5 25 ton units N No ot ...

Page 12: ... D in mm TWE051 060 48 1 8 1222 4 39 5 8 1006 5 23 5 8 600 0 TWE072 076 090 54 1 8 1374 8 49 1 8 1247 8 26 1 2 673 1 TWE101 120 54 1 8 1374 8 65 1 8 1654 2 26 1 2 673 1 TWE126 150 156 180 69 1 8 1756 0 81 1 4 2063 7 30 762 0 TWE201 240 251 300 71 7 8 1806 6 94 1 4 2394 0 32 1 8 816 0 Note Full dimensional data is available on the following pages ...

Page 13: ...E DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING ACCESS PLATE MUST BE RE INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT 3 IF PERIODIC DRAIN PAN CLEANING IS REQUIRED ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT 4 1 25 4 FEMALE SCHED 40 10 2 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION 5 1 25 4 FEMALE SCHED 40 10 2 PVC PIPE DRAIN CONNECTIO...

Page 14: ...T IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING ACCESS PLATE MUST BE RE INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT 3 IF PERIODIC DRAIN PAN CLEANING IS REQUIRED ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN CONNECTION AT END OF UNIT 4 1 25 4 FEMALE SCHED 40 10...

Page 15: ...N MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING ACCESS PLATE MUST BE RE INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT 3 IF PERIODIC DRAIN PAN CLEANING IS REQUIRED ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT 4 1 25 4 FEMALE SCHED 40 10 2 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION 5 1 25 4 FEMALE SCHED 40 10 2 PVC PIPE DRAIN CONNECTION HORIZONTAL CONF...

Page 16: ...IC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING ACCESS PLATE MUST BE RE INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT 3 IF PERIODIC DRAIN PAN CLEANING IS REQUIRED ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT 4 1 25 4 FEMALE SCHED 40 10 2 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION 5 ...

Page 17: ...ST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING ACCESS PLATE MUST BE RE INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT 3 IF PERIODIC DRAIN PAN CLEANING IS REQUIRED ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT 4 1 25 4 FEMALE SCHED 40 10 2 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION 5 1 25 4 FEMALE SCHED 40 10 2 PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGUR...

Page 18: ...E END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING ACCESS PLATE MUST BE RE INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT 3 IF PERIODIC DRAIN PAN CLEANING IS REQUIRED ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT 4 1 25 4 FEMALE SCHED 40 10 2 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION 5 1 25 4 FEMALE SCHED 40 10 2 PVC...

Page 19: ... OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING ACCESS PLATE MUST BE RE INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT 3 IF PERIODIC DRAIN PAN CLEANING IS REQUIRED ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT 4 1 25 4 FEMALE SCHED 40 10 2 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION 5 1 25 4 FEMALE SCHED 40 10 2 PVC PIPE...

Page 20: ... DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT CLEANING ACCESS PLATE MUST BE RE INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT 3 IF PERIODIC DRAIN PAN CLEANING IS REQUIRED ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT 4 1 25 4 FEMALE SCHED 40 10 2 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION 5 1 25 4 FEMALE SCHED 40 10 2 PVC PIPE DRAIN CONNECTION HOR...

Page 21: ...4 B 385 323 67 99 75 82 56 92 87 88 7 5 TWE0904 B 385 323 67 99 75 82 56 92 87 88 10 TWE1204 A B 441 393 77 121 110 85 79 118 77 119 12 5 TWE1504 B 753 676 168 192 181 135 196 164 145 171 15 TWE1804 B 752 675 167 192 181 135 196 163 145 171 20 TWE2404 B 912 818 258 168 161 231 256 181 146 235 25 TWE3004 B 993 899 211 229 184 275 272 176 228 223 Table 3 Constant volume air handler TWE unit and corn...

Page 22: ...156 201 251 150 180 240 300 Top View Control Box Access Figure 16 Horizontal TWE051 072 076 101 060 072 090 120 Top View Control Box Access Figure 17 Horizontal TWE126 156 201 251 150 180 240 300 Top View Control Box Access W We ei ig gh ht ts s ...

Page 23: ... 230 235 10 79 100 28 4 80 2 13 211 234 230 235 10 79 100 28 4 80 2 15 211 234 230 235 10 79 100 28 4 80 2 16 7 242 261 145 265 12 79 100 31 7 88 2 20 242 261 145 265 12 79 100 31 7 88 2 20 9 242 261 145 265 12 79 100 31 7 2 25 242 261 145 265 12 79 100 31 7 2 Unit Used w Tons RIS Isolator Suspend ed Mount Steel Spring Isolator Floor Mount Steel Spring Isolator Suspend ed Mount Hail Guard Control ...

Page 24: ...th the air handler and the structure Refrigerant Piping Installation brazing leak testing and evacuation of refrigerant lines are covered in the installation instructions that shipped with the outdoor unit Read the instructions before beginning installation of refrigerant lines N NO OT TI IC CE E E Eq qu ui ip pm me en nt t D Da am ma ag ge e E En ns su ur re e t th ha at t t th he e r re ef fr ri...

Page 25: ...e ee ev ve ed d l lo oo os se e f fi it tt ti in ng g c cl lo ot th hi in ng g g gl lo ov ve es s a an nd d e ey ye e p pr ro ot te ec ct ti io on n W Wa as sh h c cl lo ot th he es s s se ep pa ar ra at te el ly y f fr ro om m o ot th he er r c cl lo ot th hi in ng g r ri in ns se e w wa as sh he er r t th ho or ro ou ug gh hl ly y O Op pe er ra at ti io on ns s s su uc ch h a as s s sa aw wi in ...

Page 26: ...o ot th hi in ng g r ri in ns se e w wa as sh he er r t th ho or ro ou ug gh hl ly y O Op pe er ra at ti io on ns s s su uc ch h a as s s sa aw wi in ng g b bl lo ow wi in ng g t te ea ar r o ou ut t a an nd d s sp pr ra ay yi in ng g m ma ay y g ge en ne er ra at te e f fi ib be er r c co on nc ce en nt tr ra at ti io on ns s r re eq qu ui ir ri in ng g a ad dd di it ti io on na al l r re es sp p...

Page 27: ...f fi ie el ld d w wi ir ri in ng g i in ns st ta al ll la at ti io on n a an nd d g gr ro ou un nd di in ng g a as s d de es sc cr ri ib be ed d i in n N NE EC C a an nd d y yo ou ur r l lo oc ca al l s st ta at te e n na at ti io on na al l e el le ec ct tr ri ic ca al l c co od de es s 1 All electrical lines sizing protection and grounding must be in accordance with the National Electric Code an...

Page 28: ... only 2 Choose only one of the following Thermostat Mechanical Zone Sensor Programmable Zone Sensor Panel or BAS Zone Sensor I Im mp po or rt ta an nt t For the EDC switch to be functional and thereby facilitate reliable unit operation make the EDC connections from the indoor to the outdoor control boxes Table 5 Recommended thermostat wire size Wire Size Maximum Wire Length Gauge Physical distance...

Page 29: ...ct unit for proper filters securely installed and not touching the coil surface All cabinet panels must be secure Instruct owner operator on proper system operating and maintenance procedure Inspect blower assembly to make sure all bolts and screws are tight Inspect blower pulley alignment Inspect factory high and low voltage wiring to make sure all connections are tight and clean Low Voltage Wiri...

Page 30: ...pply 24VAC to the Relay Board b For all other units 24VAC should be supplied to the air handler from the outdoor unit as shown in the schematic See Figure 23 p 31 3 Thermostat interface Interconnection wiring as shown in Figure 24 p 31 is required to initiate air handler supply fan operation and to prevent air handler coil frosting if desired 4 Electric Heat when installed a IMC InterModule Commun...

Page 31: ...st Control Follow instructions on the Air Handler unit schematic on configuring and connecting the Evaporator Defrost Control EDC Switch 4 Electric Heat when installed For all wiring associated with electric heat refer to Air Handler unit schematic and Electric Heat Accessory Installation Guide ACC SVN91 EN Field Control Wiring Figure 23 24VAC wiring to air handler from outdoor unit 1 J15 J10 Air ...

Page 32: ...2 Y1 G EF C R ELECTROMECHANICAL CONDENSER THERMOSTAT EDC Switch Wiring The Evaporator Defrost Control Switch is wired from the factory Normally Open to operate with Symbio condensers For operation with legacy Reliatel or Electromechanical condensers change the wiring on the switch to the Normally Closed position and connect the wires from the switch to the wires from the legacy condenser that cont...

Page 33: ...nt p 44 SZVAV and Two Speed Air Handling Units with Symbio Condenser Units The Symbio 700 controller provides integrated Supply Fan speed setpoint control for paired air handler units with VFDs for SZVAV and Two Speed fan operation These setpoints can be manipulated through the Symbio 700 user interface including the Symbio Service and Installation app or through a connected BAS if required Figure...

Page 34: ...e the example below E Ex xa am mp pl le e Parameter 6 14 in the VFD 25Hz Effective Supply Fan Maximum VFD Output based on Supply Fan Maximum Speed Setpoint 60Hz Supply Fan Minimum Speed Setpoint 50 Effective Supply Fan Minimum VFD Output Effective Supply Fan Maximum VFD Output VFD Parameter 6 14 x 50 25Hz 42 5Hz Table 8 Maximum fan speed setpoints and effective supply fan maximum VFD output When V...

Page 35: ...e properly configured to integrate appropriately with various air handler configurations As shipped from the factory the Symbio 700 in the condenser is configured to be integrated with a single speed constant volume air handler If the air handler paired with the condenser is a two speed or SZVAV configuration the Symbio 700 configuration must be updated in the condenser This configuration update c...

Page 36: ...36 SSA SVX06H EN Figure 30 Edit configuration Figure 31 Select multi speed and apply changes S St ta ar rt tu up p ...

Page 37: ...SSA SVX06H EN 37 Figure 32 Verify changes S St ta ar rt tu up p ...

Page 38: ...lowing steps and refer to through Figure 35 p 39 1 In the Mobile Service and Installation app tap S Se et tt ti in ng gs s 2 Tap E Ed di it t 3 Tap S Sy ys st te em m T Ty yp pe e 4 Select V VV VZ ZT T 5 Tap A Ap pp pl ly y 6 Verify that all settings are correct Figure 33 Edit configuration S St ta ar rt tu up p ...

Page 39: ...SSA SVX06H EN 39 Figure 34 System type Figure 35 Verify changes S St ta ar rt tu up p ...

Page 40: ...s will be generated Use the following steps and refer to through 1 In the Mobile Service and Installation app tap S Se et tt ti in ng gs s 2 Tap E Ed di it t 3 Tap P Pr ri im ma ar ry y H He ea at ti in ng g S So ou ur rc ce e 4 Tap E El le ec ct tr ri ic c 5 Tap P Pr ri im ma ar ry y H He ea at ti in ng g S So ou ur rc ce e 6 Select 1 1 o or r 2 2 7 Tap A Ap pp pl ly y 8 Verify that all settings ...

Page 41: ...SSA SVX06H EN 41 Figure 37 Select primary heating source Figure 38 Apply edits Figure 39 Verify changes S St ta ar rt tu up p ...

Page 42: ... In the Mobile Service and Installation app tap S Se et tt ti in ng gs s 2 Tap E Ed di it t 3 Tap S Se ec co on nd da ar ry y H He ea at ti in ng g S So ou ur rc ce e 4 Tap E El le ec ct tr ri ic c 5 Tap S Se ec co on nd da ar ry y H He ea at ti in ng g S So ou ur rc ce e 6 Select 1 1 o or r 2 2 7 Tap A Ap pp pl ly y 8 Verify that all settings are correct Figure 40 Edit configuration S St ta ar rt...

Page 43: ...SSA SVX06H EN 43 Figure 41 Select secondary heating source Figure 42 Apply changes Figure 43 Verify changes S St ta ar rt tu up p ...

Page 44: ...or Gates tension gauge or equivalent adjust the belt tension as follows 1 To determine the appropriate belt deflection a Measure the center to center shaft distance in inches between the fan and motor sheaves b Divide the distance measured in Step 1a by 64 the resulting value represents the amount of belt deflection that corresponds to the proper belt tension 2 Set the large O ring on the belt ten...

Page 45: ... s p pr ro od du uc ct t d du ur ri in ng g i in ns st ta al ll la at ti io on n m ma ai in nt te en na an nc ce e o or r r re ep pa ai ir r w wi il ll l e ex xp po os se e y yo ou u t to o a ai ir rb bo or rn ne e p pa ar rt ti ic cl le es s o of f g gl la as ss s w wo oo ol l f fi ib be er rs s a an nd d c ce er ra am mi ic c f fi ib be er rs s k kn no ow wn n t to o t th he e s st ta at te e o ...

Page 46: ...rator fan belt If it is worn or frayed replace it Inspect the control panel wiring to ensure that all connections are tight and that the insulation is intact Check refrigerant piping and fittings for leaks Inspect the evaporator coils for dirt and debris If the coils appear dirty clean them Coil Cleaning Regular coil maintenance including annual cleaning enhances the unit s operating efficiency by...

Page 47: ...or Superheat F at compressor Subcooling F at liquid line Dry Bulb Wet Bulb Suction Pressure Discharge Pressure Circuit 1 Circuit 2 Circuit 1 Circuit 2 C1 C2 C1 C2 Note Perform each inspection once per month during cooling season while unit is operating M Ma ai in nt te en na an nc ce e ...

Page 48: ...nits with Digit 8 3 4 W D K AND Digit 15 1 121332730001 Schematics TWE 2 Speed Fan All TWE Units with Digit 15 C 121332720001 Schematics TWE Constant Volume 1 Phase All TWE Units with Digit 8 1 Device Location 121335870001 Device Location TWE SZVAV 2 Speed Fan with Symbio Condenser All TWE Units with Digit 15 D 121335850001 Device Location TWE Constant Volume All TWE Units with Digit 15 1 12133586...

Page 49: ...t No liability whatever shall attach to Warrantor until said products have been paid for and then said liability shall be limited to the purchase price of the equipment shown to be defective THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES WHETHER IN CONTRACT OR IN NEGLIGENCE EXPRESS OR IMPLIED IN LAW OR IN FACT INCLUDING IMPLIED WARRANTIES OF MERCHAN...

Page 50: ...50 SSA SVX06H EN N No ot te es s ...

Page 51: ...SSA SVX06H EN 51 N No ot te es s ...

Page 52: ...isit trane com or americanstandardair com Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice We are committed to using environmentally conscious print practices SSA SVX06H EN 27 Mar 2020 Supersedes SSA SVX06G EN August 2017 2020 ...

Reviews: