Inspect all field wiring connections. All connections
should be clean and tight.
☐
Inspect unit ground connection(s). Ground must
comply with all applicable codes.
☐
Inspect unit suspension arrangement (if used). Unit
position must be secure. Remove any tools or
debris found in or near the unit.
☐
Inspect duct outlets. Outlets must be open and
unrestricted.
☐
Inspect unit drain lines. Pipe connections must be
tight and drain line unrestricted.
☐
Inspect fan assembly to insure all moving parts
move freely.
☐
If unit is horizontally mounted, make sure
secondary drain pan has been installed.
☐
Inspect unit for proper filters, securely installed and
not touching the coil surface. All cabinet panels
must be secure.
☐
Instruct owner/operator on proper system
operating and maintenance procedure.
☐
Inspect blower assembly to make sure all bolts and
screws are tight.
☐
Inspect blower pulley alignment.
☐
Inspect factory high and low voltage wiring to make
sure all connections are tight and clean.
Low Voltage Wiring
Mount the indoor thermostat, zone sensor, or
programmable zone sensor in accordance with the
corresponding thermostat installation instructions.
Install color-coded, weather-proof, multi-wire cable
according to the field wiring instructions (see
“Field
Wiring,” p. 30
).
N
No
otte
e:: Refer to thermostat or zone sensor wire
installation guide for proper wire gauge.
IIn
nsstta
alllla
attiio
on
n