background image

10

SS-APG008H-EN

WARNING

Risk of Explosion with Refrigerant Line!

Failure to follow instructions could cause a refrigerant
line to explode under pressure which could result in
death or serious injury.
Liquid refrigerant trapped between two valves can
become highly pressurized if the ambient temperature
increases. DO NOT add a liquid line solenoid valve in
a cooling-only system that is already equipped with a
check valve.

Moisture-Indicating Sightglass

Be sure to install one moisture-indicating sight glass in the
main liquid line.

Note:

The sole value of the glass is its moisture-indicating

ability. Use the Installation manual charging curves
—not the sightglass—to determine proper charge
levels.

Expansion Valve

The expansion valve is the throttling device that meters the
refrigerant into the evaporator coil. Metering too much
refrigerant floods the compressor; metering too little
elevates the compressor temperature. Choosing the
correct size and type of expansion valve is critical to ensure
that it will correctly meter refrigerant into the evaporator coil
throughout the entire operating envelope of the system.

Correct refrigerant distribution into the coil requires an
expansion valve for each distributor.

For improved modulation, choose expansion valves with
balanced port construction and external equalization.

Table

4, p. 26

identifies the part number of the valve

recommended for TTA/TWA systems. The tonnage of the
valve should represent the tonnage of the portion of coil
that the TXV/ distributor will feed.

Some expansion valve models have built-in check valves
for heat pump operation and do not require additional
external check valves for reverse flow operation. TXVs
containing a check valve are identified in

Table 4, p. 26

.

The TWE air handler ships with a factory installed
expansion device and heat pump check valve. If an
alternate device is required, these factory shipped
components must be removed.

The Microchannel condenser cooling-only units do not
require a bleed TXV valve as required on some other
product types. TXV for TTA microchannel units can also be
selected from

Table 4, p. 26

.

Check Valves

WARNING

Risk of Explosion with Refrigerant Line!

Failure to follow instructions could cause a refrigerant
line to explode under pressure which could result in
death or serious injury.
Liquid refrigerant trapped between two valves can
become highly pressurized if the ambient temperature
increases. DO NOT add a liquid line solenoid valve in
a cooling-only system that is already equipped with a
check valve.

TWA: Due to the reverse cycle of the TWA heat pump, a
check valve is required to bypass refrigerant around the
TXV while the unit is in heating mode. If the air handler is a
TWE, it includes both the TXV and check valve.

TTA: Because of the limited holding capacity of the
microchannel heat exchanger, if more than 50 ft of liquid
line is above a TTA unit, a check valve should be installed
in the liquid line at the TTA unit to prevent backflow during
the off condition. The check valve should be one size larger
than the liquid line to reduce pressure drop and should be
located at the TTA unit. A solenoid valve should never be
used in the liquid line when using this check valve.

Gas Line

Line Sizing

Proper line sizing is required to guarantee that the oil
returns to the compressor throughout the system’s
operating envelope. At the same time, the line must be
sized so that the pressure drop does not excessively affect
capacity or efficiency. To accomplish both objectives, it may
be necessary to use two different line diameters: one for
the horizontal run and for the vertical drops, and another for
the vertical lifts (risers).

Note:

Preselected suction-line diameters shown in the

Component Selection tables found in

“Parts,” p. 25

,

are independent of total line length for properly
charged 6 – 25 ton TTA/TWA in normal air-
conditioning applications.

Routing

Route the line as straight (horizontally and vertically) as
possible. Avoid unnecessary changes of direction. To
prevent residual or condensed refrigerant from “free-
flowing” toward the compressor, install the gas line so that
it slopes by ¼ to 1 inch per 10 feet of run (1 cm per 3 m)
toward the indoor coil.

Do not install riser traps. With field-supplied air-handler
coils, what appears to be a riser trap is located at the coil
outlet; see

Figure 5, p. 11

for an example. This piping

arrangement, which isn’t a riser trap, is the result of two
requirements:

Drain the coil to the common low point.

Line Sizing, Routing, and Component Selection

Summary of Contents for Odyssey TTA0724 A Series

Page 1: ...person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment June 2022...

Page 2: ...that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the app...

Page 3: ...itutes or refrigerant additives WARNING Explosion Hazard Failure to follow instructions below could result in an explosion which could result in death or serious injury and equipment damage NEVER bypa...

Page 4: ...g Routing and Component Selection 9 Liquid Lines 9 Line Sizing 9 Routing 9 Insulation 9 Components 9 Gas Line 10 Line Sizing 10 Routing 10 Insulation 11 Components 11 Expansion Valves 12 Controls 13 H...

Page 5: ...r the evaporator inlet Operational problems can occur if these refrigerant lines are designed or installed improperly Figure 1 Interconnecting refrigerant lines in a typical split air conditioning sys...

Page 6: ...equation based formulas to predict the entrainment velocities of R 410A refrigerant and POE oil These minimum velocities are reflected in the line sizes listed in the component selection summary table...

Page 7: ...contact the manufacturer for review Figure 3 Allowable elevation difference TWA above indoor unit Not allowed for TWA units Note Regardless of orientation hot gas bypass HGBP lines are limited to 75...

Page 8: ...nits Note Route refrigerant piping for minimum linear length minimum number of bends and fittings Important Read Application Guide SS APG008 EN thoroughly before installing this unit Note All liquid p...

Page 9: ...or positioning the components in the liquid line Position the components as close to the indoor unit as possible The Component Selection tables found in Parts p 25 identify suitable components by part...

Page 10: ...th Refrigerant Line Failure to follow instructions could cause a refrigerant line to explode under pressure which could result in death or serious injury Liquid refrigerant trapped between two valves...

Page 11: ...promotes stable TXV operation Avoid Underground Refrigerant Lines Underground lines create risk due to refrigerant condensation during the off cycle installation debris inside the line including conde...

Page 12: ...nsure the condensing unit is capable of operating at these conditions Example 2 10 ton coil one refrigerant circuit with two distributors and a 60 40 coil split 10 x 6 6 and 10 x 4 4 One TXV should be...

Page 13: ...to the third party Simply stated this means that when a compressor turns on it shouldn t turn off until the expansion valve comes under control And once the compressor turns off it should be allowed...

Page 14: ...g applications To prevent evaporator freeze up our equipment typically includes Trane Frostat coil frost protection Like hot gas bypass the Frostat system protects the coil from freezing but it does s...

Page 15: ...OD and smaller of type L copper are suitable for use with R 410A Suction lines 3 1 8 OD must use type K or thicker wall Discharge lines liquid lines heat pump vapor lines and hot gas bypass lines 1 3...

Page 16: ...enters the coil quickly turns to liquid The MCHE tube volume holds very little refrigerant so the refrigerant charge of the system is reduced However the tube volume is so small that if the flow of re...

Page 17: ...are a field installed option and no longer come standard from the factory Figure 8 TTA cooling only unit and matched indoor coil typical arrangement Notes 1 If the total length of the liquid line exce...

Page 18: ...1 For applications where the length of the liquid line exceeds 80 ft 24 m and the heat pump will start in the cooling mode remove the liquid line filter driers from the TWA heat pump and install new f...

Page 19: ...and one check valve See Table 3 p 26 and for recommendations 2 For applications where the length of the liquid line exceeds 80 ft 24 m and the heat pump will start in the cooling mode remove the liqui...

Page 20: ...s away from the coil by 1 inch per 10 feet 1 cm per 3 m 4 Use the DETINT to prevent oil and refrigerant migration when the unit is off The DETINT also serves to isolate the TXV bulb from suction heade...

Page 21: ...10 feet 1 cm per 3 m 4 Use the DETINT to prevent oil and refrigerant migration when the unit is off The DETINT also serves to isolate the TXV bulb from suction header conditions See Line Sizing Routi...

Page 22: ...xpansion valve 3 Pitch the gas line leaving the coil so that it slopes away from the coil by 1 inch per 10 feet 1 cm per 3 m 4 Use the DETINT to prevent oil and refrigerant migration when the unit is...

Page 23: ...e for each expansion valve 3 Pitch the gas line leaving the coil so that it slopes away from the coil by 1 inch per 10 feet 1 cm per 3 m 4 Use the DETINT to prevent oil and refrigerant migration when...

Page 24: ...m 4 Use the DETINT to prevent oil and refrigerant migration when the unit is off The DETINT also serves to isolate the TXV bulb from suction header conditions See Line Sizing Routing and Component Se...

Page 25: ...Unit TTA1804 D TTA1804 C TTA2404 D TTA2404 C TTA3004 C Refrigerant ckts 2 1 Manifold 2 1 Manifold 1 Manifold Minimum step tons 7 5 8 6 13 4 10 12 5 GAS LINE Tube diameter in Horizontal drops 1 1 8 1...

Page 26: ...products require two filters and two check valves one set oriented for liquid in the cooling direction and one set oriented for liquid in the heating direction For units with line lengths in excess o...

Page 27: ...urated at 90 F Discharge Saturated at 125 F Note When calculating refrigerant charge the first step is to determine the unit charge and if the unit charge includes the first 25 foot of pipe This infor...

Page 28: ...For more information please visit trane com or tranetechnologies com Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications...

Reviews: