Max Motor Speed [%]
Variable
name:
SNVT
type:
Default value:
Min value:
Max value:
nciMaxSpeed
SNVT_lev_percent
100 %
0 %
163.830%
This variable configures the maximum motor speed in % and associates it with par.4-13
Motor Speed High Limit
[RPM]
(par. 4-14 in Hz mode).
The value is entered as a percent of nominal speed, as defined by the Nominal Speed (nciNmlSpeed) configu-
ration value.
For more information on reference scaling, please refer to the
How to Control the TR200
section. If a value higher
than 163.830% is requested, use the parameter access command.
Min Motor Speed [%]
Variable
name:
SNVT
type:
Default value:
Min value:
Max value:
nciMinSpeed
SNVT_lev_percent
0 %
0 %
163.830%
This variable configures the minimum motor speed in % and associates it with par.4-11
Motor Speed Low Limit
[RPM]
(par. 4-12 in Hz mode).
The value is entered as a percent of nominal speed, as defined by the Nominal Speed (nciNmlSpeed) configu-
ration value.
For more information on reference scaling, please refer to the
How to Control the TR200
section.
Nom Motor Speed [RPM]
Variable
name:
SNVT
type:
Default value:
Min value:
Max value:
nciNmlSpeed
SNVT_rpm
1420 RPM
10 RPM
65,534 RPM
This variable configures the nominal motor speed in RPM and associates it with par.1-25
Motor Nominal
Speed
.
Please note that this variable can be adjusted only while the adjustable frequency drive is stopped.
If a value lower than 10 RPM is entered, nciNmlSpeed will be set to 10 RPM.
Nominal Motor Frequency [Hz]
Variable
name:
SNVT
type:
Default value:
Min value:
Max value:
nciNmlFreq
SNVT_freq_hz
50 Hz
20 Hz
100 Hz
This variable configures the nominal motor frequency and associates it with par.1-23
Motor Frequency
.
Please note that this variable can be adjusted only while the adjustable frequency drive is stopped.
Configuration of the system