Digital Inputs
Variable
name:
SNVT
type:
State:
nvoDigitInput
SNVT_state_64
Boolean 1 bit x 64
This variable contains the status of the digital inputs.
A logical 1 indicates that the input is on or active.
A logical 0 indicates that the input is off or inactive.
Bit 0
Digital Input Terminal 33
Bit 1
Digital Input Terminal 32
Bit 2
Digital Input Terminal 29
Bit 3
Digital Input Terminal 27
Bit 4
Digital Input Terminal 19
Bit 5
Digital Input Terminal 18
Bit 6
Reserved for future terminals
Bit 7
Digital Input GP I/O Terminal X30/2
Bit 8
Digital Input GP I/O Terminal X30/3
Bit 9
Digital Input GP I/O Terminal X30/4
Bit 10-63
Reserved for future terminals
Analog Input (53)
Variable
name:
SNVT
type:
Value:
nvoAnIn1
Changeable
Min.
Max.
Resolution:
SNVT_volt
0 V
10 V
0.1 V
SNVT_amp_mil
0 mA
20 mA
0.1 mA
SNVT_lev_percent
0 %
100 %
0.1%
This variable contains the value allocated to the analog input terminal 53.
This terminal can either be configured as a voltage input (0–10 V) or as a current input (0–20 mA), depending
on the setting of switch S 201. The variable type is changeable with the commissioning tool or LNS plug-in in
order to match the appropriate unit.
If the variable type of SNVT_lev_percent is selected, the relative scaling is from 0 V/mA to par.6-11
Terminal 53
High Voltage
or par.6-13
Terminal 53 High Current
Configuration of the system
TR200 LonWorks
5-13