UNT-IOM-6
75
Tracer
®
ZN.520
Table 28. Analog Inputs
Description
Terminals
Function
Range
Zone
TB3-1
Space temperature input
5° to 122°F (-15° to 50°C)
Ground
TB3-2
Analog ground
NA
Set
TB3-3
Setpoint input
40° to 115°F (4.4° to 46.1°C)
Fan
TB3-4
Fan switch input
4821 to 4919 W (Off)
2297 to 2342 W (Auto)
10593 to 10807 W (Low)
13177 to 13443 W (Medium)
15137 to 16463 W (High)
Ground
TB3-6
Analog ground
NA
Analog Input 1 J3-1
Entering water temperature
-40° to 212°F (-40° to 100°C)
J3-2
Analog ground
NA
Analog Input 2 J3-3
Discharge air temperature
-40° to 212°F (-40° to 100°C)
J3-4
Analog ground
NA
Analog Input 3 J3-5
Fresh air temp/Generic temp
-40° to 212°F (-40° to 100°C)
J3-6
Analog ground
NA
Analog Input 4 J3-7
Universal Input
0 100%
Generic 4-20ma
0 100%
Humidity
0 2000ppm
CO2
J3-8
Analog ground
NA
Ground J3-9
Analog ground NA
Notes:
1) The zone sensor, entering water temperature sensor, discharge air sensor, and the outside air tempera-
ture sensor are 10KW thermistors.
2) Zone sensor:
Wall mounted sensors include a thermistor soldered to the sensors circuit board.
Unit mounted sensors include a return air sensor in the units return air stream.
3) Changeover units include an entering water temperature sensor.
Analog Inputs