40
18-CE07D1-1C-EN
Setting Airflow
With all ductwork connected and a clean filter in place, measure the
External Static Pressure (ESP) of the unit in locations below. Use the
appropriate airflow table for the furnace and outdoor unit installed.
Measurements must be made prior to the evaporator coil, if equipped,
and after the filter.
Evaporator
Coil
Clean
Filter
Furnace Airflow (CFM) Vs. External Static Pressure (in. W.C.)
Model
Tap
0.1
0.3
0.5
0.7
0.9
L8X1B060U3PXAA
1
SCFM
829
689
549
410
270
Watts
83
95
107
119
130
2
SCFM
1087
985
884
782
681
Watts
163
179
195
210
226
3
SCFM
1210
1126
1043
959
876
Watts
211
228
245
262
279
4
SCFM
1238
1157
1076
995
914
Watts
227
244
261
278
295
5
SCFM
1481
1409
1338
1266
1195
Watts
381
399
417
435
453
E
Ex
xa
am
mp
plle
e 1
1:: S
S8
8B
B1
1 ((D
De
effa
au
ulltt T
Ta
ap
p 7
7))
Cooling / HP
•
2 Ton Single Stage Outdoor
•
Total ESP = 0.7” W.C.
•
Required Airflow = 1400 cfm (4T x 350 cfm/ton)
•
New Tap Number = Tap 6