System Start-up
RT-SVX35H-EN
75
Example
: If the voltage readings of the supply power
measured 221, 230, and 227, the average volts would be:
The percentage of Imbalance equals:
The 2.2% imbalance in this example exceeds the
maximum allowable imbalance of 2.0%. This much
imbalance between phases can equal as much as a 20%
current imbalance with a resulting increase in motor
winding temperatures that will decrease motor life. If the
voltage imbalance is over 2%, notify the proper agencies
to correct the voltage problem before operating this
equipment.
221 + 230 + 227 = 226 Avg.
3
VD (reading farthest from average) = 221
100 X 226 - 221 = 2.2%
226
Table 20. Service test guide for component operation
COMPONENT
BEING TESTED
COMPONENT CONFIGURATION
Occ
Unocc
Relay
(a)
Supply
Fan
Exhaust
Fan
Heat Stages
Econo
Damper
Exhaust
Damper
VFD
Output
1
2
3
SUPPLY FAN*
On
Off
Off
Off
Off
Closed
Closed
100%
Unocc
EXHAUST FAN
Off
On
Off
Off
Off
Closed
100%
Open
100%
Default
GAS HEAT (Full Cap.)
On
Off
On
On
N/A
Closed
Closed
100%
Unocc
Stage 1
On
Off
On
Off
N/A
Closed
Closed
100%
Unocc
Stage 2
On
Off
Off
On
N/A
Closed
Closed
100%
Unocc
Full Modulating
(For High Fire Adjustment)
On
Off
90%
Select
Closed
Closed
100%
Unocc
Full Modulating
(For Low Fire Adjustment)
On
Off
5% Select
Closed
Closed
100%
Unocc
Limited Modulating
(For High Fire Adjustment)
On
Off
90%
Select
Closed
Closed
100%
Unocc
Limited Modulating
(For Low Fire Adjustment)
On
Off
33%
Select
Closed
Closed
100%
Unocc
ELECT HEAT (Full Cap.)
On
Off
On
On
On
Closed
Closed
100%
Unocc
Stage 1
On
Off
On
Off
Off
Closed
Closed
100%
Unocc
Stage 2
On
Off
Off
On
Off
Closed
Closed
100%
Unocc
Stage 3
On
Off
Off
Off
On
Closed
Closed
100%
Unocc
Modulating
Hydronic Heat
Off
Off
100%
Select
Closed
Closed
0%
Default
Pre - Heater
Off
Off
On
N/A
N/A
Closed
Closed
0%
Default
Fresh Air Dampers
Off
Off
Off
Off
Off
100%
Open
Closed
0%
Default
Exhaust Dampers
Off
Off
Off
Off
Off
100%
100%
Open
0%
Default
(a) RTM OCC/UNOCC output in the Service Test Mode must be in the unoccupied mode to open the system VAV boxes or
to drive the VFD to 100%.
Summary of Contents for IntelliPak WEHE Series
Page 15: ...General Information RT SVX35H EN 15 Figure 1 Unit component layout and ship with locations...
Page 17: ...Installation RT SVX35H EN 17 Figure 2 Typical control module location...
Page 44: ...Installation 44 RT SVX35H EN Figure 27 Typical field power wiring for W_HE casings 2 through 6...
Page 56: ...Installation 56 RT SVX35H EN Figure 32 Wiring notes for CV controls...
Page 60: ...Installation 60 RT SVX35H EN Figure 35 Wiring notes VAV...
Page 68: ...System Start up 68 RT SVX35H EN Figure 38 Typical fenwall ignition control system...
Page 69: ...System Start up RT SVX35H EN 69 Figure 39 Typical Fenwall ignition control system...