SCXF-SVX01B-EN
53
Programming
Installation
Table I-P-2. Zone Sensor BAYSENS020 Option Menu Settings.
Option #
Description
Value
Factory Setting
1
Morning Warm-up
0 = Disabled
0
1 = Enabled
2
Economizer minimum
0 = Disabled
1
Position override
1 = Enabled
3
Temperature Scale
0 = Fahrenheit
0
1 = Enabled
4
Heat Installed
0 = No
0
1 = Yes
5
Time Clock
0 = 12 hours
0
1 = 24 hours
6
Hydronic Heat
0 = No
0
1 = Yes
7
Daytime Warmup
0 = Disabled
0
1 = Enabled
8
Programmable Days/Week
0 = 7 days (M,T,W,T,F,S,S)
0
1 = 3 days (M-F, S, S)
2 = 2 days (M-F, S,S)
9
Programmable Periods/Day
2,3,4
4
10
Remote Sensor Installed
0 = No
0
1 = Yes
11
Check Filter Interval
0 = Disabled
350
3000 to 50 in 50 hour
increments
12
Display Zone Temperature
0 = No
1
1 = Yes
13
Keypad Lockout Enabled
0 = Disabled
1
1 = Enabled
14
Initial Time Setting in Temporary
1,2,3,4,5
3
Override Mode (hrs.)
15
Buzzer Options
0 = Key Press only
1
1 = Key Press & Check filter
2 = Key Press, Check Filter,
and System Failures
16
Zone Temperature Calibration
Displays current temp.
0 offset
with any offsets
17
Default Cooling Setpoint
45 to 98 F (unoccupied)
74 F
18
Default Heating Setpoint
43 to 96 F (unoccupied)
68 F
19
Default Supply Air Cool
40 to 80 F (occupied)
55 F
20
Default Supply Air Heat
60 to 160 F
100 F
21
Default Warmup
50 to 90 F (occupied)
68
22
Minimum Cooling Setpoint
45 to 98 F
45 F
23
Maximum Heating Setpoint
43 to 96 F
96 F
24
Minimum Supply Air Cool
40 to 80 F (occupied)
40 F
25
Maximum Supply Air Heat
60 to 160 F
160 F
26
Maximum Warmup
50 to 90 F
90 F
Note: On both programmable zone sensor
options, changing either option 9 or 10 will
erase the current program. To avoid
reprogramming, set options 9 and 10
before programming.
Intelligent Copy
Note:
Once you have used Intelligent
Copy, you cannot use it again until you
erase all weekday and weekend time
periods by pressing ERASE for 5 seconds.
If your heating and cooling requirements
are the same for each day of the week,
and for each day of the weekend, your
ZSM is designed to employ Intelligent
Copy.
To program the five weekdays, Monday
through Friday, program only one
weekday. Likewise, to program the
weekend, Saturday and Sunday, pro-
gram only one day. After programming
one weekday and/or one weekend day,
Intelligent Copy automatically copies your
program to the other days.
To use Intelligent Copy:
1) Be sure to select the seven day
programming format in the Options
Menu. See Tables I-P-1 and I-P-2.
2) Be sure the entire program is blank.
3) Go to Program Menu.
4) Enter your setpoint parameters.
Intelligent Copy will automatically copy
these parameters to the other
weekdays.
5) Depress the DAY pushbutton until a
weekend day icon appears.
6) Enter setpoint parameters. Intelligent
Copy will automatically copy these
parameters to the other weekend day.
Remote Panel Indicator Signals From
UCM to ZSM
The unit control module (UCM) can send
four signals to the ZSM.
• Heat
• Cool
• On
• Service
Each of these four signals have three
different conditions. See Table I-P-3.
• Off
• On
• Flashing
Table I-P-3. UCM Signal Conditions.
Signal
Condition
Heat
On
FlashingHEAT is ON and indicated by a solid HEAT icon in the
Display. Failure in the cooling system indicated by a flashing COOL
FAIL icon.
Cool
On
FlashingCOOLING is ON and indicated by a solid COOL icon in the
Display. Failure in the cooling system indicated by a flashing
COOL FAIL icon.
On
Off
FlashingSystem is OFF and indicated by a solid colon on the time of
On
day display. System is ON and indicated by a flashing colon on
the time of day display. System is in TEST mode and indicated by a
flashing TEST icon.
Service
Flashing
ON System requires service and is indicated by a solid SERVICE
icon. There is a FAN failure indicated by a flashing SERVICE icon.
Note: There is no indication for a signal in the OFF condition. If Option 16 is set to “2,” any flashing signals will
also give audible buzzer indication