52
SCXF-SVX01B-EN
Table I-P-1. Zone Sensor BAYSENS019 Option Menu Settings.
Option #
Description
Value
Factory Setting
1
Morning Warm-up
0 = Disabled
0
1 = Enabled
2
Economizer minimum
0 = Disabled
1
Position override
1 = Enabled
3
Temperature Scale
0 = Fahrenheit
0
1 = Enabled
4
Supply Air Tempering
0 = Disabled
0
1 = Enabled
5
Time Clock
0 = 12 hours
0
1 = 24 hours
6
Smart Fan
0 = Disabled
1
1 = Enabled
7
Intelligent Temperature Recovery
0 = Disabled
0
1 = Enabled
8
Programmable Days/Week
0 = 7 days (M,T,W,T,F,S,S)
0
1 = 3 days (M-F, S, S)
2 = 2 days (M-F, S,S)
9
Programmable Periods/Day
2,3,4
4
10
Programmable Fan Operation
0 = Disallowed
0
1 = Allowed
11
Remote Sensor Installed
0 = No
0
1 = Yes
12
Check Filter Interval
0 = Disabled
350
3000 to 50 in 50 hour
increments
13
Display Zone Temperature
0 = No
1
1 = Yes
14
Keypad Lockout Enabled
0 = Disabled
1
1 = Enabled
15
Initial Time Setting in Temporary
1,2,3,4,5
3
Override Mode (hrs.)
16
Buzzer Options
0 = Key Press only
1
1 = Key Press & Check filter
2 = Key Press, Check Filter,
and System Failures
17
Zone Temperature Calibration
Displays current temp.
0 offset
with any offsets
18
Baud Rate
0 = 1024 baud
1
1 = 1200 baud
19
CV or HP Operation
0 = CV
0
1 = HP
20
Default Cooling setpoint
45 to 98 F
74 F
21
Default Heating setpoint
43 to 96 F
68 F
22
Minimum Cooling Setpoint
45 to 98 F
45 F
23
Maximum Heating Setpoint
43 to 96 F
96 F
Programming
Installation
Figure I-P-8. Typical option menu screen.
Option Menu and Keypad Operation
The operation menu sets all
programmable options built into your
ZSM. All options are retained in
permanent EEPROM memory.
To access the option menu display,
simultaneously depress and hold the
mode button and program button for four
seconds.
The example in Figure I-P-8 shows option
15 displayed and indicates the initial timer
setting in the temporary override run
mode. The option value shown is in
hours, and value selected is five hours.
When the option menu displays, the only
active buttons are the
↑
or
↓
arrow and
the “minus” and “plus” button. The
↑
or
↓
arrow increment through the available
options by number (1-24), and the
“minus” and “plus” button toggles
through the various option values
associated with each option number. See
Table I-P-1.
Note: On both programmable zone sensor
options, changing either option 9 or 10 will
erase the current program. To avoid
reprogramming, set options 9 and 10
before programming.
Figure I-P-7. Temporary manual override run
mode screen.