TWE5-PRC001-EN-10-15-99
19
Performance
Data Heating
Metric Units
TWJ030CA WITH TWE040CA4-B AT 1868 CMH
O.D.
HEATING CAPACITY IN KILOWATTS AT
TOTAL POWER IN KILOWATTS AT
TEMP.
INDICATED INDOOR DRY BULB TEMP.
INDICATED INDOOR DRY BULB TEMP.
C.
15.6
21.1
23.9
26.7
15.6
21.1
23.9
26.7
-27.8
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
-25.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
-22.2
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
-19.4
2.8
2.7
2.7
2.7
2.1
2.2
2.3
2.4
-16.7
3.4
3.3
3.3
3.3
2.2
2.3
2.4
2.4
-13.9
4.0
3.9
3.9
3.8
2.3
2.4
2.5
2.5
-11.1
4.6
4.5
4.5
4.4
2.3
2.5
2.5
2.6
-8.3
5.2
5.1
5.1
5.0
2.4
2.5
2.6
2.7
-5.6
5.5
5.4
5.4
5.3
2.5
2.6
2.7
2.8
-2.8
5.8
5.7
5.7
5.6
2.5
2.7
2.8
2.8
0.0
6.2
6.0
5.9
5.9
2.6
2.8
2.8
2.9
2.8
6.4
6.3
6.2
6.2
2.7
2.8
2.9
3.0
5.6
6.8
6.6
6.5
6.5
2.7
2.9
3.0
3.1
8.3
8.9
8.7
8.6
8.5
2.8
3.0
3.1
3.2
11.1
9.5
9.3
9.2
9.1
2.9
3.1
3.2
3.3
13.9
10.1
9.9
9.8
9.7
3.0
3.2
3.2
3.3
16.7
10.8
10.5
10.4
10.3
3.0
3.2
3.3
3.4
19.4
11.4
11.1
11.0
10.9
3.1
3.3
3.4
3.5
22.2
12.0
11.7
11.6
11.5
3.2
3.4
3.5
3.6
CORRECTION FACTORS - OTHER AIRFLOWS
(VALUE AT 1868 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1656
2165
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1910 CMH
HEATING CAP. (HIGH TEMP.) = 8.73 KW
HEATING CAP. (LOW TEMP.) = 5.13 KW
COMPR. POWER (HIGH TEMP.) = 2504 WATTS
COMPR. POWER (LOW TEMP.) = 2047 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.92
COEFF. OF PERF. (LOW TEMP.) = 2.00
OUTDOOR FAN POWER = 195 WATTS
INDOOR FAN POWER = 300 WATTS
NOTE: RATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE
TWJ036CA WITH TWE030CA4 AT 1868 CMH
O.D.
HEATING CAPACITY IN KILOWATTS AT
TOTAL POWER IN KILOWATTS AT
TEMP.
INDICATED INDOOR DRY BULB TEMP.
INDICATED INDOOR DRY BULB TEMP.
C.
15.6
21.1
23.9
26.7
15.6
21.1
23.9
26.7
-27.8
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
-25.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
-22.2
2.4
2.4
2.4
2.4
2.0
2.1
2.1
2.2
-19.4
3.2
3.1
3.1
3.0
2.1
2.2
2.3
2.3
-16.7
3.9
3.8
3.8
3.8
2.3
2.4
2.4
2.5
-13.9
4.6
4.5
4.5
4.5
2.4
2.5
2.5
2.6
-11.1
5.4
5.2
5.2
5.1
2.5
2.6
2.7
2.7
-8.3
6.1
5.9
5.9
5.8
2.6
2.8
2.8
2.9
-5.6
6.4
6.3
6.2
6.2
2.7
2.8
2.9
3.0
-2.8
6.8
6.7
6.6
6.5
2.8
2.9
3.0
3.1
0.0
7.1
7.0
6.9
6.8
2.9
3.0
3.1
3.2
2.8
7.5
7.3
7.2
7.2
3.0
3.1
3.2
3.3
5.6
7.8
7.7
7.6
7.5
3.1
3.2
3.3
3.4
8.3
10.4
10.2
10.1
10.0
3.4
3.5
3.6
3.7
11.1
11.2
10.9
10.8
10.7
3.5
3.7
3.8
3.9
13.9
11.9
11.7
11.5
11.4
3.6
3.8
3.9
4.0
16.7
12.6
12.4
12.2
12.1
3.8
4.0
4.1
4.2
19.4
13.4
13.1
13.0
12.8
3.9
4.1
4.2
4.3
22.2
14.1
13.8
13.7
13.5
4.0
4.2
4.3
4.4
CORRECTION FACTORS - OTHER AIRFLOWS
(VALUE AT 1868 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1656
2165
HEATING CAP.
X0.99
X1.02
COMPR. KW
X1.02
X0.97
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1910 CMH
HEATING CAP. (HIGH TEMP.) = 10.25 KW
HEATING CAP. (LOW TEMP.) = 5.98 KW
COMPR. POWER (HIGH TEMP.) = 2776 WATTS
COMPR. POWER (LOW TEMP.) = 1982 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.88
COEFF. OF PERF. (LOW TEMP.) = 2.16
OUTDOOR FAN POWER = 235 WATTS
INDOOR FAN POWER = 540 WATTS
NOTE: RATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE
TWJ036CA WITH TWE040CA4-B AT 2378 CMH
O.D.
HEATING CAPACITY IN KILOWATTS AT
TOTAL POWER IN KILOWATTS AT
TEMP.
INDICATED INDOOR DRY BULB TEMP.
INDICATED INDOOR DRY BULB TEMP.
C.
15.6
21.1
23.9
26.7
15.6
21.1
23.9
26.7
-27.8
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
-25.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
-22.2
2.3
2.2
2.2
2.2
1.8
1.9
2.0
2.0
-19.4
3.0
3.0
2.9
2.9
1.9
2.0
2.1
2.2
-16.7
3.8
3.7
3.7
3.6
2.0
2.2
2.2
2.3
-13.9
4.5
4.5
4.4
4.4
2.2
2.3
2.3
2.4
-11.1
5.3
5.2
5.2
5.1
2.3
2.4
2.5
2.5
-8.3
6.1
5.9
5.9
5.8
2.4
2.5
2.6
2.6
-5.6
6.4
6.3
6.2
6.2
2.4
2.6
2.7
2.7
-2.8
6.8
6.7
6.6
6.6
2.5
2.7
2.7
2.8
0.0
7.2
7.1
7.0
6.9
2.6
2.7
2.8
2.9
2.8
7.6
7.4
7.4
7.3
2.7
2.8
2.9
3.0
5.6
8.0
7.8
7.7
7.6
2.7
2.9
3.0
3.1
8.3
10.6
10.4
10.3
10.2
3.0
3.2
3.3
3.4
11.1
11.4
11.2
11.0
10.9
3.1
3.3
3.4
3.5
13.9
12.2
11.9
11.8
11.6
3.2
3.4
3.5
3.6
16.7
12.9
12.6
12.5
12.4
3.3
3.5
3.6
3.7
19.4
13.7
13.4
13.2
13.1
3.4
3.6
3.7
3.8
22.2
14.4
14.1
14.0
13.8
3.5
3.8
3.8
4.0
CORRECTION FACTORS - OTHER AIRFLOWS
(VALUE AT 2378 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1995
2590
HEATING CAP.
X0.98
X1.01
COMPR. KW
X1.03
X0.99
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 2293 CMH
HEATING CAP. (HIGH TEMP.) = 10.37 KW
HEATING CAP. (LOW TEMP.) = 5.92 KW
COMPR. POWER (HIGH TEMP.) = 2590 WATTS
COMPR. POWER (LOW TEMP.) = 1906 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.24
COEFF. OF PERF. (LOW TEMP.) = 2.36
OUTDOOR FAN POWER = 235 WATTS
INDOOR FAN POWER = 360 WATTS
NOTE: RATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE