14
TWE5-PRC001-EN-10-15-99
Performance
Data Cooling
English Units
TWA040CD WITH TWE050CA5-C AT 1500 CFM
(CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
I.D.
TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
D.B.
W.B.
CAP.
72
74
76
78
80
KW
59
40.1
33.2
35.9
38.6
40.6*
41.5*
2.78
85
63
43.1
28.0
30.7
33.3
36.0
38.7
2.89
67
46.1
22.2
24.9
27.5
30.2
32.9
3.01
71
49.3
16.3
18.9
21.6
24.3
27.0
3.13
59
39.1
32.8
35.5
38.2
39.8*
40.7*
2.91
90
63
42.0
27.5
30.2
32.9
35.6
38.2
3.02
67
44.9
21.7
24.4
27.1
29.8
32.4
3.14
71
48.0
15.8
18.5
21.2
23.8
26.5
3.27
59
38.1
32.4
35.0
37.7
38.9*
39.8*
3.04
95
63
40.9
27.1
29.8
32.4
35.1
37.8
3.15
67
43.7
21.3
24.0
26.6
29.3
32.0
3.28
71
46.7
15.4
18.0
20.7
23.4
26.1
3.41
59
37.0
31.9
34.6
37.2*
38.0*
38.9*
3.16
100
63
39.7
26.6
29.3
32.0
34.6
37.3
3.29
67
42.5
20.8
23.5
26.2
28.8
31.5
3.41
71
45.3
14.9
17.6
20.2
22.9
25.6
3.55
59
35.9
31.4
34.1
36.3*
37.1*
37.9*
3.30
105
63
38.5
26.1
28.8
31.5
34.2
36.8
3.42
67
41.2
20.3
23.0
25.7
28.4
31.0
3.55
71
44.0
14.4
17.1
19.8
22.4
25.1
3.69
59
33.6
30.5
33.2
34.4*
35.2*
36.0*
3.56
115
63
36.1
25.2
27.9
30.6
33.2
35.9
3.69
67
38.6
19.4
22.1
24.7
27.4
30.1
3.82
71
41.2
13.5
16.2
18.8
21.5
24.2
3.96
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
1325
1700
TOTAL CAP.
X0.99
X1.01
SENS. CAP.
X0.95
X1.06
COMPR. KW
X0.99
X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 43800 BTUH
AIRFLOW = 1500 CFM
COMPRESSOR POWER = 3279 WATTS
I.D. FAN POWER = 510 WATTS
O.D. FAN POWER = 244 WATTS
E.E.R. = 10.30 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
TWA050CD WITH TWE050CA5-C AT 1800 CFM
(CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
I.D.
TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
D.B.
W.B.
CAP.
72
74
76
78
80
KW
59
48.8
39.6
42.7
45.8
49.0*
50.1*
3.60
85
63
52.3
33.4
36.5
39.6
42.7
45.9
3.72
67
55.9
26.6
29.7
32.8
35.9
39.0
3.84
71
59.6
19.6
22.7
25.8
29.0
32.1
3.96
59
47.6
39.1
42.2
45.3
48.0*
49.1*
3.77
90
63
51.0
32.9
36.0
39.1
42.2
45.3
3.88
67
54.5
26.0
29.2
32.3
35.4
38.5
4.00
71
58.1
19.1
22.2
25.3
28.4
31.5
4.13
59
46.4
38.5
41.6
44.8
47.0*
48.1*
3.93
95
63
49.7
32.3
35.5
38.6
41.7
44.8
4.05
67
53.1
25.5
28.6
31.7
34.9
38.0
4.17
71
56.6
18.6
21.7
24.8
27.9
31.0
4.30
59
45.1
38.0
41.1
44.2
45.9*
46.9*
4.10
100
63
48.2
31.8
34.9
38.0
41.1
44.2
4.21
67
51.5
24.9
28.1
31.2
34.3
37.4
4.33
71
54.9
18.0
21.1
24.2
27.3
30.4
4.46
59
43.7
37.4
40.5
43.6
44.8*
45.8*
4.27
105
63
46.8
31.2
34.3
37.4
40.5
43.7
4.38
67
50.0
24.4
27.5
30.6
33.7
36.8
4.50
71
53.2
17.4
20.5
23.6
26.8
29.9
4.62
59
41.1
36.3
39.4
41.6*
42.5*
43.5*
4.61
115
63
43.9
30.1
33.2
36.3
39.4
42.5
4.71
67
46.9
23.2
26.3
29.5
32.6
35.7
4.83
71
49.9
16.3
19.4
22.5
25.6
28.7
4.94
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
1575
2025
TOTAL CAP.
X0.99
X1.01
SENS. CAP.
X0.95
X1.05
COMPR. KW
X0.99
X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 53100 BTUH
AIRFLOW = 1800 CFM
COMPRESSOR POWER = 4171 WATTS
I.D. FAN POWER = 750 WATTS
O.D. FAN POWER = 255 WATTS
E.E.R. = 9.65 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
TWA060CD WITH TWE050CA5-C AT 1800 CFM
(CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
I.D.
TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
D.B.
W.B.
CAP.
72
74
76
78
80
KW
59
57.2
43.7
46.8
50.0
53.1
56.3
4.61
85
63
61.6
37.6
40.7
43.9
47.0
50.2
4.77
67
66.1
30.8
34.0
37.1
40.2
43.4
4.93
71
70.8
23.8
27.0
30.1
33.3
36.4
5.10
59
55.9
43.1
46.3
49.4
52.6
55.7
4.80
90
63
60.1
37.0
40.2
43.3
46.5
49.6
4.96
67
64.6
30.2
33.4
36.5
39.7
42.8
5.13
71
69.1
23.2
26.4
29.5
32.7
35.8
5.30
59
54.6
42.5
45.7
48.8
52.0
55.0*
5.00
95
63
58.7
36.4
39.6
42.7
45.9
49.0
5.16
67
63.1
29.6
32.8
35.9
39.1
42.2
5.33
71
67.5
22.7
25.8
29.0
32.1
35.3
5.50
59
53.2
41.9
45.1
48.2
51.4
53.8*
5.23
100
63
57.2
35.8
38.9
42.1
45.2
48.4
5.38
67
61.4
29.0
32.1
35.3
38.4
41.6
5.55
71
65.8
22.0
25.2
28.3
31.5
34.6
5.71
59
51.8
41.3
44.4
47.6
50.7
52.7*
5.45
105
63
55.7
35.2
38.3
41.5
44.6
47.8
5.61
67
59.8
28.4
31.5
34.7
37.8
40.9
5.77
71
64.0
21.4
24.5
27.7
30.8
34.0
5.93
59
48.9
40.1
43.2
46.3
49.3*
50.4*
5.91
115
63
52.6
33.9
37.1
40.2
43.4
46.5
6.06
67
56.5
27.1
30.2
33.4
36.5
39.7
6.20
71
60.5
20.1
23.3
26.4
29.6
32.7
6.36
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
1575
2025
TOTAL CAP.
X0.98
X1.01
SENS. CAP.
X0.95
X1.05
COMPR. KW
X0.99
X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 63100 BTUH
AIRFLOW = 1800 CFM
COMPRESSOR POWER = 5326 WATTS
I.D. FAN POWER = 750 WATTS
O.D. FAN POWER = 395 WATTS
E.E.R. = 9.20 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.