background image

Electrical Installation 

Electrical Installation  

All wiring and grounding must comply with local electrical codes.  

Wiring Important Safeguards:  

- Check the unit nameplate for electrical rating. Be sure wiring is done according to local codes and wiring diagram.  

- Use a separate power line with circuit breaker for each air conditioning unit.  

- Connect electrical ground to all units.  

- Wiring should not touch refrigerant tubing, compressor, motors or moving parts.  

- The manufacturer will accept no responsibility for problems caused by unauthorized changes in the internal wiring.  

- Connect the wiring firmly.  

Indoor Unit  

Remove the right side junction box (see previous instructions) to access the terminal base.  

System Wiring Routing  

- Pass the system wiring through the PVC pipe, referred to in the Section of Installation Method 

(both power and control lines) to interconnect indoor and outdoor units.  

- Connect the wire terminals to the terminal base. See connection indication on system wiring diagram.  

- Make sure all connections are tight.  

Outdoor Unit  

See the electrical installation instructions in the Installation Manual for the Outdoor Unit.

Caution

In order to avoid a hazard due to inadvertent resetting of the thermal cut-out, this appliance must not be supplied through 

an external switching device, such as a timer, or connected to a circuit that is regularly switched on and off by the utility. 

Dimensional Data  

Dimensional Data  

Figure 13

Figure 14

Figure 15

Condensate Drain Piping  

1. The drain hose should run straight down the wall to a level where the run 

off will not stain the wall.  

2. These should be no water traps. Avoid putting the end of the hose in 

water.  

3. To conveniently drain the system, the drain piping must slant downward, 

with a slope of at least 1:50 to prevent leakage.

4. When the drain hose is placed in the room, insulate the hose with foam 

polyethylene to avoid damage to the ceiling or furniture.  

5. After completing installation of refrigerant lines, wiring and drain 

connections, bind the tubing, wiring and drain piping (check if local codes 

permit binding) into a bundle by using tape at 100 or 200 mm (4" to 8") 

intervals. Make sure the drain tube is at the bottom of the bundle 

(Figure 16). 

Figure 16

Wiring Diagram

REMOVE HI-BR WIRE FROM TB-1 AND REPLACE

WITH EXTRA HI-BLK WIRE WHEN HI SPEED/CFM

6

5

1

0

6

4

WHT

COM

WHT

WHT

RED

EXTRA-HI

BLOWER

MOTOR

BLK

For 4 speeds only

BLU

BRW

MED

HI

RED

LOW

IS REQUIRED IN THE FIELD.

FACTORY WIRING

FIELD WIRING

220-240V/1PH/60Hz

POWER SUPPLY

220-240V/1PH/50Hz

L

220-240 VAC

CONTROL WIRING

TO CONDENSING UNIT.

LEGEND :

LEGEND :

C1

N

C2

2. ENSURE THAT POWER SUPPLY AGREES WITH

3. USE ONLY COPPER CONDUCTORS.

MUST COMPLY WITH LOCAL CODES.

EQUIPMENT NAME PLATE.

1. POWER WIRING AND GROUDING OF EQUIPMENT

NOTES :

TO HEATING

TO COOLING

WHT

WHT

A

B

COOL

SWITCH

COOLING - HEATING

HEAT

h

THERMOSTAT

OFF

LOW

3 SPEED 

SWITCH

HI

MED

HEATER

MANUAL RESET

AUTO RESET

4

3

2

1

Maintenance

Regular Maintenance

Be sure to disconnect the power before inspection or maintenance air conditioner.

1. Cleaning the air filter

   Air flow is reduced and cooling efficiency impaired if the filter is clogged. Be sure to clean the filter every two weeks 

during the cooling season.

1.1 Remove air filters to side

  - Slide air filter to left or right side.

1.2 Remove air filters to bottom

  - Loose screws located under the filters at return air plenum set.

  - Remove air filter frame and pull air filter down.

How to clean the air filter

    - Wash away dust from the air filters with clean water or vacuum it  

  with an electric vacuum cleaner 

Note:

 Once the air filter is washed, dry it completely before returning it  

 

to its original position.

 

After cleaning be sure to return it to its original position.

Cautions

- Do not wash the air filter in water that is over 40 

C or it may shrink.

- Do not expose the air filter to fire.

- Do not expose the air filter to direct sunlight for a long time when the 

air is very dirty.

- Clean the air filter more frequently.

- Do not inject water into motor

บริษัท

 

แอมแอร

 

จำกัด

999/1 

หมูที่

 9 

ถนนบางนา

-

ตราด

 

กม

.19 

ตำบลบางโฉลง

 

อำเภอบางพลี

 

จังหวัดสมุทรปราการ

 10540

Trane
www.trane.com

For more information, contact your locat district office

Literature Order Number:  MS-SVN004-EN

Date: February 

2011

Supersedes November 

2014

Stocking Location: 

Bangkok, Thailand 

Trane has a policy of continuous product and product data improvement and reserves the right 

to change design and specifications without notice.

CONCEALED DX AIR HANDLER 

COOLING-HEATING 

MCD 512-524 DB/D1

MCDA 18-A24 DB/D1

Wiring Diagram

Wiring Diagram

THERMOSTAT

EQUIPMENT NAME PLATE.

3. USE ONLY COPPER CONDUCTORS.

MUST COMPLY WITH LOCAL CODES.

2. ENSURE THAT POWER SUPPLY AGREES WITH

1. POWER WIRING AND GROUDING OF EQUIPMENT

HEATER THERMAL OVERLOAD PROTECTOR

(MAX.20AMP. NON-INDUCTIVE FULL LOAD CURRENT)

HEATER#1

HEATER#2

4

6

8

0

1

2

FACTORY WIRING

FIELD WIRING

LEGEND :

LEGEND :

L

N

220-240V/1pH/50Hz

220-240V/1pH/60Hz

POWER SUPPLY

WHT

WHT

WHT

A

TO CONDENSING UNIT.

CONTROL WIRING

220-240 VAC

C2

C1

NOTES :

COOLING - HEATING

SWITCH

COOL

h

TO COOLING

with EXTRA HI-BLK wire when high speed/cfm

Remove HI-BR wire FROM TB-1 and replace 

BLK

For 4 speeds only

EXTRA-HI

MOTOR

BLOWER

WHT

WHT

RED

BRW

BLU

B

HI

COM

LOW

MED

WHT

RED

is required in the field.

HEAT

TO HEATING

0350374C

3 SPEED 

SWITCH

LOW

OFF

HI

MED

MANUAL RESET#1

MANUAL RESET#2

AUTO RESET#2

AUTO RESET#1

5

3

4

1

2

6

CONCEALED FAN COIL UNITS 

COOLING-HEATING 

MCD 530-536 DB/D1 

MCD 048-060 DB/D1

MCDA 30-A36 DB/D1

MCDB 42-B60 DB/D1 

MS_SVN004_EN.indd   2

MS_SVN004_EN.indd   2

21-Nov-14   10:29:58

21-Nov-14   10:29:58

Reviews: