40
MUA-SVX004B-EN
from the locating slot while retaining spring is still compressed. Pull the burners upward and
out.
7. Remove any dirt, dust or other foreign matter from the burners using a wire brush and/or
compressed air. Ensure that all parts are unobstructed. Inspect and clean pilot burner if
necessary.
8. Reassemble the gas duct furnace by replacing all parts in order.
9. Complete the appropriate unit start-up procedure as given in the “Start-Up” section of this
manual.
10. Check the burner adjustment. See the “Primary Air Shutter Adjustment” chapter of this
manual.
11. Check all gas control valves and pipe connections for leaks.
W
WA
AR
RN
NIIN
NG
G
C
Co
om
mb
bu
ussttiib
blle
e M
Ma
atte
erriia
allss!!
F
Fa
aiillu
urre
e tto
o m
ma
aiin
ntta
aiin
n p
prro
op
pe
err cclle
ea
arra
an
ncce
e b
be
ettw
we
ee
en
n tth
he
e u
un
niitt a
an
nd
d cco
om
mb
bu
ussttiib
blle
e m
ma
atte
erriia
allss cco
ou
ulld
d
cca
au
usse
e a
a ffiirre
e w
wh
hiicch
h cco
ou
ulld
d rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss iin
njju
urry
y o
orr p
prro
op
pe
errtty
y d
da
am
ma
ag
ge
e..
R
Re
effe
err tto
o u
un
niitt n
na
am
me
ep
plla
atte
e a
an
nd
d iin
nsstta
alllla
attiio
on
n iin
nssttrru
uccttiio
on
nss ffo
orr p
prro
op
pe
err cclle
ea
arra
an
ncce
ess..
12. Check the operation of the automatic gas valve by lowering the setting of the thermostat,
stopping the operation of the gas duct furnace. The gas valve should close tightly, completely
extinguishing the flame on the main burners.
13. Check the operation of all safety devices.
14. Inspect and service the blower section of the system.
•
The outdoor unit should be thoroughly checked before the start of the heating season. Check
the air through-put as an added precaution to stay within the specified temperature limits.
•
If the unit is used with cooling equipment, periodic maintenance should be scheduled
throughout the year.