WSHP-SVN08B-EN
21
Table OP-1: Operating Pressures
GENERAL: There are many variables (airflow, air temperatures) in an air conditioning system that will affect operating re-
frigerant pressures and temperatures. The chart below shows approximate conditions and is based on air flow at the rated
SCFM, entering air at 80.6 °FDB, 66.2 °FWB in cooling, 68 °FDB in heating. (+)Heating data with 35 °F EWT is based on the
use of an anti-freeze solution having a freezing point 20 °F lower than the minimum expected entering temperature.
Operating Data
Model
Entering
Water
Temp, °F
Water
Flow
GPM
Cooling
Heating
Suction
Pressure,
PSIG
Discharge
Pressure,
PSIG
Water
Temp
Rise, °F
Air Temp
Drop,
°FDB
Suction
Pressure,
PSIG
Discharge
Pressure,
PSIG
Water
Temp
Drop, °F
Air Temp
Rise,
°FDB
GET 009
35
1.8
46 - 52
158 - 201
5 - 6
11 - 15
GET 009
35
2.25
46 - 53
159 - 203
4 - 5
12 - 15
GET 009
45
1.8
68 - 78
100 - 127
11 - 14
11 - 15
55 - 63
171 - 218
6 - 7
13 - 17
GET 009
45
2.25
68 - 78
97 - 123
9 - 11
12 - 15
56 - 65
172 - 219
5 - 6
14 - 18
GET 009
55
1.8
70 - 80
117 - 148
11 - 14
11 - 14
65 - 75
182 - 231
7 - 9
15 - 19
GET 009
55
2.25
70 - 80
113 - 144
9 - 11
12 - 15
66 - 76
183 - 233
6 - 7
16 - 20
GET 009
68
1.8
73 - 84
142 - 180
10 - 13
11 - 14
78 - 90
193 - 246
8 - 10
18 - 22
GET 009
68
2.25
73 - 84
138 - 176
9 - 11
12 - 15
79 - 91
195 - 248
7 - 9
18 - 23
GET 009
75
1.8
75 - 86
157 - 199
10 - 13
11 - 14
85 - 98
201 - 256
9 - 11
19 - 24
GET 009
75
2.25
74 - 86
153 - 195
8 - 11
11 - 15
87 - 100
202 - 257
7 - 9
19 - 25
GET 009
86
1.8
77 - 88
183 - 233
10 - 13
11 - 14
96 - 110
208 - 265
10 - 13
21 - 26
GET 009
86
2.25
76 - 88
179 - 227
8 - 11
11 - 15
98 - 113
209 - 266
8 - 10
21 - 27
GET 009
95
1.8
78 - 90
206 - 262
10 - 13
11 - 14
GET 009
95
2.25
78 - 90
202 - 257
8 - 10
11 - 14
GET 012
35
2.5
44 - 50
160 - 204
5 - 6
19 - 24
GET 012
35
3.1
45 - 51
162 - 206
4 - 5
19 - 24
GET 012
45
2.5
68 - 78
106 - 135
10 - 13
18 - 23
54 - 62
170 - 217
5 - 7
21 - 27
GET 012
45
3.1
67 - 77
102 - 130
9 - 11
19 - 24
55 - 63
172 - 219
4 - 6
22 - 27
GET 012
55
2.5
72 - 83
124 - 158
10 - 13
18 - 23
64 - 74
181 - 230
6 - 8
24 - 31
GET 012
55
3.1
71 - 82
120 - 153
9 - 11
18 - 23
65 - 75
182 - 232
5 - 7
25 - 31
GET 012
68
2.5
74 - 86
152 - 193
10 - 13
17 - 22
75 - 86
192 - 245
7 - 9
27 - 35
GET 012
68
3.1
74 - 85
147 - 187
8 - 11
18 - 23
76 - 87
194 - 247
6 - 8
28 - 36
GET 012
75
2.5
76 - 87
168 - 213
10 - 13
17 - 21
79 - 90
196 - 250
8 - 10
29 - 37
GET 012
75
3.1
75 - 86
163 - 207
8 - 10
17 - 22
79 - 91
198 - 252
6 - 8
29 - 37
GET 012
86
2.5
77 - 89
195 - 248
10 - 12
16 - 20
84 - 96
203 - 258
8 - 11
30 - 39
GET 012
86
3.1
77 - 88
190 - 242
8 - 10
16 - 21
85 - 97
204 - 260
7 - 9
31 - 39
GET 012
95
2.5
79 - 91
219 - 279
9 - 12
15 - 19
GET 012
95
3.1
78 - 90
214 - 273
8 - 10
15 - 19
GET 015
35
2.8
42 - 49
161 - 204
5 - 7
16 - 20
GET 015
35
3.5
44 - 51
163 - 208
4 - 6
16 - 20
GET 015
45
2.8
71 - 81
100 - 127
12 - 15
16 - 20
51 - 59
171 - 217
6 - 8
18 - 23
GET 015
45
3.5
71 - 81
97 - 124
10 - 12
16 - 21
53 - 61
174 - 221
5 - 7
19 - 24
GET 015
55
2.8
73 - 84
116 - 147
12 - 15
16 - 20
61 - 70
181 - 231
8 - 10
21 - 26
GET 015
55
3.5
73 - 84
112 - 143
10 - 12
16 - 20
63 - 72
184 - 234
6 - 8
21 - 27
GET 015
68
2.8
75 - 86
141 - 179
12 - 15
15 - 20
75 - 87
195 - 249
9 - 12
24 - 31
GET 015
68
3.5
74 - 86
137 - 174
10 - 12
16 - 20
77 - 89
198 - 252
7 - 9
25 - 31
GET 015
75
2.8
75 - 86
156 - 199
12 - 15
15 - 19
83 - 95
203 - 258
10 - 13
26 - 33
GET 015
75
3.5
75 - 86
152 - 194
10 - 12
15 - 19
84 - 97
205 - 261
8 - 10
26 - 34
GET 015
86
2.8
76 - 87
184 - 234
12 - 15
14 - 18
92 - 106
211 - 269
11 - 14
28 - 36
GET 015
86
3.5
76 - 87
179 - 228
9 - 12
15 - 19
94 - 108
214 - 272
9 - 12
29 - 37
GET 015
95
2.8
77 - 88
208 - 265
11 - 14
14 - 18
GET 015
95
3.5
77 - 88
203 - 258
9 - 12
14 - 18
Operating Pressures