background image

18

WSHP-SVN08B-EN

Electrical
Requirements

Table F2: Blower External Static Pressure 

with Return Air Door (RAD), with filter

1

The NO "Ducted" option is for non-ducted (free return) units.

2

Units specified as "non-ducted" (free return) are factory wired to low-speed.

3

Units specified as "ducted" are factory wired to high-speed.

Table E1: Electrical Performance

 

Model No.

Speed

Tap

Ducted

Min

CFM

Max

CFM

External Static Pressure (in. of wg)

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

0.55

0.6

0.65

0.7

GET009

High

Yes

280

482

-

451

417

378

342

303

-

-

-

-

-

-

-

-

-

GET009

Low

Yes

-

-

-

336

324

304

278

-

-

-

-

-

-

-

-

-

-

GET009

High

No

-

-

345

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET009

Low

No

-

-

280

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET012

High

Yes

380

481

-

-

-

459

436

413

389

363

-

-

-

-

-

-

-

GET012

Low

Yes

-

-

-

420

400

382

362

-

-

-

-

-

-

-

-

-

-

GET012

High

No

-

-

470

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET012

Low

No

-

-

380

-

-

-

-

-

-

-

-

-

-

-

-

-

GET015

High

Yes

475

652

-

-

-

-

-

642

621

601

574

551

525

493

457

419

679

GET015

Low

Yes

-

-

-

572

556

541

525

509

495

476

-

-

-

-

-

-

-

GET015

High

No

-

-

575

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET015

Low

No

-

-

475

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET018

High

Yes

570

800

-

-

-

-

-

-

-

774

747

722

698

668

639

607

578

GET018

Low

Yes

-

-

-

623

617

603

588

571

555

-

-

-

-

-

-

-

-

GET018

High

No

-

-

690

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET018

Low

No

-

-

524

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET024

High

Yes

760

974

-

-

-

-

927

907

880

858

830

799

777

743

-

-

-

GET024

Low

Yes

-

-

-

831

806

789

767

746

726

-

-

-

-

-

-

-

-

GET024

High

No

-

-

940

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET024

Low

No

-

-

760

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET036

High

Yes

1135 1344

-

-

-

-

-

-

-

-

-

-

1250 1219 1188 1161 1125

GET036

Low

Yes

-

-

-

1177 1169 1159 1144 1136 1119 1102 1084 1061

-

-

-

-

-

GET036

High

No

-

-

1280

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET036

Low

No

-

-

1140

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 Model No.

Oversized Blower

 Volts

Total

FLA

Comp.

RLA

Comp.

LRA

Blower

Motor

FLA

Blower

Motor

HP

Minimum

Circuit

Ampacity

Overcurrent

Protective

Device

GET009

No

208/60/1

4.0

3.4

22.2

0.6

1/10

4.9

15

GET009

No

220-240/50/1

3.6

3.1

18.8

0.5

1/10

4.4

15

GET009

No

230/60/1

4.0

3.4

22.2

0.6

1/10

4.9

15

GET009

No

265/60/1

3.6

3.1

18.8

0.5

1/10

4.4

15

GET012

No

208/60/1

5.7

5.0

27.9

0.7

1/8

6.9

15

GET012

No

220-240/50/1

4.9

4.3

22.2

0.6

1/8

6.0

15

GET012

No

230/60/1

5.7

5.0

27.9

0.7

1/8

6.9

15

GET012

No

265/60/1

4.9

4.3

22.2

0.6

1/8

6.0

15

GET015

No

208/60/1

6.1

5.4

29.0

0.7

1/8

7.5

15

GET015

No

220-240/50/1

5.4

4.8

27.0

0.6

1/8

6.6

15

GET015

No

230/60/1

6.1

5.4

29.0

0.7

1/8

7.5

15

GET015

No

265/60/1

5.4

4.8

27.0

0.6

1/8

6.6

15

GET018

No

208/60/1

9.3

7.6

45.0

1.7

1/5

11.2

15

GET018

No

220-240/50/1

7.4

6.3

32.0

1.1

1/5

9.0

15

GET018

No

230/60/1

9.3

7.6

45.0

1.7

1/5

11.2

15

GET018

No

265/60/1

7.4

6.3

32.0

1.1

1/5

9.0

15

GET024

No

208/60/1

13.1

10.9

56.0

2.2

1/5

15.8

25

GET024

No

220-240/50/1

11.7

9.9

55.0

1.8

1/5

14.2

20

GET024

No

230/60/1

13.1

10.9

56.0

2.2

1/5

15.8

25

GET024

No

265/60/1

11.7

9.9

55.0

1.8

1/5

14.2

20

GET036

No

208/60/1

19.3

16.0

82.0

3.3

1/2

23.3

35

GET036

No

220-240/50/1

16.4

13.6

64.0

2.8

1/2

19.8

30

GET036

No

230/60/1

19.3

16.0

82.0

3.3

1/2

23.3

35

GET036

No

265/60/1

16.4

13.6

64.0

2.8

1/2

19.8

30

Summary of Contents for GETB

Page 1: ...WSHP SVN08B EN February 2006 Models A and later Design Sequence Installation Owner Diagnostics Vertical Stack Water Source Heat Pump Model GETB GETB 009 036 60 HZ 009 036 50 HZ ...

Page 2: ...ditioning system to knowingly vent or release any CFC or HCFC refrigerant Minimal releases air purges or refrigerant hoses associated with good faith attempts to recapture or recycle are exempt from the ban on venting Responsible Refrigerant Practices Trane believes that responsible refrigerant practices are important to the environment our customers and the air conditioning industry All technicia...

Page 3: ...al Information 5 Dimensions Weights 6 Installation Instructions 9 Electrical Requirements 18 Pre Startup Checklist 19 Startup Commissioning 20 Sequence of Operation 20 Operating Pressures 21 Startup Checklist Log 24 Maintenance 25 Warranty Information 26 Troubleshooting Checklist 27 Unit Wiring 29 ...

Page 4: ...rge has been retained reinstall the schrader caps to assure that refrigerant leakage does not occur CAUTION Microbial Growth Wet interior unit insulation can become an amplification site for microbial growth mold which may cause odors and damage to the equipment and building materials If there is evidence of microbial growth mold on the interior insulation the insulation should be removed and repl...

Page 5: ...It includes a heavy gage base plate gasket and in sulation around the compressor enclo sure and vibration isolation between the chassis and cabinet An additional dampening treatment is applied around the compressor enclosure to achieve greater acoustical reductions Controls The control system offered to control the unit is a Basic 24 volt control for the 3 4 ton through 2 ton retrofit WPRD equipme...

Page 6: ... in death or serious injury or possible equipment or property only damage Dimensions Weights Clearance Figure 1 Mechanical clearances Unit Location and Clearances Locate the unit in an indoor area The ambient temperature surrounding the unit must not be less than 45 F Do not locate the unit in areas subject to freezing Attention should be given to service clearance and technician safety The unit c...

Page 7: ...NAL DUCT OPENING 1 12 7 DUCT COLLAR R S D VARIES DEPENDENT ON RISER O D TOP FRONT RIGHT SIDE 11 279 FOR 80 2032 CABINET HEIGHT 3 76 FOR 88 2235 CABINET HEIGHT SUPPLY AIR OPENINGS AND RISER LOCATIONS CANNOT BE ONTHE SAME SIDE OFTHE UNIT RISER LOCATION CAN BE ON ANY SIDE EXCEPT FRONT AND MAY BE SUPPLIED BYTRANE OR BY OTHERS NOTE RIGHT RISER LOCATION SHOWN IN FRONT AND RIGHT VIEWS RISER CONNECTION 1 ...

Page 8: ...1 4 1 2 0 A 1 X 1 CLOSED CELL INSULATION 1 X 1 CLOSED CELL INSULATION 2 X 4 STUD 2 X 4 STUD RETURN AIR OPENING FLANGE ON CABINET RETURN AIR OPENING FLANGE ON CABINET SHEETROCK SHEETROCK RETURN AIR DOOR FLANGE CABINET CABINET Note Finished wall and framing should not touch the unit cabinetry Return Air hinged Acoustical Door The hinged acoustical door is recessed into the wall so that the door is f...

Page 9: ...emove refrigeration access panel and inspect the unit Be certain the refrigerant tubing has clearance from adjacent parts WARNING Hazardous Voltage Disconnect all electric power including remote disconnects and discharge all motor start run capacitors before servicing Follow proper lockout tagout procedures to ensure the power can not be inadvertently energized Failure to disconnect power before s...

Page 10: ...net 4 Plumb risers in two planes to as sure proper unit operation and con densate drainage 5 Anchor all units into place 6 For field provided risers center the supply return stubouts into the unit expansion slots The stubouts should be perpendicular to the cab inet panel 7 Verify all risers are vertical and that they penetrate the swaged joint at least 1 Riser should not be al lowed to bottom out ...

Page 11: ...ric Code NEC latest edition Location of the applicable electric ser vice entrance for HIGH line voltage may be found in Figure 3 1 Route power wire to the cabinet control box through the factory in stalled conduit at the top of the unit cabinetry The high voltage connection is made at the 1PB1 power block in the cabinet control box Refer to the customer connection diagram that is shipped with the ...

Page 12: ...wall to allow for frame mounting Units utilizing Hinged Acoustic Door Assembly 1 Locate the side studs a minimum of 1 1 4 inches and a maximum of 1 3 8 inches from the cabinet to the side of the stud This critical dimension combined with distance between studs is used to determine the side to side opening for the door dimen sion A The distances provided in the table are a minimum dimen sion Allow ...

Page 13: ...ign install field ductwork to the unit providing a wa ter tight flexible connector at the unit This helps prevent operating sounds from transmitting through the ductwork Elbows with turning vanes or splitters are recommended to minimize air noise due to turbu lence and to help reduce static pres sure Chassis Installation 1 Remove three 16 inch bolts on the chassis and discard Figure 9 Figure 9 Shi...

Page 14: ...ircuit external to the unit avoiding trash settle out in the condenser An extra pipe may be necessary to con nect the hose kits See Page 15 for an tifreeze water mixture by volume 3 Water circulation system should be filled with clean water using the wa ter make up connections Note Air vents should be opened during fill ing 4 With the air vents closed start the circulating pump and then crack the ...

Page 15: ... the water tem perature are expected to fall below 30 F At extreme temperatures the vis cosity increases to the point where normal loop circulating pumps may not maintain proper flow If propylene glycol is the only locally approved solution for anti freeze good engineering practices should be used to achieve the desired flow Calculate the approximate volume of water in the system by using the re q...

Page 16: ...uctors for grounds shorts and mis wiring Use copper conductors unless other wise specified Do not run the AC low voltage wiring in the same conduit with the high volt age power wiring Table 4 24V AC conductors Distance from unit to Control Recommended Wire Size 000 460 feet 18 gauge 461 732 feet 16 gauge 733 1000 feet 14 gauge Installation Low Voltage Wiring Table 5 Deluxe controller diagnostic LE...

Page 17: ...th filter 1 The NO Ducted option is for non ducted free return units 2 Units specified as non ducted free return are factory wired to low speed 3 Units specified as ducted are factory wired to high speed Model No Speed Tap Ducted Min CFM Max CFM External Static Pressure in of wg 0 0 05 0 1 0 15 0 2 0 25 0 3 0 35 0 4 0 45 0 5 0 55 0 6 0 65 0 7 GET009 High Yes 280 482 456 422 383 347 308 GET009 Low ...

Page 18: ...59 1144 1136 1119 1102 1084 1061 GET036 High No 1280 GET036 Low No 1140 Model No Oversized Blower Volts Total FLA Comp RLA Comp LRA Blower Motor FLA Blower Motor HP Minimum Circuit Ampacity Overcurrent Protective Device GET009 No 208 60 1 4 0 3 4 22 2 0 6 1 10 4 9 15 GET009 No 220 240 50 1 3 6 3 1 18 8 0 5 1 10 4 4 15 GET009 No 230 60 1 4 0 3 4 22 2 0 6 1 10 4 9 15 GET009 No 265 60 1 3 6 3 1 18 8 ...

Page 19: ...ation pad hose kits ____ Is unit serviceable See clearance specifications on page 6 ____ Are the low high side pressure temperature caps secure and in place ____ Are all the unit access panels secure and in place ____ Is the thermostat in the OFF position ____ Is the water flow established and circulating through all the units ____ Is the duct work if required correctly sized run taped insulated a...

Page 20: ...sheet data Water leaving the heat exchanger should be warmer than the entering water temperature approximately 9 F 12 F blower operation should be smooth compressor and blower amps should be within data plate ratings the suction line should be cool with no frost observed in the refrigerant circuit 4 Check the cooling refrigerant pressures against values in Table OP1 Page 21 5 Turn the thermostat s...

Page 21: ...90 206 262 10 13 11 14 GET 009 95 2 25 78 90 202 257 8 10 11 14 GET 012 35 2 5 44 50 160 204 5 6 19 24 GET 012 35 3 1 45 51 162 206 4 5 19 24 GET 012 45 2 5 68 78 106 135 10 13 18 23 54 62 170 217 5 7 21 27 GET 012 45 3 1 67 77 102 130 9 11 19 24 55 63 172 219 4 6 22 27 GET 012 55 2 5 72 83 124 158 10 13 18 23 64 74 181 230 6 8 24 31 GET 012 55 3 1 71 82 120 153 9 11 18 23 65 75 182 232 5 7 25 31 ...

Page 22: ...45 6 0 63 73 104 133 10 13 17 22 52 59 177 225 5 7 21 27 GET 024 55 4 8 67 78 125 159 12 16 17 22 59 68 187 238 7 10 24 30 GET 024 55 6 0 67 77 121 154 10 13 17 22 61 70 189 240 6 8 24 31 GET 024 68 4 8 71 82 151 193 12 16 16 21 70 81 202 257 9 11 27 34 GET 024 68 6 0 70 81 147 187 10 13 17 21 72 82 204 259 7 9 28 35 GET 024 75 4 8 72 83 167 213 12 15 16 20 75 87 209 266 9 12 29 37 GET 024 75 6 0 ...

Page 23: ...peratures during start up WARNING Live Electrical Components During installation testing servicing and troubleshooting of this product it may be necessary to work with live electrical components Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety pre cautions when ...

Page 24: ...and costly system failures complete the following checks and data entries before the system is put into full operation MODE Entering fluid temperature Leaving fluid temperature Temperature differential Return air temperature DB WB Supply air temperature DB WB Temperature differential Water coil heat exchanger Water Pressure IN Water coil heat exchanger Water Pressure OUT Pressure Differential HEAT...

Page 25: ...t heat exchanger Should it become contaminated with dirt and scaling as a result of bad water the heat exchanger will have to be back flushed and cleaned with a chemical that will remove the scale This service Model GET Filter Size nominal 009 012 14 x 20 356 x 508 015 18 x 20 457 x 508 018 18 x 25 457 x 635 024 036 20 x 30 508 x 762 Maintenance should be performed by an experi enced service perso...

Page 26: ...ed 18 months from shipment Extended Warranty The optional extended warranty is a second through fifth year warranty The time starts at the end of standard 1 year coverage through the fifth year These extended warranties apply only to new equipment installed in domestic Trane Commercial Systems Group sales territories and must be ordered prior to start up Warranty Information ...

Page 27: ...ion broken or disconnected wires etc If everything appears to be in or der but the unit still fails to operate properly refer to the troubleshooting chart on page 28 General Operation The standard model is designed for in door installation When the unit is in stalled in an unconditioned space the unit may not start in cool weather ap proximately 45 F It may then be nec essary to start the unit in ...

Page 28: ...y superheat X X Restricted thermal expansion valve Replace X X Defective reversing valve See WSHP IOM for touch test chart X X Thermostat improperly located Relocate X X Unit undersized Recalculate heat gains losses X X Inadequate water flow Increase GPM X X Scaling in heat exchanger Clean or replace X Water too hot Decrease temperature X Water too cold Increase temperature High pressure switch op...

Page 29: ...OTES DEATH SEVERE PERSONAL INJURY OR BEFORE SERVICING CAN CAUSE FAILURE TO DISCONNECT POWER BEFORE SERVICING INCLUDING REMOTE DISCONNECTS DISCONNECT ALL ELECTRIC POWER OU LA MORT BLESSURES CORPORELLES SEVERES L ENTRETIEN PEUT ENTRAINER DES ELECTRIQUE AVANT D EFFECTUER FAUTE DE DECONNECTER LA SOURCE AVANT D EFFECTUER L ENTRETIEN DISJONCTEURS SITUES A DISTANCE ELECTRIQUES INCLUANT LES DECONNECTEZ TO...

Page 30: ...30 WSHP SVN08B EN Unit Wiring Deluxe Diagram 208V 50 60 Hz 1PH ...

Page 31: ...WSHP SVN08B EN 31 Unit Wiring ZN510 Diagram 230V 50 60 Hz 1PH ...

Page 32: ...ications without notice Literature Order Number WSHP SVN08B EN File Number SV UN WSHP SVN08B EN 0206 Supersedes SV UN WSHP SVN08A EN 1105 Stocking Location Inland Trane A business of American Standard Companies www trane com For more information contact your local district office or e mail us at comfort trane com ...

Reviews: