32
CLCH-SVX08A-EN
Routine Maintenance
WARNING
Hazardous Gases and Flammable Vapors!
Exposure to hazardous gases from fuel substances have been shown to cause cancer, birth
defects or other reproductive harm. Improper installation, adjustment, alteration, service or use
of this product could cause flammable mixtures. To avoid hazardous gases and flammable
vapors follow proper installation and set up of this product and all warnings as provided in this
manual. Failure to follow all instructions could result in death or serious injury.
Heating Mode Maintenance
Service Personnel Maintenance
Table 10. Routine maintenance in heating mode
Task
Frequency
Remarks
Unit startup
Weekly
Listen to and visually inspect the unit during normal startup.
Unit shutdown
Weekly
Listen to and visually inspect the unit during normal shutdown.
Check fuel valves, pilot and main Weekly
Open limit switches and listen to and visually inspect.
Check combustion safety controls:
• Flame failure
Weekly
• Close manual fuel supply for the pilot and the main fuel valves; check safety shutdown timing
and record.
• Flame signal strength
Weekly
• Follow procedure to check flame signal strength outlined in
“Main Burner Ignition (3:1, 10:1
Turndown, 200-2000 MBh)” on page 28
.
Drain condensate from heat
exchanger
Weekly
This task only needs to be done if the unit runs for extended hours at low fire.
Clean air inlet louver
Monthly
Use brush and vacuum cleaner
Clean combustion air blower and
motor
Monthly
Use brush and vacuum cleaner
Clean exhaust flue
Monthly
Use brush and vacuum cleaner
Clean combustion air dampers
Monthly
Use brush and vacuum cleaner
Check combustion air inlets for
obstruction. Remove debris.
Monthly
Use brush or vacuum cleaner.
Check gas piping for leaks
Yearly
Use soap bubble solution or equivalent leak tester.
WARNING: Do
not
use an open flame to perform a leak test as personal injury or death could
occur.
Table 11. Routine maintenance for trained service personnel
Task
Frequency
Remarks
Inspect burner components
Semiannually
Refer to burner and component manufacturer’s manuals
Visually inspect safety switches Semiannually
Inspect airflow sensor lines for obstructions.
Inspect terminal connections for tightness.
Inspect switches for fused contacts.
Check that settings haven’t changed or been tampered with.
Check flue emissions
Annually
Use a combustion analyzer
Check fuel valves, main
Annually
Perform valve leak test per valve manufacturer’s instructions
Check safety controls:
• High limit
• Airflow
• Low gas pressure
• High gas pressure
• Exhaust fan switch (where
applicable)
Annually
Refer to control manufacturer’s instructions
Inspect gas pilot assembly
Annually
Remove and clean if applicable
Summary of Contents for Gas Heat Sections for Performance Climate Changer Air Handlers
Page 23: ...CLCH SVX08A EN 23 Wiring Figure 13 200 1000 MBh 3 1 or 10 1 turndown wiring diagram ...
Page 24: ...24 CLCH SVX08A EN Wiring Figure 14 1250 2000 MBh 3 1 or 10 1 turndown wiring diagram ...
Page 25: ...CLCH SVX08A EN 25 Wiring Figure 15 1250 2400 MBh 20 1 turndown wiring diagram ...
Page 35: ...CLCH SVX08A EN 35 Notes ...