background image

40

RT-SVX51L-EN

Table 17.

Belt tension measurement and deflection ranges (mm/kg)

Belts Cross

Section

Small P.D Range

(mm)

Deflection Force (kg)

Super Gripbelts (mm)

Gripnotch (mm)

Steel Cable Gripbelts (mm)

Min.

Max.

Min.

Max.

Min.

Max

A

13.3–16.0

13.3

20.0

17.2

24.5

14.5

17.8

16.9–21.4

15.6

22.2

20.0

27.8

16.7

21.1

22.0–31.1

17.8

24.5

22.2

30.6

18.9

23.4

B

15.1–18.7

17.8

24.5

25.6

35.6

20.0

24.5

19.6–24.9

22.8

31.7

28.9

40.6

25.6

32.3

25.8–39.1

28.4

38.9

32.8

45.0

31.1

38.9

Monthly Maintenance

Before completing the following checks, turn the unit OFF
and lock the main power disconnect switch open.

WARNING

Hazardous Voltage!

Failure to disconnect power before servicing could
result in death or serious injury.
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Verify that no power is
present with a voltmeter.

Filters

Inspect the return air filters. Clean or replace them if
necessary. Refer to the unit Service Facts for filter
information.

Condensate Overflow Switch

During maintenance, the switch float (black ring) must be
checked to ensure free movement up and down.

Cooling Season

Check the unit’s drain pans and condensate piping to
ensure that there are no blockages.

Inspect the evaporator and condenser coils for dirt,
bent fins, etc. If the coils appear dirty, clean them
according to the instructions described in “Coil
Cleaning” later in this section.

Manually rotate the condenser fans to ensure free
movement and check motor bearings for wear. Verify
that all of the fan mounting hardware is tight.

Inspect the F/A-R/A damper hinges and pins to ensure
that all moving parts are securely mounted. Keep the
blades clean as necessary.

WARNING

Rotating Components!

Failure to disconnect power before servicing
could result in rotating components cutting and
slashing technician which could result in death or
serious injury.
During installation, testing, servicing and
troubleshooting of this product it may be
necessary to work with live and exposed rotating
components. Have a qualified or licensed service
individual who has been properly trained in
handling exposed rotating components, perform
these tasks.

NOTICE

Equipment Damage!

Forcibly turning the motor shaft can damage the
gear train and motor beyond repair.
Never turn the motor shaft by hand or with a
wrench.

Verify that all damper linkages move freely; lubricate
with white grease, if necessary.

Check supply fan motor bearings; repair or replace the
motor as necessary.

Check the fan shaft bearings for wear. Replace the
bearings as necessary.

Check the supply fan belt(s). If the belts are frayed or
worn, replace them. Refer to the

“Fan Belt Adjustment-

Belt Drive Units,” p. 39

for belt replacement and

adjustments.

Verify that all wire terminal connections are tight.

Remove any corrosion present on the exterior surfaces
of the unit and repaint these areas.

Generally inspect the unit for unusual conditions (e.g.,
loose access panels, leaking piping connections, etc.)

Make sure that all retaining screws are reinstalled in the
unit access panels once these checks are complete.

With the unit running, check and record the following:

Maintenance

Summary of Contents for Foundation GCC180-300

Page 1: ...Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the t...

Page 2: ...t is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the applic...

Page 3: ...o help assure trouble free operation A maintenance schedule is provided at the end of this manual Should equipment failure occur contact a qualified service organization with qualified experienced HVA...

Page 4: ...28 Unit Disconnect FIYUDC 28 Through the Base Gas Utility Option 29 Field Installed Connections 29 Pre Start 31 Verifying Proper Air Flow Units with Belt Drive Indoor Fan 31 Electromechanical Control...

Page 5: ...thly Maintenance 40 Filters 40 Condensate Overflow Switch 40 Cooling Season 40 Heating Season 41 Coil Cleaning 41 Troubleshooting 44 Standard Troubleshooting 44 Ignition Module 44 Failures 44 Low Leak...

Page 6: ...lief1 J Downflow Low Leak Economizer Dry Bulb w o Barometric Relief L Downflow Low Leak Economizer Reference Enthalpy w o Barometric Relief N Downflow Low Leak Economizer Comparative Enthalpy w o Baro...

Page 7: ...o not proceed with installation of a damaged unit without sales representative approval Inspect the complete exterior for signs of shipping damages to unit or packing material Verify that the nameplat...

Page 8: ...nd the module will automatically reset from a fault condition Discharge Line Thermostat Control The high pressure controls and the discharge line thermostat signals are wired in series and connected t...

Page 9: ...nu OCC INPUT Attach the occupancy sensor to the OCC SENSOR wire and R terminal at customer connections The occupancy sensor must utilize a normally open contact for proper operation If an occupancy se...

Page 10: ...er airflows or recirculation of hot condenser air Figure 1 Typical installation clearance for single and multiple unit applications NOTES 1 FOR HORIZONTAL DISCHARGE UNIT THIS MEASUREMENT IS REDUCED TO...

Page 11: ...Y GAS CONNECTION G C UNIT ONLY CONDENSATE DRAIN CONNECTION Figure 3 Cooling with optional electrical heat front and side views gas electric NOTES 1 THROUGH THE BASE GAS AND ELECTRICAL IS NOT STANDARD...

Page 12: ...CTION AND ALL DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSTALLATION THROUGH THE BASE ELECTRICAL RETURN SUPPLY 7 3 8 123 1 8 THRU THE BASE GAS G C UNIT ONLY 36 1 16 6 15 16 6 13 16 68 9 16 7 7 16 14...

Page 13: ...1 16 357 MM 2 51 MM 69 1 2 1765 MM Figure 7 Cooling with optional electrical heat downflow duct connections field fabricated 1 25 4 MM CURB FLANGE LONG SIDES 14 1 16 357 MM 7 7 16 189 MM 73 7 16 1865...

Page 14: ...ing with optional electric heat barometric relief and economizer NOTES 1 VERIFY WEIGHT CONNECTION AND ALL DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 2 BAROMETRIC RELIEF IS FOR USE WITH A...

Page 15: ...l electric heat manual damper NOTE VERIFY WEIGHT CONNECTION AND ALL DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSTALLATION BACK VIEW OF UNIT LEFT VIEW OF UNIT FAN MANUAL DAMPER HOOD 123 1 8 18 1 4 26...

Page 16: ...20 GCC240A 2350 2025 643 512 403 466 55 37 25 GCC300A 2386 2061 671 524 393 472 55 36 a Weights are approximate Horizontal and downflow unit and corner weights may vary slightly b Weights do not inclu...

Page 17: ...unit operating weights rigging before proceeding 1 Remove the shipping crate from around the unit Once fork trucking is complete and unit is ready to place on the curb remove all fork access brackets...

Page 18: ...equired anchor the unit to the roof with hold down bolts or isolators Check with a roofing contractor for proper waterproofing procedures Ductwork Elbows with turning vanes or splitters are recommende...

Page 19: ...installed disconnect switch and to the main power terminal block HTB1 in the unit control panel Install proper grounding wires to an earth ground Note All field installed wiring must comply with NEC a...

Page 20: ...r horizontal operation 4 Reinstall the heat section access panel Figure 17 Factory installed down flow TCO1 limit location Gas Heater Conversion Instructions Important Conversion should be made prior...

Page 21: ...te See the following figure 9 Using three screws install the ship with air orifice plate Figure 21 Remove screws from inducer blower assembly and air orifice plate Figure 22 Remove screws from inducer...

Page 22: ...nversion is complete scratch off the ink square to the right hand side SCRATCH INK OFF SQUARE WHEN USING SUPPLEMENTAL HEATING DATA on both English and French nameplate 18 Paste the ship with supplemen...

Page 23: ...s is determined by unit size Access to the filters is obtained by removing the filter access panel Refer to the unit Service Facts shipped with each unit for filter requirements Note Do not operate th...

Page 24: ...Wiring Through the Base Electrical Option Location of the applicable electrical service is illustrated below Refer to the customer connection diagram that is shipped with the unit for specific termina...

Page 25: ...n and optional through the base gas shut off valve are rated at 0 50 PSIG maximum A pressure reducing regulator is recommended to prevent this maximum from being exceeded These components must be isol...

Page 26: ...Gas 8 5 to 9 5 LP Minimum Supply Air Temperature Across Heat Exchanger 40 F a A voltage reading across pens V and V is equatable to the flame sensing current One volt equals one micro amp Table 4 Pip...

Page 27: ...ernally connected for the proper rotation when the incoming power supply is phased as A B C Proper electrical supply phasing can be quickly determined and corrected before starting the unit by using a...

Page 28: ...rify that no power is present with a voltmeter Check all electrical connections for tightness and point of termination accuracy Verify that the condenser airflow is unobstructed Verify that the conden...

Page 29: ...connects and discharge all motor start run capacitors before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized Verify with a CAT III or IV voltmet...

Page 30: ...30 RT SVX51L EN Figure 31 Through the base gas piping installation Installation...

Page 31: ...using the setpoint potentiometer located on the Economizer Control ECA if applicable Electromechanical Controls Test Procedure See unit schematic for correct wire numbers Fan Test and Minimum Ventila...

Page 32: ...itch is set to the Auto position the thermostat energizes the indoor fan relay coil F to start the indoor fan motor IDM The fan relay F de energizes after the cooling requirement has been satisfied Wh...

Page 33: ...blinks System lockout failure to ignite no spark low no gas pressure etc Table 8 Ignition module diagnostics continued Three blinks Pressure switch no vent air flow bad CBM closed at initial call for...

Page 34: ...ign Min Position pot with a range of 0 50 If the Building Design Min Position is set to be higher than the DCV Min Position the setpoints will be capped at the DCV Min Position and the setpoint for th...

Page 35: ...VENTMAX Closed On Off Low 24 v On 0 v Off VENTMIN L to VENTMAX Closed On On High 24 v On 24 v On VENTMIN H to VENTMAX Closed Yes Off Off Low 0 v Off 0 v Off VENTMIN L to VENTMAX Closed On Off Low 0 v...

Page 36: ...e enthalpy and dual enthalpy boundaries parameters ES1 through ES5 Enth Curve Temp dry Bulb F Temp dewpoint F Enthalpy btu lb da Point P1 Point P2 Temp F Humid RH Temp F Humid RH ES1 80 0 60 0 28 0 80...

Page 37: ...emand for cooling When a open circuit has occurred the Frostat opens the 24 Vac ground and opens all of the cooling contactors Initiation of Operating Modes The JADE controller is able to initiate the...

Page 38: ...he following illustration for the compressor terminal phase identification Do not allow the compressor to operate backwards for more than 5 seconds Operation for a period of time longer than this will...

Page 39: ...roper belt tension 2 Set the large O ring on the belt tension gauge at the deflection value determined in Step 1b 3 Set the small O ring at zero on the force scale of the gauge plunger 4 Place the lar...

Page 40: ...ns to ensure free movement and check motor bearings for wear Verify that all of the fan mounting hardware is tight Inspect the F A R A damper hinges and pins to ensure that all moving parts are secure...

Page 41: ...eaning agents can be either acidic or highly alkaline and can burn severely if contact with skin or eyes occurs Handle chemical carefully and avoid contact with skin ALWAYS wear Personal Protective Eq...

Page 42: ...42 RT SVX51L EN Table 18 Unit data log continued schematic s connections Network ID Maintenance...

Page 43: ...sig kPa Liquid Press Psig kPa Superheat F C Sub cool F C Compr Oil Level Suct Press Psig kPa Disch Press Psig kPa Liquid Press Psig kPa Superheat F C Sub cool F C ok low ok low ok low ok low ok low ok...

Page 44: ...to start the unit This procedure will allow you to check all of the external controls relays contactors etc and the IGN 5 Test the system through all of the available modes and verify operation of al...

Page 45: ...emp sensor failure fault Not economizing when it should Economizing when it should not Damper not modulating Excess outdoor air Damper Stuck Open x x x Damper Stuck at Minimum x x Bad or Unplugged Act...

Page 46: ...s between pulse sequences Error Code 1 Flash Actuator Fault 2 Flashes CO2 Sensor 3 Flashes RA Humidity Sensor 4 Flashes RA Temp Sensor 6 Flashes OA Humidity Sensor 7 Flashes OA Temp Sensor 8 Flashes M...

Page 47: ...rt Table 21 Wiring diagrams Type of Airflow Schematic Type Voltage Diagram Number Description Multi Speed Fans Power 208 230 12134575 Schematic PWR EM 208V 230V 2 Stage GH with VFD 15T 25T 460 575 121...

Page 48: ...and liabilities under this warranty are limited to furnishing F O B factory or warehouse at the warrantor designated shipping point freight allowed to Buyer s city or port of export for shipments out...

Page 49: ...RT SVX51L EN 49 Notes...

Page 50: ...50 RT SVX51L EN Notes...

Page 51: ...RT SVX51L EN 51 Notes...

Page 52: ...please visit trane com or americanstandardair com Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications...

Reviews: