ELECTRIC AND ELECTRONIC
COMPLIANCE
YES NO
11
THE UNIT IS ELECTRICALLY POWERED AND ALL THE RELEVANT ELECTRICAL WIRES ARE PROPERLY CONNECTED.
12
ELECTRICAL SUPPLY HAS BEEN INSTALLED IN ACCORDANCE WITH THE INSTRUCTIONS PROVIDED IN THE NAME PLATE AND
IN THE TECHNICAL DOCUMENTATION. (ELECTRICAL POWER SUPPLY: 230V/400V +/- 10% - MAXIMUM “%” OF PHASE
IMBALANCE: +/- 2% ) . IT IS RECOMMENDABLE TO CHECK BY USING A TESTER THE VOLTAGE VALUE (BETWEEN PHASES AND
BETWEEN PHASE AND NEUTRAL)
13
PHASES ARE CONNECTED IN THE PROPER SEQUENCE.
14
ELECTRICAL CABLES SIZE ARE CONFORM TO FLA MAX VALUE.
15
BOTH EXTERNAL AND INTERNAL ELECTRICAL WIRES ARE WELL TIGHTENED.
16
THE COMPRESSOR CRANCKCASE HEATERS HAVE BEEN POWERED AND HEATED AT LEAST 8 HOURS BEFORE THE START-UP
17
AN ELECTRONIC SUPERVISOR (OR ANY ADDITIONAL CONTROLLER) HAS BEEN INSTALLED.
18
THE CONNECTION WIRES ARE SHIELDED.
19
REMOTE CONTROL DEVICES OR INTERFACES ARE CONNECTED TO THE ELECTRICAL PANEL IN CONFORMITY
WITH TRANE WIRING DIAGRAMS
20
ELECTRONIC DEVICES ARE INTACT AND DON’T DISPLAY ANY DAMAGE.
21
AN EXTERNAL WATER PUMP IS ELECTRICALLY CONNECTED TO THE ELECTRICAL PANEL IN ACCORDANCE WITH THE WIRING
DIAGRAMS PROVIDED BY TRANE
22
THE ELECTRICAL ABSORPTION AND THE WATER PUMP OVERHEATING ARE STANDARD.
REFRIGERANT CIRCUIT
COMPLIANCE
YES NO
23
ALL CONNECTIONS ON THE REFRIGERANT CIRCUITS ARE WELL TIGHTENED.
24
THE ELECTRONIC LEAKAGE DETECTOR OR THE PRESSURE GAUGE LEVEL INSTALLED ON THE REFRIGERANT CIRCUIT HAVE
DETECTED ANY LEAKAGE.
IF ANY, SPECIFY BELOW:
25
THE COMPRESSOR OIL INDICATOR LIGHT POINTS THE MAXIMUM LEVEL.
26
THE FILTER INDICATOR LIGHT ON THE LIQUID LINE IS GREEN.
WARNING:
THE YELLOW INDICATOR LIGHT INDICATES PRESENCE OF MOISTURE IN THE CIRCUIT. IN THIS CASE PLEASE
CONTACT TRANE.