6
WSHP-SVX01Q-EN
Digits 1-3 — Unit Configuration
EXH =High Efficiency Horizontal
EXV =High Efficiency Vertical
Digit 4
—
Development Sequence
F
Digits 5-7 — Nominal Capacity
006 =.5 Tons
009 =.75 Tons
012 =1 Tons
015 =1.25 Tons
018 =1.5 Tons
024 =2 Tons
030 =2.5 Tons
036 =3 Tons
042 =3.5 Tons
048 =4 Tons
060 =5 Tons
070 =6 Tons
Digit 8 — Voltage (Volts/Hz/
Phase)
1 = 208/60/1
2 = 230/60/1
3 = 208/60/3
4 = 460/60/3
7 = 265/60/1
8 = 230/60/3
Digit 9 — Heat Exchanger
1 = Copper-Water Coil
2 = Cupro-Nickel Water Coil
7 = Insulated Copper Water
Coil/Suction Line
8 = Insulated Cupro-Nickel Water
Coil/Suction Line
Digit 10 — Current Design
Sequence
Digit 11 — Refrigeration Circuit
0 = Heating and Cooling Circuit
2 = Heating and Cooling Circuit with
Hot Gas Reheat
3 = Heating and Cooling Circuit with
Waterside Economizer
Digit 12 — Blower Configuration
3 = ECM Motor
Digit 13 - Freeze Protection
A = 20°F Freezestat
B = 35°F Freezestat
Digit 14 — Open Digit = 0
Digit 15 — Supply-Air
Arrangement
B = Back Supply-Air Arrangement
L = Left Supply-Air Arrangement
R = Right Supply-Air Arrangement
T = Top Supply-Air Arrangement
Digit 16 — Return-Air
Arrangement
L = Left Return-Air Arrangement
R = Right Return-Air Arrangement
Digit 17 — Control Types
D = Deluxe 24V Controls
B = Tracer® ZN524 Controls
F = UC400
G = UC400 w/ Wireless Comm
Digit 18 — Tstat/Sensor Location
0 = Wall Mounted Location
Digit 19 — Fault Sensors
1 = Condensate Overflow Sensor
3 = Condensate Overflow and Filter
Maintenance Timer
6 = Condensate Overflow and Fan Status
J = Fan Status, Filter Maintenance Timer
and Condensate Overflow Sensor
Digit 20 — Temperature Sensor
0 = No Additional Temperature Sensor
1 = Entering Water Sensor
Digit 21 — Open Digit
Digit 22 — Electric Heat
0 = No Electric Heat
1 = Internal Boilerless Electric Heat
4 = External Boilerless Electric Heat
Digit 23 — Open Digit
Digit 24 — Filter Type
1 = 1" Throwaway Filter
2 = 2" Throwaway Filter
4 = MERV 8
5 = MERV13
Digit 25 — Acoustic
Arrangement
0 = Enhanced Sound Attenuation
1 = Deluxe Sound Attenuation
Digits 26-36 — Does not Apply
to EXH or EXV
00000000000 Digits 26-36 are not
applicable to the EXH or EXV products
Model Number Description - .5 to 6 Tons