background image

SAFETY WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.

Water Source Heat Pump

Axiom™ Horizontal/Vertical

GEH/V*, EXH/V*
.5 to 25 Tons, 50/60 Hz

Installation, Operation,
and Maintenance

Model Numbers

GEHE 006-060 - 50/60 Hz

GEVE 006-060 - 50/60 Hz

GEHE 072-180 - 50/60 Hz

GEVE 072-300 - 50/60 Hz

EXHF 006-070 - 60 Hz

EXVF 006-070 - 60 Hz

WSHP-SVX01Q-EN

December 2016

Summary of Contents for EXHF 006-070

Page 1: ... an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment Water Source Heat Pump Axiom Horizontal Vertical GEH V EXH V 5 to 25Tons 50 60 Hz Installation Operation and Maintenance Model Numbers GEHE 006 060 50 60 Hz GEVE 006 060 50 60 Hz GEHE 072 180 50...

Page 2: ...ch if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage only accidents WARNING Proper Field Wiring and Grounding Required Failure to follow code could result in death or serious injury All field wiring MUST be performed by qualified personnel Improperly installe...

Page 3: ...hout written permission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks referenced in this document are the trademarks of their respective owners Revision History Updated GEH models in Table 53 p 88 Minor running changes ...

Page 4: ...ton 56 Sound Attenuation Pad 57 Hanging the Horizontal Unit 57 Condensate Drain Connection 57 Supply Return Pipe Connections 58 Cleaning and Flushing the Water Loop 58 Field Installed Power Wiring 58 Main Unit Power Wiring 58 Control Power Transformer 59 Thermostat Location 59 Controls Using 24 VAC 59 Blower Motor Speed Tap Retrofit 60 Hole Plug Installation 61 Air Flow Adjustment 61 Waterside Eco...

Page 5: ...ve Package F 7 2 Speed Drive Package G 8 2 Speed Drive Package H 9 2 Speed Drive Package J Digit 13 Freeze Protection A 20 F Freezestat4 B 35 F Freezestat Digit 14 Open Digit 0 Digit 15 Supply Air Arrangement B Back Supply Air Arrangement F Front Supply Air Arrangement L Left Supply Air Arrangement R Right Supply Air Arrangement T Top Supply Air Arrangement Digit 16 Return Air Arrangement B Back R...

Page 6: ...Supply Air Arrangement L Left Supply Air Arrangement R Right Supply Air Arrangement T Top Supply Air Arrangement Digit 16 Return Air Arrangement L Left Return Air Arrangement R Right Return Air Arrangement Digit 17 ControlTypes D Deluxe 24V Controls B Tracer ZN524 Controls F UC400 G UC400 w Wireless Comm Digit 18 Tstat Sensor Location 0 Wall Mounted Location Digit 19 Fault Sensors 1 Condensate Ove...

Page 7: ...ectrician Unit Nameplate The unit nameplate is located on the outside of the control box access panel at the front of the unit It includes the unit model number serial number electrical characteristics refrigerant charge and other pertinent unit data Compressor Nameplate The nameplate for the compressors are located on the compressor shell Model Number Description All products are identified by a ...

Page 8: ...The switch is set to activate at refrigerant pressure of 40 psig to fit most applications A high pressure switch prevents compressor operation during high or excessive discharge pressures exceeding 650 psig The lockout relay will disable the compressor on a high or low pressure condition For units that contain a condensate overflow switch option a condensate overflow condition will also disable th...

Page 9: ...e controls interface ONLY for field provided electric heat selection The heater for this model shall be external to the equipment by the contractor for ease of installation All power connections for the electric heater will be completely separate from the unit for field supplied electric heat Note When the unit has boilerless control the electric heat is not used as supplemental electric heat but ...

Page 10: ... 871 GEVE060 74 0 2 098 79 5 2 254 GEHE072 55 1 559 55 1 559 59 1 673 55 1 559 GEHE090 64 1 814 54 1 531 68 1 928 54 1 531 GEHE120 86 2 438 86 2 438 90 2 551 86 2 438 GEHE150 136 3 856 136 3 856 144 4 082 136 3 856 GEHE180 126 3 572 126 3 572 134 3 799 126 3 572 GEVE072 58 1 644 58 1 644 62 1 758 58 1 644 GEVE090 83 2 353 75 2 126 87 2 466 75 2 126 GEVE120 88 2 495 88 2 495 92 2 608 88 2 495 GEVE1...

Page 11: ...850 32 0 0 907 EXVF018 45 0 1 276 48 0 1 361 EXVF024 52 0 1 474 54 5 1 545 EXVF030 53 0 1 503 56 0 1 588 EXVF036 70 0 1 984 73 0 2 070 EXVF042 81 0 2 296 86 0 2 438 EXVF048 83 0 2 353 88 5 2 509 EXVF060 114 0 3 232 119 5 3 388 EXVF070 122 0 3 459 128 0 3 629 Table 3 Refrigerant charge continued Model 60 Hz Heat Pump oz Kg Heat Pump w HGR oz Kg ...

Page 12: ...tored indoors If indoor storage is not possible the following provisions for outdoor storage must be met Place the unit s on a dry surface or raise above the ground to assure adequate air circulation beneath the unit Cover the unit s with a water proof tarp to protect them from the elements Make provisions for continuous venting of the covered units to prevent moisture from standing on the unit s ...

Page 13: ...The optimum clearance required is 20 inches Equipment containing a same side supply return combination requires a 3 inches limitation on one side Access to theTXV may not be possible with this 3 inches clearance This configuration is typically applied in a corridor installation where space limitations force the left or right side of the unit against a wall 14 14 14 14 LEFT RETURN BACK SUPPLY UNIT ...

Page 14: ...k of the unit represents the supply duct collar for the back supply option This clearance is needed to clear these flanges 36 1 1 UNIT FRONT LEFT RETURN TOP BACK SUPPLY 1 1 24 UNIT FRONT 36 RIGHT RETURN TOP BACK SUPPLY 24 Figure 4 Clearance GEV 6 to 10Tons A 24 inch clearance from other mechanical and electrical equipment where shown is recommended for all configurations The unit may be serviced t...

Page 15: ...9 5 8 23 1 2 5 1 2 Hi 048 060 Hi 042 048 060 58 33 21 29 1 2 23 1 2 13 7 8 x 13 7 8 18 5 1 4 1 1 2 1 1 56 3 4 31 3 4 19 5 8 23 1 2 5 1 2 EXH Unit 60 Hz EXH Unit 50 Hz A B C D a E F x G H J K L NPTI M NPTI N P Q R b S 006 009 N A 40 20 15 20 15 6 7 8 x 8 11 1 2 4 1 2 1 3 4 1 2 1 2 38 3 4 18 3 4 13 5 8 18 1 2 3 1 4 012 015 N A 40 20 15 20 15 8 1 4 x 9 3 4 11 1 2 4 1 4 3 4 1 2 1 2 38 3 4 18 3 4 13 5 ...

Page 16: ...4 Std 048 Std 042 58 33 21 29 1 2 23 1 2 13 1 8 x 11 3 8 18 5 1 4 1 1 2 1 1 56 3 4 31 3 4 19 5 8 23 1 2 5 1 2 Hi 048 060 Hi 042 048 060 060 58 33 29 1 2 23 1 2 13 7 8 x 13 7 8 18 5 1 4 1 1 2 1 1 56 3 4 31 3 4 19 5 8 23 1 2 5 1 2 EXH Unit 60 Hz EXH Unit 50 Hz A B C D a E F x G H J K L NPTI M NPTI N P Q R b S 006 009 N A 40 20 15 20 15 6 7 8 x 8 11 1 2 4 1 2 1 3 4 1 2 1 2 38 3 4 18 3 4 13 5 8 18 1 2...

Page 17: ...1 4 Std 048 Std 042 58 33 21 29 1 2 23 1 2 13 1 8 x 11 3 8 18 5 1 4 1 1 2 1 1 56 3 4 31 3 4 19 5 8 23 1 2 5 1 2 Hi 048 060 Hi 042 048 060 58 33 21 29 1 2 23 1 2 13 7 8 x 13 7 8 18 5 1 4 1 1 2 1 1 56 3 4 31 3 4 19 5 8 23 1 2 5 1 2 EXH Unit 60 Hz EXHUnit 50 Hz A B C D a E F x G H J K L NPTI M NPTI N P Q R b S 006 009 N A 40 20 15 20 15 6 7 8 x 8 11 1 2 4 1 2 1 3 4 1 2 1 2 38 3 4 18 3 4 13 5 8 18 1 2...

Page 18: ...1 4 Std 048 Std 042 58 33 21 29 1 2 23 1 2 13 1 8 x 11 3 8 18 5 1 4 1 1 2 1 1 56 3 4 31 3 4 19 5 8 23 1 2 5 1 2 Hi 048 060 Hi 042 048 060 58 33 21 29 1 2 23 1 2 13 7 8 x 13 7 8 18 5 1 4 1 1 2 1 1 56 3 4 31 3 4 19 5 8 23 1 2 5 1 2 EXH Unit 60 Hz EXH Unit 50 Hz A B C D a E F x G H J K L NPTI M NPTI N P Q R b S 006 009 N A 40 20 15 20 15 6 7 8 x 8 11 1 2 4 1 2 1 3 4 1 2 1 2 38 3 4 18 3 4 13 5 8 18 1 ...

Page 19: ...1 4 Std 048 Std 042 58 33 21 29 1 2 23 1 2 13 1 8 x 11 3 8 18 5 1 4 1 1 2 1 1 56 3 4 31 3 4 19 5 8 23 1 2 5 1 2 Hi 048 060 Hi 042 048 060 58 33 21 29 1 2 23 1 2 13 7 8 x 13 7 8 18 5 1 4 1 1 2 1 1 56 3 4 31 3 4 19 5 8 23 1 2 5 1 2 EXH Unit 60 Hz EXH Unit 50 Hz A B C D a E F x G H J K L NPTI M NPTI N P Q R b S 006 009 N A 40 20 15 20 15 6 7 8 x 8 11 1 2 4 1 2 1 3 4 1 2 1 2 38 3 4 18 3 4 13 5 8 18 1 ...

Page 20: ... 19 5 8 23 1 2 5 1 2 Hi 048 060 Hi 042 048 060 58 33 21 29 1 2 23 1 2 13 7 8 x 13 7 8 18 5 1 4 1 1 2 1 1 56 3 4 31 3 4 19 5 8 23 1 2 5 1 2 EXH Unit 60 Hz EXH Unit 50 Hz A B C D a E F x G H J K L NPTI M NPTI N P Q R b S 006 009 N A 40 20 15 20 15 6 7 8 x 8 11 1 2 4 1 2 1 3 4 1 2 1 2 38 3 4 18 3 4 13 5 8 18 1 2 3 1 4 012 015 N A 40 20 15 20 15 8 1 4 x 9 3 4 11 1 2 4 1 4 3 4 1 2 1 2 38 3 4 18 3 4 13 ...

Page 21: ...1 4 2 9 1 2 29 27 7 8 13 1 8 11 3 8 1 2 1 1 3 4 Hi 048 060 Hi 042 048 060 26 1 2 46 7 8 30 1 2 18 4 1 4 2 9 1 2 29 27 7 8 13 7 8 13 7 8 1 2 1 1 3 4 EXV Unit 60 Hz EXV Unit 50 Hz A B C D E F G H J K L M W I NPTI W O NPTI Drain FPT 006 019 N A 19 1 2 31 1 4 21 1 2 11 1 2 4 5 3 4 9 1 2 15 17 6 7 8 8 3 4 1 2 1 2 3 4 012 015 N A 19 1 2 31 1 4 21 1 2 11 1 2 5 1 2 5 5 8 9 1 2 15 17 8 1 4 9 3 4 3 4 1 2 1 ...

Page 22: ... 3 4 Std 48 Std 42 26 1 2 46 7 8 30 1 2 18 4 1 4 2 9 1 2 29 27 7 8 13 1 8 11 3 8 1 2 1 1 3 4 Hi 048 060 Hi 042 048 060 26 1 2 46 7 8 30 1 2 18 4 1 4 2 9 1 2 29 27 7 8 13 7 8 13 7 8 1 2 1 1 3 4 EXV Unit 60 Hz EXV Unit 50 Hz A B C D E F G H J K L M W I NPTI W O NPTI Drain FPT 006 019 N A 19 1 2 31 1 4 21 1 2 11 1 2 4 5 3 4 9 1 2 15 17 6 7 8 8 3 4 1 2 1 2 3 4 012 015 N A 19 1 2 31 1 4 21 1 2 11 1 2 5...

Page 23: ...48 Std 42 26 1 2 46 7 8 30 1 2 18 4 1 4 2 9 1 2 29 27 7 8 13 1 8 11 3 8 1 2 1 1 3 4 Hi 048 060 Hi 042 048 060 26 1 2 46 7 8 30 1 2 18 4 1 4 2 9 1 2 29 27 7 8 13 7 8 13 7 8 1 2 1 1 3 4 EXV Unit 60 Hz EXV Unit 50 Hz A B C D E F G H J K L M W I NPTI W O NPTI Drain FPT 006 019 N A 19 1 2 31 1 4 21 1 2 11 1 2 4 5 3 4 9 1 2 15 17 6 7 8 8 3 4 1 2 1 2 3 4 012 015 N A 19 1 2 31 1 4 21 1 2 11 1 2 2 1 2 5 5 ...

Page 24: ...4 1 7 8 9 1 2 19 23 10 1 2 13 1 2 3 4 3 4 3 4 3 4 Std 48 Std 42 26 1 2 46 7 8 30 1 2 18 4 1 4 2 9 1 2 29 27 7 8 13 1 8 11 3 8 1 2 1 1 3 4 Hi 048 060 Hi 042 048 060 26 1 2 46 7 8 30 1 2 18 4 1 4 2 9 1 2 29 27 7 8 13 7 8 13 7 8 1 2 1 1 3 4 EXV Unit 60 Hz EXV Unit 50 Hz A B C D E F G H J K L M W I NPTI W O NPTI Drain FPT 006 019 N A 19 1 2 31 1 4 21 1 2 11 1 2 4 1 3 4 9 1 2 15 17 6 7 8 8 3 4 1 2 1 2 ...

Page 25: ...1 4 16 1 2 6 1 2 2 1 4 HIGH VOLTAGE 7 8 DIA LEFT SIDE W I D NPTI A C B BLOWER ACCESS PANEL 18 3 8 7 5 8 14 1 2 1 4 7 8 18 3 4 5 8 3 1 8 BACK SIDE 1 1 4 RETURN AIR OPENING 1 DIA MOUNTING HOLE 4X s SUPPLY OPENING 1 DUCT FLANGE Table 14 Dimensional data right return left supply GEH 6 to 10 tons 60 Hz GEH 6 to 7 5 tons 50 Hz GEH 60 Hz GEH 50 Hz A B C D 072 36 1 4 in 15 5 8 in 6 5 8 in 1 1 4 in 090 072...

Page 26: ...OLT 1 1 8 DIA W O D NPTI 16 1 2 23 1 4 WCI mounting location 2 1 4 6 1 2 HIGH VOLTAGE 7 8 DIA LEFT SIDE RETURN AIR OPENING W I D NPTI 4 7 8 14 1 2 18 3 4 1 1 4 5 8 1 DIA MOUNTING HOLE 4X s SUPPLY OPENING 1 DUCT FLANGE Table 15 Dimensional data right return back supply GEH 6 to 10 tons 60 Hz GEH 6 to 7 5 tons 50 Hz GEH 60 Hz GEH 50 Hz A B C D 072 36 1 4 in 15 5 8 in 6 5 8 in 1 1 4 in 090 072 36 1 8...

Page 27: ...NG HOLE 4X S SUPPLY OPENING 1 DUCT FLANGE DRAIN CONNECTION 1 2 SCHEDULE 40 PVC BACK SIDE 3 1 8 14 1 2 1 4 7 8 18 3 4 5 8 1 1 4 85 81 A C B BLOWER ACCESS PANEL TOP VIEW 18 3 8 7 5 8 1 1 4 24 3 4 1 3 4 74 1 2 79 4 5 8 40 5 8 36 Table 16 Dimensional data left return right supply GEH 6 to 10 tons 60 Hz GEH 6 to 7 5 tons 50 Hz GEH 60 Hz GEH 50 Hz A B C D 072 36 1 8 in 17 in 8 in 1 1 4 in 090 072 36 1 8...

Page 28: ... 4 5 8 40 5 8 36 1 1 2 W O D NPTI 24 VOLT 1 1 8 DIA A C B 1 1 4 5 8 3 1 8 4 7 8 18 3 4 14 1 2 W I D NPTI HIGH VOLTAGE 7 8 DIA LEFT SIDE 6 1 2 6 1 2 2 1 4 RETURN AIR OPENING SUPPLY OPENING 1 DUCT FLANGE 1 DIA MOUNTING HOLE 4X S Table 17 Dimensional data left return back supply GEH 6 to 10 tons 60 Hz GEH 6 to 7 5 tons 50 Hz GEH 60 Hz GEH 50 Hz A B C D 072 36 1 8 in 17 in 8 in 1 1 4 in 090 072 36 1 8...

Page 29: ... 1 8 21 3 8 87 91 2 1 4 29 3 4 BLOWER ACCESS PANEL 3 1 8 4 7 8 1 1 3 8 23 3 4 16 3 4 DRAIN CONNECTION 1 2 SCHEDULE 40 PVC 2 5 5 8 24 7 8 61 1 4 W O 1 1 2 NPTI W I 1 1 2 NPTI 24 VOLT 1 1 8 DIA HIGH VOLTAGE 7 8 DIA 30 1 4 22 3 4 2 1 4 9 1 8 2 1 4 RETURN AIR OPENING 1 DIA MOUNTING HOLE 4X S SUPPLY OPENING 1 DUCT FLANGE TOP VIEW BACK SIDE LEFT SIDE WCI mounting location ...

Page 30: ... 8 WCI mounting location 7 1 8 29 3 4 21 3 8 2 85 74 1 2 87 91 42 46 5 8 4 5 8 BLOWER ACCESS PANEL TOP VIEW LEFT SIDE 1 3 8 2 4 7 8 23 3 4 3 1 8 DRAIN CONNECTION 1 2 SCHEDULE 40 PVC 16 3 4 24 7 8 5 5 8 61 1 4 W O 1 1 2 NPTI 24 VOLT 1 1 8 DIA 1 1 2 22 3 4 30 1 4 HIGH VOLTAGE 7 8 DIA RETURN AIR OPENING 1 DIA MOUNTING HOLE 4X S SUPPLY OPENING 1 DUCT FLANGE ...

Page 31: ...N 1 2 SCHEDULE 40 PVC 5 5 8 24 7 8 30 1 4 22 3 4 LEFT SIDE WCI mounting location 85 74 1 2 4 5 8 46 5 8 42 29 3 4 2 1 4 21 3 8 7 1 8 87 91 TOP VIEW BLOWER ACCESS PANEL 2 1 8 W O 1 1 2 NPTI 24 VOLT 1 1 8 DIA 39 1 2 2 1 4 7 8 3 1 8 BACK SIDE 9 1 8 2 1 4 W I 1 1 2 NPTI HIGH VOLTAGE 7 8 DIA RETURN AIR OPENING SUPPLY OPENING 1 DUCT FLANGE 1 DIA MOUNTING HOLE 4X S ...

Page 32: ...29 3 4 TOP VIEW 21 3 8 7 1 8 4 5 8 2 BLOWER ACCESS PANEL 3 1 8 4 7 8 1 3 8 23 3 4 DRAIN CONNECTION 1 2 SCHEDULE 40 PVC 2 16 3 4 5 5 8 24 7 8 39 1 2 W O 1 1 2 NPTI W I 1 1 2 NPTI 24 VOLT 1 1 8 DIA HIGH VOLTAGE 7 8 DIA 30 1 4 22 3 4 2 1 4 9 1 8 2 1 8 LEFT SIDE RETURN AIR OPENING 1 DIA MOUNTING HOLE 4X S SUPPLY OPENING 1 DUCT FLANGE WCI mounting location ...

Page 33: ...3 8 36 1 4 13 1 2 46 1 2 62 5 8 B W O C NPTI DRAIN 3 4 NPTI A 11 1 2 1 7 8 W I C NPTI HIGH VOLTAGE 7 8 DIA 1 5 8 5 15 24 VOLT 1 1 8 22 3 8 38 7 8 3 4 SUPPLY OPENING 1 DUCT FLANGE RETURN AIR OPENING WCI mounting location Table 18 Dimensional data front return back supply GEV 6 to 10 tons 60 Hz 6 and 7 5 tons 50 Hz Unit 60 Hz Unit 50 Hz A B C 6 ton 6 5 8 in 18 3 8 in 1 1 4 in 7 5 ton 6 ton 6 5 8 in ...

Page 34: ... 31 3 8 36 1 4 13 3 8 63 62 5 8 B W O C NPTI DRAIN 3 4 NPTI A 11 1 2 1 7 8 W I C NPTI HIGH VOLTAGE 7 8 DIA 1 5 8 5 15 24 VOLT 1 1 8 22 3 8 38 7 8 3 4 1 SUPPLY OPENING 1 DUCT FLANGE RETURN AIR OPENING WCI mounting location Table 19 Dimensional data front return top supply GEV 6 to 10 tons 60 Hz 6 and 7 5 tons 50 Hz Unit 60 Hz Unit 50 Hz A B C 6 ton 6 5 8 in 18 3 8 in 1 1 4 in 7 5 ton 6 ton 6 5 8 in...

Page 35: ... 36 1 4 31 3 8 62 5 8 46 1 2 B W O C NPTI DRAIN 3 4 NPTI A 11 1 2 1 7 8 W I C NPTI HIGH VOLTAGE 7 8 DIA 1 5 8 5 15 38 7 8 22 3 8 3 4 SUPPLY OPENING 1 DUCT FLANGE RETURN AIR OPENING 24 VOLT 1 1 8 13 1 2 WCI mounting location Table 20 Dimensional data back return front supply GEV 6 to 10 tons 60 Hz 6 and 7 5 ton 50 Hz Unit 60 Hz Unit 50 Hz A B C 6 ton 6 5 8 in 18 3 8 in 1 1 4 in 7 5 ton 6 ton 6 5 8 ...

Page 36: ... 31 3 8 36 1 4 13 1 2 63 62 5 8 B W O C NPTI DRAIN 3 4 NPTI A 11 1 2 1 7 8 W I C NPTI HIGH VOLTAGE 7 8 DIA 1 5 8 5 15 24 VOLT 1 1 8 38 7 8 22 3 8 3 4 1 SUPPLY OPENING 1 DUCT FLANGE RETURN AIR OPENING WCI mounting location Table 21 Dimensional data back return top supply GEV 6 to 10 tons 60 Hz 6 and 7 5 ton 50 Hz Unit 60 Hz Unit 50 Hz A B C 6 ton 6 5 8 in 18 3 8 in 1 1 4 in 7 5 ton 6 ton 6 5 8 in 1...

Page 37: ...00 front return must be a non ducted return RETURN AIR OPENING W I 1 1 2 NPTI 2 5 8 4 1 4 12 1 2 23 1 2 DRAIN 3 4 NPTI W O 1 1 2 NPTI 38 7 8 27 1 8 67 5 8 31 1 2 18 5 8 1 HIGH VOLTAGE 7 8 O D 20 1 2 20 1 2 6 7 8 2 3 8 15 7 8 49 1 8 24 VOLT 1 1 8 O D 74 1 2 81 5 8 31 1 2 36 1 4 4 3 4 CONTROL BOX ACCESS TOP VIEW FRONT VIEW SIDE VIEW 10 WCI mounting location ...

Page 38: ...RETURN AIR OPENING W I 1 1 2 NPTI 2 5 8 4 1 4 12 1 2 10 23 1 2 DRAIN 3 4 NPTI W O 1 1 2 NPTI 38 7 8 27 1 8 67 5 8 31 1 2 18 5 8 1 HIGH VOLTAGE 7 8 22 O D 20 1 2 20 1 2 2 6 7 8 2 3 8 15 7 8 49 1 8 74 1 2 81 5 8 31 1 2 36 1 4 4 3 4 CONTROL BOX ACCESS TOP VIEW FRONT VIEW SIDE VIEW 1 8 24 VOLT 1 1 8 O D WCI mounting location ...

Page 39: ...st be a non ducted return RETURN AIR OPENING SUPPLY OPENING WITH 1 DUCT FLANGE W I 1 1 2 NPTI 2 5 8 4 1 4 12 1 2 23 1 2 15 7 8 14 3 8 DRAIN 3 4 NPTI W O 1 1 2 NPTI 38 7 8 27 1 8 68 31 1 2 18 5 8 1 HIGH VOLTAGE 7 8 O D 20 1 2 2 3 8 74 1 2 81 5 8 31 1 2 36 1 4 4 3 4 27 20 1 2 2 6 7 8 10 CONTROL BOX ACCESS TOP VIEW FRONT VIEW SIDE VIEW 24 VOLT 1 1 8 O D WCI mounting location ...

Page 40: ...e a non ducted return RETURN AIR OPENING SUPPLY OPENING WITH 1 DUCT FLANGE W I 1 1 2 NPTI 2 5 8 4 1 4 12 1 2 23 1 2 15 7 8 14 3 8 DRAIN 3 4 NPTI W O 1 1 2 NPTI 38 7 8 27 1 8 68 31 1 2 18 5 8 1 HIGH VOLTAGE 7 8 O D 20 1 2 20 1 2 2 6 7 8 2 3 8 74 1 2 81 5 8 31 1 2 36 1 4 4 3 4 CONTROL BOX ACCESS TOP VIEW FRONT VIEW SIDE VIEW 1 8 24 VOLT 1 1 8 O D 15 7 10 WCI mounting location ...

Page 41: ...0 1 2 20 1 2 6 7 8 2 3 8 B D 24 VOLT 1 1 8 O D 74 1 2 81 5 8 31 1 2 36 1 4 4 3 4 6 1 4 19 1 8 CONTROL BOX ACCESS TOP VIEW FRONT VIEW SIDE VIEW WCI mounting location Table 22 Dimensional data front return back supply GEV 20 and 25 ton 60 Hz GEV 15 and 20 ton 50 Hz Unit 60 Hz Unit 50 Hz A B C D E 20 ton 15 ton 15 5 8 in 13 1 2 in 12 in 51 5 8 in 20 7 8 in 25 ton Std Static 20 ton Std Static 14 3 4 i...

Page 42: ...6 7 8 2 3 8 B D 74 1 2 81 5 8 31 1 2 36 1 4 4 3 4 6 1 4 CONTROL BOX ACCESS TOP VIEW FRONT VIEW SIDE VIEW RETURN AIR OPENING 1 8 24 VOLT 1 1 8 O D WCI mounting location Table 23 Dimensional data back return front supply GEV 20 and 25 ton 60 Hz GEV 15 and 20 ton 50 Hz Unit 60 Hz Unit 50 Hz A B C D E 20 ton 15 ton 15 5 8 in 13 1 2 in 12 in 51 5 8 in 20 7 8 in 25 ton Std Static 20 ton Std Static 14 3 ...

Page 43: ... A 1 25 4 HIGH VOLTAGE 7 8 O D 20 1 2 2 3 8 74 1 2 81 5 8 31 1 2 36 1 4 4 3 4 27 20 1 2 6 7 8 19 1 8 1 1 4 6 1 4 CONTROL BOX ACCESS TOP VIEW FRONT VIEW SIDE VIEW 24 VOLT 1 1 8 O D WCI mounting location Table 24 Dimensional data front return top supply GEV 20 and 25 ton 60 Hz GEV 15 and 20 ton 50 Hz Unit 60 Hz Unit 50 Hz A B C D 20 ton 15 ton 15 5 8 in 13 1 2 in 12 in 20 7 8 in 25 ton Std Static 20...

Page 44: ...4 68 20 1 2 6 7 8 19 1 8 1 1 4 RETURN AIR OPENING SUPPLY OPENING WITH 1 DUCT FLANGE B 1 1 6 1 4 CONTROL BOX ACCESS TOP VIEW FRONT VIEW SIDE VIEW 24 VOLT 1 1 8 O D WCI mounting location Table 25 Dimensional data back return top supply GEV 20 and 25 ton 240 and 300 60 Hz GEV 15 and 20 ton 180 and 240 50 Hz Unit 60 Hz Unit 50 Hz A B C D 20 ton 15 ton 15 5 8 in 13 1 2 in 12 in 20 7 8 in 25 ton Std Sta...

Page 45: ...4 7 1 2 1 2 1 4 18 1 2 018 030 015 024 3 4 3 4 18 1 2 15 5 8 1 1 2 13 3 4 26 3 1 4 6 7 8 1 2 1 4 18 1 2 035 042 030 036 3 4 3 4 21 17 5 8 2 1 4 16 1 2 30 3 3 4 6 1 4 1 1 4 2 4 1 2 23 1 2 048 060 042 060 1 1 23 1 8 19 5 8 2 1 2 19 1 2 34 5 1 4 5 7 8 1 1 4 2 4 1 2 23 1 2 EXH 60 Hz EXH 50 Hz A NPTI B NPTI C D E F G H J K L M N 006 015 1 2 1 2 16 1 8 13 5 8 1 1 2 10 3 4 23 2 1 4 7 1 2 1 2 1 4 18 1 2 0...

Page 46: ... 3 4 17 0 54 lbs 84 lbs 018 030 015 024 44 3 4 21 3 4 24 3 4 21 1 65 lbs 95 lbs 035 042 030 036 48 3 4 23 3 4 28 3 4 21 2 76 lbs 106 lbs 048 060 042 048 56 3 4 31 3 4 32 3 4 25 1 97 lbs 127 lbs EXH Unit 60 Hz EXH Unit 50 Hz A B C D E Hanging Weight Shipping Weight 006 015 38 3 4 18 3 4 21 3 4 17 0 54 lbs 84 lbs 018 024 44 3 4 21 3 4 24 3 4 21 1 65 lbs 95 lbs 030 036 48 3 4 23 3 4 28 3 4 21 2 76 lb...

Page 47: ... 6 to 7 5 tons 50 Hz left return with waterside economizer a a Field piping required on waterside economizer C 9 7 8 36 50 5 8 B OD COPPER TO FIELD SUPPLY PIPING 18 1 2 24 3 4 1 1 4 D E A NPTI FOR FIELD RETURN PIPING Table 28 Dimensional data GEH 6 to 10 tons 60 Hz GEH 6 to 7 5 tons 50 Hz waterside economizer GEH 60 Hz GEH 50 Hz A B C D E Hanging Weight Shipping Weight 072 1 1 4 1 3 8 31 9 7 8 3 7...

Page 48: ...n waterside economizer 48 3 4 9 7 8 42 56 1 2 1 5 8 OD COPPER TO FIELD SUPPLY PIPING 18 1 2 29 3 4 2 1 4 12 5 3 8 1 1 2 NPTI FOR FIELD RETURN PIPING Table 29 Dimensional data GEH 12 5 to 15 tons 60 Hz GEH 10 to 12 5 tons 50 Hz right return with waterside economizer GEH 60 Hz GEH 50 Hz Hanging Weight Shipping Weight 150 120 138 lbs 168 lbs 180 150 144 lbs 174 lbs ...

Page 49: ...quired on waterside economizer 27 1 8 9 7 8 42 56 1 2 1 5 8 OD COPPER TO FIELD SUPPLY PIPING 18 1 2 29 3 4 2 1 4 12 5 3 8 1 1 2 NPTI FOR FIELD RETURN PIPING Table 30 Dimensional data GEH 12 5 to 15 tons 60 Hz GEH 10 to 12 5 tons 50 Hz left return with waterside economizer GEH 60 Hz GEH 50 Hz Hanging Weight Shipping Weight 150 180 120 150 213 lbs 243 lbs ...

Page 50: ... RETURN PIPING 13 1 4 13 C 2 1 4 B TO FIELD SUPPLY PIPING Table 31 Dimensional data GEV 6 to 10 tons 60 Hz 6 and 7 5 tons 50 Hz waterside economizer Unit 60 Hz Unit 50 Hz A B C Hanging Weight Shipping Weight 072 1 1 4 1 3 8 4 148 lbs 178 lbs 090 072 1 1 4 1 1 4 4 168 lbs 198 lbs 120 090 1 1 2 1 5 8 4 3 8 207 lbs 237 lbs ...

Page 51: ...ELD RETURN PIPING 2 3 4 B TO FIELD SUPPLY PIPING Table 32 Dimensional data GEV 12 5 to 25 tons waterside economizer GEV 60 Hz GEV 50 Hz A NPTI B I D C D Hanging Weight Shipping Weight 150 180 120 150 1 1 2 1 5 8 15 7 8 4 3 8 275 lbs 305 lbs 240 180 2 2 1 8 16 1 4 4 7 8 310 lbs 340 lbs 300 240 2 2 1 8 16 1 4 4 7 8 395 lbs 425 lbs ...

Page 52: ...pplicable only to 6 to 25 ton models Unit Water Outlet Unit Heat Exchanger Unit Water Inlet TEE WSE Coil Outlet WSE Coil WSE Coil Inlet Port A 3 Way Valve Port AB Port B Entering Water Please match the entering water port marking with the marking label on the valve prior to using this diagram ...

Page 53: ...Weight without pallet lbs 006 195 165 009 195 165 012 203 173 015 203 173 018 284 264 024 301 269 030 319 299 036 333 313 042 402 381 048 422 374 060 442 394 070 482 434 Table 36 Unit weights EXH 5 to 6 tons EXH 60 Hz Shipping Weight with pallet lbs Unit Weight without pallet lbs 006 195 165 009 195 165 012 203 173 015 203 173 018 284 264 024 301 269 030 329 299 036 343 313 042 461 431 048 454 424...

Page 54: ...mpressor contactor on the 5 to 5 ton for GEH V 5 to 5 ton and EXH V 5 to 6 ton units or 1TB1 for GEH V 6 to 25 ton equipment in the unit control panel 4 Install proper grounding wires to an earth ground EXH and EXV 460 V units require a neutral a four wire system Note All field installed wiring must comply with NEC and applicable local codes Electric Heat Requirements 5 Verify that the power suppl...

Page 55: ...to prevent operating sounds from transmitting through the ductwork Elbows with turning vanes or splitters are recommended tominimizeairnoiseduetoturbulenceandtoreducestatic pressure Ducted Panel The return air arrangement may be easily converted from a free return air system to a ducted return air system with the addition of a return air side panel By replacing the filter racks with the return air...

Page 56: ...t panel to the return air opening with the six screws provided for the filter rack assembly Table 38 Opening size and part number EXH EXH 60 hz A in B in Duct Collar Part Number 006 015 17 1 2 13 447411330100 018 024 20 1 2 16 447456280100 030 036 22 1 2 17 447411350100 042 070 26 1 2 19 447411360100 When it is necessary to have filter access at the unit in a ducted return a ducted filter rack is ...

Page 57: ...ty of the contractor Condensate Drain Connection Install proper trapping to the equipment The unit drain connection is 75 in NPT for all GEV 5 to 25 ton and GEH 5 to 5 ton and EXH V 5 to 6 ton models For 6 to15 ton GEH models the drain connection is 5 in PVC schedule 40 pipe When designing the condensate trap for the water source system it is important to consider the unit draw thru design requiri...

Page 58: ...heat exchanger in the water circulating system Note Vents should be open when the pumps and supplementary heat system are shut down Field Installed Power Wiring Verify that the power supply available is compatible with the unit s nameplate Use only copper conductors to connect the power supply to the unit Main Unit Power Wiring A field supplied disconnect switch must be installed at or near the un...

Page 59: ...pment sizes are shown in Figure 59 p 59 WARNING Hazardous Voltage Failure to disconnect power before servicing could result in death or serious injury Disconnect all electric power including remote disconnects before servicing Follow proper lockout tagout procedures to ensure the power can not be inadvertently energized Figure 58 Thermostat sensor location 5 Feet YES NO NO NO O NOTICE Component Fa...

Page 60: ...T8511 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1TB2 24 VAC R FAN G COMPRESSOR 1 Y1 COMPRESSOR 2 Y2 REVERSING VALVE 0 HUMIDISTAT 24 VAC COMMON C WATER ISOLATION VA COMPRESSOR DISABLE COMPRESSOR DISABLE ALARM ALARM ELECTRIC HEAT ELECTRIC HEAT HUMIDISTAT WATER ISOLATION VALVE 3RD STAGE HEAT W3 NOT USED Deluxe Controls with all Heat Pump Units w Reheat using X13511091010 X13511092010 T7300 1 2 3 4 5 6 7...

Page 61: ...lt tension loosen the adjustment bolt and pull motor mounting plate back until the belt is tight Tighten the adjustment bolt after the belt has reached the desired tension See Figure 66 p 62 for fan motor and sheave adjustment Figure 63 Wiring change Figure 64 Connecting speed tap wire Table 41 4 speed motor 115 208 230 265 Lead Colors Lead Black Blue Orange Red Speed High Medium High Medium Low L...

Page 62: ...ce them in a convenient location 3 Attach ducted panel to the water source heat pump unit with six factory provided screws This panel is shipped loose with the water source heat pump but must be field installed to the unit Figure 66 Fan motor and sheave adjustment 1 Belt 2 Adjustment Bolt and Plate 3 Sheave Figure 67 ECM control board and dip switch setting 2 3 1 Dip switch to select profile WARNI...

Page 63: ...ided hose between the upper most piping connection of the economizer and the water in of the heat pump The hose is shipped loose with the water side economizer 6 Install the SUPPLY and RETURN hoses to the a 2 position valve s threaded connection b water out threaded connection of the water source heat pump 7 Verify the control board for the water side economizer is located at the back of the contr...

Page 64: ...iagram located on the service control panel RED 1TB1 14 BLK 1TB1 18 WHT 1TB1 15 See Figure 77 p 64 13 Bundle excess valve wire and wire tie the bundle neatly See Figure 78 p 64 14 Install control side service panel 15 Install the hanging isolation grommets see Figure 79 p 64 into the hanging bracketsThe unit isolators were located in the return air section of the unit See Step 2 Isolators for the ...

Page 65: ...plied to each economizer side GEV ONLY Secure the bracket on the bottom of the economizer cabinet to the unit compressor compartment center post 8 Install the field portion of the water piping and the 3 way valve together 9 Verify the control board for the waterside economizer is located at the back of the control box The temperature rating of this board is factory set to 55ºF 10 Thread the econom...

Page 66: ...kage with field supplied pipe insulation Insulating the piping will help stop condensation from forming on the pipe Notes Trane does not provide insulation on the economizing piping package This insulation must be field provided and field installed Trane does not provide condensate overflow protection of the waterside economizer This must be field provided and field installed 20 Install waterside ...

Page 67: ...sor operation will halt allowing for free cooling in the space 5 Turn the thermostat system switch to the OFF position Unit should stop running and the reversing valve should de energize 6 Leave unit off for approximately FIVE minutes to allow for pressure equalization 7 Turn the thermostat to the lowest setting 8 Set the thermostat system switch to the HEAT position 9 Adjust the temperature setti...

Page 68: ...20 135 second stroke time 33 Cv at full port GEV GEH 10 15 Ton GEV GEH 7 5 12 5 Ton 1 5 FPT 600 psi 200 psi 0ºF to 212ºF 18ºC to 121ºC Non spring return type 24 VAC 20 135 second stroke time 37 Cv at full port GEV 20 25 Ton GEV 15 20 Ton 2 FPT 600 psi 200 psi 0ºF to 212ºF 18ºC to 121ºC Non spring return type 24 VAC 20 135 second stroke time 57 Cv at full port EXH006 015 1 2 FPT 600 psi 200 psi 0ºF...

Page 69: ... 70 1 8 1 8 58 15 0 0 0 0 GEH V012 230 60 1 9 4 6 3 30 0 1 8 8 0 70 1 8 1 11 74 15 2 0 8 7 GEH V012 265 60 1 5 7 5 0 23 0 1 7 0 0 72 1 8 1 6 97 15 0 0 0 0 GEH V012 265 60 1 10 7 5 0 23 0 1 7 0 0 72 1 8 1 13 40 15 2 7 10 0 GEH V015 208 60 1 8 6 7 9 36 0 1 11 1 0 70 1 8 1 10 58 15 0 0 0 0 GEH V015 208 60 1 10 3 7 9 36 0 1 11 1 0 70 1 8 1 12 89 15 2 0 9 6 GEH V015 230 60 1 8 6 7 9 36 0 1 11 1 0 70 1 ...

Page 70: ...23 33 25 6 0 15 1 GEH035 460 60 3 7 3 5 6 38 0 1 8 8 1 70 1 2 1 8 70 15 0 0 0 0 GEH035 460 60 3 11 7 5 6 38 0 1 8 8 1 70 1 2 1 14 60 15 8 0 10 0 GEV036 208 60 1 20 3 16 7 79 0 1 26 0 3 60 1 2 1 24 48 40 0 0 0 0 GEV036 208 60 1 27 2 16 7 79 0 1 26 0 3 60 1 2 1 33 95 40 4 9 23 6 GEV036 230 60 1 20 3 16 7 79 0 1 26 0 3 60 1 2 1 24 48 40 0 0 0 0 GEV036 230 60 1 29 7 16 7 79 0 1 26 0 3 60 1 2 1 37 11 4...

Page 71: ...060 208 60 3 23 4 15 6 110 0 1 24 4 5 40 1 1 29 30 40 6 5 18 0 GEH V060 230 60 3 21 0 15 6 110 0 1 24 4 5 40 1 1 24 90 40 0 0 0 0 GEH V060 230 60 3 25 5 15 6 110 0 1 24 4 5 40 1 1 31 85 40 8 0 20 1 GEH V060 460 60 3 10 5 7 8 52 0 1 12 1 2 70 1 1 12 45 20 0 0 0 0 GEH V060 460 60 3 16 0 7 8 52 0 1 12 1 2 70 1 1 20 01 25 10 6 13 3 GEH V060 575 60 3 8 0 5 8 38 9 1 9 1 2 20 1 1 9 45 15 0 0 0 0 GEH072 2...

Page 72: ... 4 3 0 1 45 40 60 GEH120 230 60 3 40 2 16 110 2 24 9 8 2 3 0 1 44 20 60 GEH120 460 60 3 19 7 7 8 52 2 12 1 4 1 3 0 1 21 65 25 GEH120 575 60 3 14 7 5 7 38 9 2 8 9 3 3 3 0 1 16 13 20 GEH120 208 60 3 46 0 16 110 2 24 9 14 0 5 0 1 50 00 60 GEH120 230 60 3 45 0 16 110 2 24 9 13 0 5 0 1 49 00 60 GEH120 460 60 3 22 1 7 8 52 2 12 1 6 5 5 0 1 24 05 30 GEH120 575 60 3 16 7 5 7 38 9 2 8 9 5 3 5 0 1 18 13 20 ...

Page 73: ...EV072 208 60 1 44 6 16 7 79 2 26 11 2 2 0 1 48 78 60 GEV072 230 60 1 43 6 16 7 79 2 26 10 2 2 0 1 47 81 60 GEV072 208 60 3 24 3 10 4 73 2 16 3 3 5 1 0 1 26 90 35 GEV072 230 60 3 24 6 10 4 73 2 16 3 3 8 1 0 1 27 20 35 GEV072 460 60 3 13 4 5 8 38 2 9 1 8 1 0 1 14 85 20 GEV072 208 60 3 26 4 10 4 73 2 16 3 5 6 1 5 1 29 00 35 GEV072 230 60 3 25 6 10 4 73 2 16 3 4 8 1 5 1 28 20 35 GEV072 460 60 3 14 0 5...

Page 74: ...2 35 7 1 2 0 1 57 50 70 GEV150 230 60 3 51 0 22 4 149 2 35 6 2 2 0 1 56 60 70 GEV150 460 60 3 24 3 10 6 75 2 16 5 3 1 2 0 1 26 96 35 GEV150 575 60 3 17 7 7 7 54 2 12 2 3 2 0 1 19 63 25 GEV150 208 60 3 54 2 22 4 149 2 35 9 4 3 0 1 59 80 80 GEV150 230 60 3 53 0 22 4 149 2 35 8 2 3 0 1 58 60 80 GEV150 460 60 3 25 3 10 6 75 2 16 5 4 1 3 0 1 27 95 35 GEV150 575 60 3 18 7 7 7 54 2 12 3 3 3 0 1 20 63 25 ...

Page 75: ... 4 7 5 1 127 63 175 GEV300 460 60 3 46 9 18 6 125 2 29 9 7 7 5 1 51 55 70 GEV300 575 60 3 37 4 14 7 100 2 23 8 0 7 5 1 41 08 50 GEV300 208 60 3 122 2 48 1 245 2 75 26 0 10 0 1 134 23 175 GEV300 230 60 3 121 2 48 1 245 2 75 25 0 10 0 1 133 23 175 GEV300 460 60 3 49 7 18 6 125 2 29 12 5 10 0 1 54 35 70 GEV300 575 60 3 39 4 14 7 100 2 23 10 0 10 0 1 43 08 50 GEV300 208 60 3 133 2 48 1 245 2 75 37 0 1...

Page 76: ...3 1 17 41 20 2 5 11 8 GEH V018 230 60 1 11 7 9 6 42 0 1 13 4 2 10 1 3 1 14 10 20 0 0 0 0 GEH V018 230 60 1 15 1 9 6 42 0 1 13 4 2 10 1 3 1 18 93 20 3 0 13 0 GEH V018 265 60 1 9 2 7 7 35 0 1 10 8 1 53 1 3 1 11 16 15 0 0 0 0 GEH V018 265 60 1 16 6 7 7 35 0 1 10 8 1 53 1 3 1 20 78 25 4 0 15 1 GEH V024 208 60 1 14 9 12 8 58 3 1 20 0 2 10 1 3 1 18 10 30 0 0 0 0 GEH V024 208 60 1 17 8 12 8 58 3 1 20 0 2...

Page 77: ...2 77 1 2 1 40 96 45 8 0 30 0 GEV036 208 60 3 14 0 10 4 73 0 1 16 3 3 60 1 2 1 16 60 25 0 0 0 0 GEV036 208 60 3 17 2 10 4 73 0 1 16 3 3 60 1 2 1 21 50 25 4 9 13 6 GEV036 230 60 3 14 0 10 4 73 0 1 16 3 3 60 1 2 1 16 60 25 0 0 0 0 GEV036 230 60 3 18 7 10 4 73 0 1 16 3 3 60 1 2 1 23 33 25 6 0 15 1 GEH V036 380 415 50 3 7 7 6 0 44 0 1 9 3 1 70 1 2 1 9 20 15 0 0 0 0 GEH V036 380 415 50 3 11 6 6 0 44 0 1...

Page 78: ...mp RLA ea Comp LRA ea No of Comp Cmp MCC Blower Motor FLA Blower Motor hp Fan Motor Num Minimum Circuit Ampacity Maximum Overcurrent Protective Device Electric Heat kW Electric Heat Amps Table 49 Electrical data ECM motors 5 to 6 tons EXH EXV Model No Volts Total Unit FLA Comp RLA ea Comp LRA ea Blower Motor FLA Blower Motor hp Minimum Circuit Ampacity Maximum Overcurrent Protective Device Electri...

Page 79: ... 1 18 10 14 1 77 0 4 00 3 4 21 63 35 0 0 0 0 EXH036 230 60 1 30 09 14 1 77 0 4 00 3 4 37 61 40 6 0 26 1 EXH036 265 60 1 15 70 12 2 72 0 3 50 3 4 18 75 30 0 0 0 0 EXH036 265 60 1 33 50 12 2 72 0 3 50 3 4 41 88 45 8 0 30 0 EXH036 208 60 3 13 00 9 0 71 0 4 00 3 4 15 25 20 0 0 0 0 EXH036 208 60 3 17 60 9 0 71 0 4 00 3 4 22 00 25 4 9 13 6 EXH036 230 60 3 13 00 9 0 71 0 4 00 3 4 15 25 20 0 0 0 0 EXH036 ...

Page 80: ... 63 50 6 5 18 0 EXH070 230 60 3 27 50 20 5 155 0 7 00 1 32 63 50 0 0 0 0 EXH070 230 60 3 27 50 20 5 155 0 7 00 1 33 85 50 8 0 20 1 EXH070 460 60 3 15 70 9 6 75 0 6 10 1 18 10 25 0 0 0 0 EXH070 460 60 3 19 40 9 6 75 0 6 10 1 24 26 25 10 6 13 3 EXV006 208 60 1 3 76 3 3 14 0 0 46 1 3 4 59 15 0 0 0 0 EXV006 208 60 1 4 40 3 3 14 0 0 46 1 3 5 50 15 0 8 3 9 EXV006 230 60 1 3 66 3 2 15 0 0 46 1 3 4 46 15 ...

Page 81: ...1 18 10 14 1 77 0 4 00 3 4 21 63 35 0 0 0 0 EXV036 208 60 1 27 56 14 1 77 0 4 00 3 4 34 45 35 4 9 23 6 EXV036 230 60 1 18 10 14 1 77 0 4 00 3 4 21 63 35 0 0 0 0 EXV036 230 60 1 30 09 14 1 77 0 4 00 3 4 37 61 40 6 0 26 1 EXV036 265 60 1 15 70 12 2 72 0 3 50 3 4 18 75 30 0 0 0 0 EXV036 265 60 1 33 50 12 2 72 0 3 50 3 4 41 88 45 8 0 30 0 EXV036 208 60 3 13 00 9 0 71 0 4 00 3 4 15 25 20 0 0 0 0 EXV036...

Page 82: ...EXV070 230 60 1 41 78 30 1 158 0 7 00 1 52 23 70 8 0 34 8 EXV070 208 60 3 27 50 20 5 155 0 7 00 1 32 63 50 0 0 0 0 EXV070 208 60 3 27 50 20 5 155 0 7 00 1 32 63 50 6 5 18 0 EXV070 230 60 3 27 50 20 5 155 0 7 00 1 32 63 50 0 0 0 0 EXV070 230 60 3 27 50 20 5 155 0 7 00 1 33 85 50 8 0 20 1 EXV070 460 60 3 15 70 9 6 75 0 6 10 1 18 10 25 0 0 0 0 EXV070 460 60 3 19 40 9 6 75 0 6 10 1 24 26 25 10 6 13 3 ...

Page 83: ...50 208 60 3 49 7 22 4 149 2 35 4 9 1 5 1 55 30 70 GEH150 230 60 3 49 2 22 4 149 2 35 4 4 1 5 1 54 80 70 GEH150 460 60 3 23 4 10 6 75 2 16 5 2 2 1 5 1 26 05 35 GEH150 208 60 3 51 5 22 4 149 2 35 6 7 2 0 1 57 10 70 GEH150 230 60 3 50 9 22 4 149 2 35 6 1 2 0 1 56 50 70 GEH150 460 60 3 24 3 10 6 75 2 16 5 3 1 2 0 1 26 95 35 GEH150 208 60 3 53 6 22 4 149 2 35 8 8 3 0 1 59 20 80 GEH150 230 60 3 52 8 22 ...

Page 84: ... 40 90 50 GEV120 230 60 3 36 4 16 110 2 24 9 4 4 1 5 1 40 40 50 GEV120 460 60 3 17 8 7 8 52 2 12 1 2 2 1 5 1 19 75 25 GEV120 208 60 3 38 7 16 110 2 24 9 6 7 2 0 1 42 70 50 GEV120 230 60 3 38 1 16 110 2 24 9 6 1 2 0 1 42 10 50 GEV120 460 60 3 18 7 7 8 52 2 12 1 3 1 2 0 1 20 65 25 GEV120 208 60 3 40 8 16 110 2 24 9 8 8 3 0 1 44 80 60 GEV120 230 60 3 40 0 16 110 2 24 9 8 0 3 0 1 44 00 60 GEV120 460 6...

Page 85: ... 60 3 110 8 48 1 245 2 75 14 6 5 0 1 122 83 150 GEV300 230 60 3 109 4 48 1 245 2 75 13 2 5 0 1 121 43 150 GEV300 460 60 3 43 8 18 6 125 2 29 6 6 5 0 1 48 45 60 GEV300 208 60 3 118 3 48 1 245 2 75 22 1 7 5 1 130 33 175 GEV300 230 60 3 116 2 48 1 245 2 75 20 0 7 5 1 128 23 175 GEV300 460 60 3 47 2 18 6 125 2 29 10 0 7 5 1 51 85 70 GEV300 208 60 3 123 8 48 1 245 2 75 27 6 10 0 1 135 83 175 GEV300 230...

Page 86: ...und Source Heat Pump Systems Installation Guide Is vibration isolation provided i e unit isolation pad hose kits Is unit serviceable See clearance specifications in Unit Dimensions p 13 Are the low high side pressure temperature caps secure and in place Are all the unit access panels secure and in place Is the thermostat in the OFF position Is the water flow established and circulating through all...

Page 87: ...p 88 11 Set the thermostat to maintain the desired space temperature 12 Instruct the owner on system operation Start Up Checklist and Log Installing Contractor Use this checklist to thoroughly check out the system and units before and during start up This form need not be returned to the factory unless requested during technical service support Job Name ________________________ Model Number ______...

Page 88: ... 1 7 150 173 363 462 10 13 22 28 GEH GEV 009 60Hz GEH GEV 006 50 Hz 35 1 7 93 107 272 346 6 7 20 26 GEH GEV 009 60Hz GEH GEV 006 50 Hz 35 2 1 95 110 274 348 5 6 21 27 GEH GEV 009 60Hz GEH GEV 006 50 Hz 45 1 7 142 164 187 238 13 16 22 28 109 126 288 366 7 9 24 30 GEH GEV 009 60Hz GEH GEV 006 50 Hz 45 2 1 142 164 181 230 11 14 22 27 112 129 291 370 6 7 24 31 GEH GEV 009 60Hz GEH GEV 006 50 Hz 55 1 7...

Page 89: ...H GEV 012 50 Hz 45 2 8 138 159 180 230 11 14 22 28 107 123 313 398 7 8 23 29 GEH GEV 015 60Hz GEH GEV 012 50 Hz 45 3 5 138 158 174 221 9 11 22 27 109 126 316 402 5 7 23 30 GEH GEV 015 60Hz GEH GEV 012 50 Hz 55 2 8 139 159 210 267 11 14 21 27 124 143 332 423 8 10 26 33 GEH GEV 015 60Hz GEH GEV 012 50 Hz 55 3 5 138 159 203 258 9 11 21 27 128 147 336 427 6 8 27 34 GEH GEV 015 60Hz GEH GEV 012 50 Hz 6...

Page 90: ... 488 12 15 19 24 GEH GEV 018 60Hz GEH GEV 015 50 Hz 95 4 2 144 166 372 473 9 12 19 25 GEH 024 60Hz GEH 018 50Hz 35 76 88 279 355 6 7 21 30 GEH 024 60Hz GEH 018 50Hz 35 78 89 280 357 5 6 21 31 GEH 024 60Hz GEH 018 50Hz 45 4 5 114 131 172 219 12 16 20 26 89 103 290 369 7 9 24 34 GEH 024 60Hz GEH 018 50Hz 45 5 6 114 131 165 211 10 13 20 26 91 105 292 371 6 7 24 34 GEH 024 60Hz GEH 018 50Hz 55 4 5 115...

Page 91: ... 12 19 25 167 193 353 449 9 12 39 50 GEV 024 60Hz GEV 018 50Hz 95 4 5 127 146 349 445 12 15 19 25 GEV 024 60Hz GEV 018 50Hz 95 5 6 127 146 340 433 9 12 19 25 GEH 030 60 Hz GEH 024 50 Hz 35 77 89 276 351 6 7 21 30 GEH 030 60 Hz GEH 024 50 Hz 35 79 90 277 352 4 6 21 30 GEH 030 60 Hz GEH 024 50 Hz 45 5 6 120 138 171 218 12 15 22 27 91 104 290 369 7 8 24 34 GEH 030 60 Hz GEH 024 50 Hz 45 7 0 120 138 1...

Page 92: ... 19 25 161 185 345 439 11 14 38 49 GEV 030 60 Hz GEV 024 50 Hz 86 7 0 123 142 303 385 9 11 19 25 167 192 350 445 9 11 39 50 GEV 030 60 Hz GEV 024 50 Hz 95 5 6 125 144 351 447 11 14 19 25 GEV 030 60 Hz GEV 024 50 Hz 95 7 0 125 144 342 436 9 11 19 25 GEHE035 60 Hz 32 8 4 87 100 267 340 4 5 18 27 GEHE035 60 Hz 45 6 6 134 155 180 229 12 15 20 26 103 118 282 359 6 8 22 31 GEHE035 60 Hz 45 8 4 134 154 1...

Page 93: ...134 163 208 10 12 21 26 91 105 298 380 6 7 25 35 GEV 036 60 Hz GEV 030 50 Hz 55 6 7 118 136 198 251 12 15 20 26 106 122 315 401 8 10 28 38 GEV 036 60 Hz GEV 030 50 Hz 55 8 4 118 135 191 243 10 12 20 26 109 125 318 404 7 8 29 39 GEV 036 60 Hz GEV 030 50 Hz 68 6 7 121 139 238 303 12 15 20 25 128 147 341 434 10 12 33 43 GEV 036 60 Hz GEV 030 50 Hz 68 8 4 121 139 231 294 10 12 20 26 132 151 344 437 8 ...

Page 94: ... 7 8 116 133 173 220 12 16 21 26 86 99 283 360 7 9 23 33 GEV 042 60 Hz GEV 036 50 Hz 45 9 8 116 133 167 212 10 12 21 27 88 102 283 360 6 7 24 33 GEV 042 60 Hz GEV 036 50 Hz 55 7 8 117 135 201 256 12 15 20 26 103 118 298 380 8 10 27 37 GEV 042 60 Hz GEV 036 50 Hz 55 9 8 117 135 194 247 10 12 20 26 105 121 301 383 6 8 27 37 GEV 042 60 Hz GEV 036 50 Hz 68 7 8 122 140 242 308 12 15 20 26 122 140 318 4...

Page 95: ... 21 27 GEH 048 60 Hz GEH 042 50 Hz 95 11 2 130 149 354 451 10 12 21 27 GEV 048 60 Hz GEV 042 50 Hz 35 63 73 248 315 5 7 19 28 GEV 048 60 Hz GEV 042 50 Hz 35 64 74 249 316 4 5 19 28 GEV 048 60 Hz GEV 042 50 Hz 45 9 0 120 138 184 234 13 16 22 28 72 82 257 327 6 8 21 30 GEV 048 60 Hz GEV 042 50 Hz 45 11 2 119 137 177 225 10 13 22 28 73 84 259 329 5 6 21 30 GEV 048 60 Hz GEV 042 50 Hz 55 9 0 121 139 2...

Page 96: ...44 GEH 060 60 Hz GEH 048 50 Hz 86 11 2 121 139 309 393 12 15 19 25 151 174 347 442 11 14 37 48 GEH 060 60 Hz GEH 048 50 Hz 86 14 0 121 139 301 383 10 12 19 25 157 180 351 447 9 11 38 49 GEH 060 60 Hz GEH 048 50 Hz 95 11 2 123 141 348 442 12 15 19 25 GEH 060 60 Hz GEH 048 50 Hz 95 14 0 122 141 339 431 9 12 19 25 GEV 060 60 Hz GEV 048 50 Hz 35 70 81 261 332 6 7 20 30 GEV 060 60 Hz GEV 048 50 Hz 35 7...

Page 97: ... 16 41 50 GEH GEV 072 60 Hz 86 18 135 155 300 382 9 12 23 28 175 201 335 427 9 11 43 53 GEH GEV 072 60 Hz 95 12 137 158 356 453 13 17 22 27 GEH GEV 072 60 Hz 95 18 137 157 340 432 9 11 22 27 GEH GEV 090 60 Hz GEH GEV 072 50 Hz 32 15 65 75 245 312 6 8 22 27 GEH GEV 090 60 Hz GEH GEV 072 50 Hz 32 22 5 68 78 248 316 4 5 23 28 GEH GEV 090 60 Hz GEH GEV 072 50 Hz 45 15 125 144 183 233 15 19 24 30 83 95...

Page 98: ...50 311 396 13 16 22 27 163 187 320 407 12 15 40 50 GEH GEV 120 60 Hz GEH GEV 090 50 Hz 86 30 130 150 296 376 9 11 22 27 174 200 326 415 8 11 41 51 GEH GEV 120 60 Hz GEH GEV 090 50 Hz 95 20 132 152 348 443 13 16 22 27 GEH GEV 120 60 Hz GEH GEV 090 50 Hz 95 30 132 152 333 423 8 11 22 27 GEH GEV 150 60 Hz GEH GEV 120 50 Hz 32 25 66 75 256 326 7 8 23 29 GEH GEV 150 60 Hz GEH GEV 120 50 Hz 32 37 5 69 7...

Page 99: ...0 123 142 308 392 15 19 22 28 133 153 329 419 12 15 35 43 GEH GEV 180 60 Hz GEH GEV 150 50 Hz 77 45 123 141 288 367 10 13 22 28 142 163 334 425 8 10 36 46 GEH GEV 180 60 Hz GEH GEV 150 50 Hz 86 30 124 143 340 432 14 18 21 27 156 179 351 447 13 17 38 48 GEH GEV 180 60 Hz GEH GEV 150 50 Hz 86 45 124 143 321 409 9 12 21 27 167 192 357 455 9 12 40 50 GEH GEV 180 60 Hz GEH GEV 150 50 Hz 95 30 126 145 3...

Page 100: ...50 Hz 68 50 124 142 251 320 14 18 22 27 119 137 330 420 10 13 32 40 GEH GEV 300 60 Hz GEH GEV 240 50 Hz 68 75 123 142 236 301 9 12 22 27 127 146 335 427 7 9 33 42 GEH GEV 300 60 Hz GEH GEV 240 50 Hz 77 50 126 145 289 368 15 18 21 27 133 153 342 435 11 14 34 43 GEH GEV 300 60 Hz GEH GEV 240 50 Hz 77 75 125 144 272 346 10 12 21 27 142 163 348 443 8 10 35 45 GEH GEV 300 60 Hz GEH GEV 240 50 Hz 86 50 ...

Page 101: ... 11 34 43 EXH 009 86 1 7 149 171 336 427 12 15 19 25 195 224 370 471 11 14 36 46 EXH 009 86 2 1 148 171 326 415 9 12 20 25 202 232 375 477 9 12 37 47 EXH 009 95 1 7 149 172 386 491 12 15 19 24 EXH 009 95 2 1 149 172 375 477 9 12 19 24 EXH 012 35 2 2 92 106 288 367 10 13 21 27 EXH 012 35 2 8 95 109 290 370 8 11 21 27 EXH 012 45 2 2 142 163 183 233 12 15 22 28 108 125 304 387 12 15 24 30 EXH 012 45 ...

Page 102: ...492 9 11 37 47 EXH 018 95 3 3 144 166 336 433 12 15 19 24 EXH 018 95 4 2 144 166 326 421 9 12 19 25 EXH 024 35 4 4 84 97 276 348 5 7 21 27 EXH 024 35 5 6 86 99 278 350 4 5 22 28 EXH 024 45 4 4 134 154 164 214 12 15 23 30 99 114 296 372 6 8 25 32 EXH 024 45 5 6 132 152 157 205 9 12 23 30 101 116 298 375 5 6 26 32 EXH 024 55 4 4 134 154 191 249 12 15 22 28 115 132 311 391 7 9 29 36 EXH 024 55 5 6 13...

Page 103: ...5 7 8 86 99 281 353 6 7 22 27 EXH 042 35 9 8 88 101 282 354 4 6 22 28 EXH 042 45 7 8 138 159 161 212 12 15 21 27 101 116 297 372 7 8 25 31 EXH 042 45 9 8 138 159 155 204 10 12 21 27 103 119 299 375 5 7 25 32 EXH 042 55 7 8 139 160 190 249 12 15 21 27 117 135 312 392 8 10 28 35 EXH 042 55 9 8 139 160 183 240 10 12 21 27 120 139 314 395 6 8 29 35 EXH 042 68 7 8 140 161 230 300 12 15 21 26 142 163 34...

Page 104: ...6 12 16 22 28 100 115 322 403 7 8 23 29 EXH 070 45 15 4 132 151 161 209 10 12 22 28 103 118 324 406 5 7 23 30 EXH 070 55 12 3 132 152 195 252 12 15 21 27 117 134 341 427 8 10 26 33 EXH 070 55 15 4 132 152 188 244 10 12 21 27 120 138 343 431 6 8 26 34 EXH 070 68 12 3 134 154 235 304 12 15 21 27 141 162 374 468 9 12 30 39 EXH 070 68 15 4 134 154 228 294 10 12 21 27 145 167 378 473 8 10 31 39 EXH 070...

Page 105: ... 12 15 21 27 126 145 322 410 13 16 26 33 EXV 012 55 2 8 143 164 204 260 9 12 22 27 130 149 325 413 10 13 27 34 EXV 012 68 2 2 144 166 257 327 12 15 21 26 152 174 346 441 14 18 29 37 EXV 012 68 2 8 144 166 248 316 9 12 21 26 157 180 352 448 11 15 29 37 EXV 012 75 2 2 145 167 284 361 12 15 20 26 167 192 361 460 15 19 30 38 EXV 012 75 2 8 145 167 274 349 9 12 20 26 173 199 366 466 12 15 30 39 EXV 012...

Page 106: ...59 234 304 12 15 21 27 141 162 346 433 9 11 33 42 EXV 024 68 5 6 138 159 226 293 9 12 22 28 145 167 350 438 7 9 33 42 EXV 024 75 4 4 139 160 260 336 12 15 21 27 155 179 358 449 10 12 35 44 EXV 024 75 5 6 139 160 251 325 9 12 21 27 161 185 363 454 8 10 35 45 EXV 024 86 4 4 141 162 303 391 12 15 20 26 180 207 380 476 11 14 37 47 EXV 024 86 5 6 141 162 294 379 9 12 20 26 187 215 385 482 9 11 38 48 EX...

Page 107: ...442 7 9 30 38 EXV 042 75 7 8 138 159 255 332 12 15 20 26 154 177 365 456 10 12 32 40 EXV 042 75 9 8 138 159 247 322 9 12 20 26 158 182 369 460 8 10 32 41 EXV 042 86 7 8 140 161 299 389 11 15 19 25 179 205 388 485 11 14 34 43 EXV 042 86 9 8 140 161 291 379 9 12 19 25 184 212 392 490 9 11 34 44 EXV 042 95 7 8 142 163 341 442 11 14 19 24 EXV 042 95 9 8 142 163 332 430 9 11 19 24 EXV 048 35 8 8 87 101...

Page 108: ... 243 10 12 21 27 121 139 340 427 6 8 27 34 EXV 070 68 12 32 133 153 235 303 12 15 20 26 142 164 374 467 9 12 31 39 EXV 070 68 15 4 133 153 228 294 9 12 21 26 146 168 376 470 8 10 31 40 EXV 070 75 12 32 134 154 259 335 12 15 20 26 157 180 389 487 10 13 33 42 EXV 070 75 15 4 134 154 252 325 9 12 20 26 162 186 393 492 8 11 34 43 EXV 070 86 12 32 136 156 297 384 11 15 20 25 181 209 417 523 12 15 37 47...

Page 109: ...9 EXV060 86 14 7 4 EXV070 86 15 4 6 6 Table 55 Cooling water pressure drops WPD in feet of head for GE units 5 6 ton continued Unit Size 60 Hz Unit Size 50 Hz EWT F GPM Ft Pressure Table 57 Heating water pressure drops WPD in feet of head for GE units Unit Size 60 Hz Unit Size 50 Hz EWT F GPM Ft Pressure GEH006 68 1 8 4 2 GEH009 GEH006 68 2 1 3 9 GEH012 GEH009 68 2 8 4 1 GEH015 GEH012 68 3 5 5 7 G...

Page 110: ...49 1 0 028 0 213 GEH035 171 2 0 099 0 741 GEV036 030 70 4 0 041 0 305 042 036 79 0 046 0 342 048 042 71 7 0 041 0 31 060 048 91 8 0 053 0 397 060 91 8 0 053 0 397 072 181 0 105 0 783 090 072 214 0 125 0 927 120 090 390 0 227 1 69 150 180 120 150 508 0 296 2 201 240 180 779 0 453 3 374 300 240 1057 0 615 4 576 Table 60 Water volume for EX units Unit Size 60 Hz Unit Size 50 Hz Water Side Volume in3 ...

Page 111: ...els as well as the following instructions Unless specified otherwise disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing Follow proper lockout tagout procedures to ensure the power can not be inadvertently energized When necessary to work with live electrical components have a qualified licensed electrician or oth...

Page 112: ...e to follow all safety instructions below could result in death or serious injury Coil cleaning agents can be either acidic or highly alkaline and can burn severely if contact with skin occurs Handle chemical carefully and avoid contact with skin ALWAYS wear Personal Protective Equipment PPE including goggles or face shield chemical resistant gloves boots apron or suit as required For personal saf...

Page 113: ... components have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks Table 63 Diagnostic LEDs Color Green Color Red Controller Mode LED1 LED2 LED3 OFF OFF OFF Control OFF ON OFF OFF Normal Compressor OFF ON OFF FLASH Anti short cycle ON OFF ON Normal Compressor ON FLASH ON OFF Brownout Condition ON FLASH ON Soft Locko...

Page 114: ...ease temperature X Inadequate air flow Check clean blower and coil X Dirty filter Clean replace X X Overcharged with refrigerant Decrease charge X X Defective pressure switch Check or replace High head pressure X Trash in heat exchanger Backflush X Low water flow Increase GPM X X Overcharge of refrigerant Decrease charge X X Non condensable in system Evacuate and recharge by weight X X Water too h...

Page 115: ...olation valve wiring Control type 3 wire Honeywell isolation valve connections Blue Brown Black Basic 24V 1TB1 6 1TB1 1 1TB1 4 Deluxe 24V 1TB1 6 1TB1 1 1TB1 4 ZN524 1TB1 18 1TB2 3 1TB1 16 Figure 81 GEH_V 5 to 1 5 tons basic 208V 60 Hz 1 ph a a Wiring diagrams provided in the catalog are generic A unit specific As Built wiring diagram is located on the unit control panel ...

Page 116: ...iagrams 116 WSHP SVX01Q EN Figure 82 GEH_V 5 to 5 tons basic 208V 60 Hz 1 ph a a Wiring diagrams provided in the catalog are generic A unit specific As Built wiring diagram is located on the unit control panel ...

Page 117: ...agrams WSHP SVX01Q EN 117 Figure 83 GEH_V 5 to 1 5 tons basic 208V 60 Hz 3 ph a a Wiring diagrams provided in the catalog are generic A unit specific As Built wiring diagram is located on the unit control panel ...

Page 118: ...grams 118 WSHP SVX01Q EN Figure 84 GEH_V 5 to 5 tons basic 24V 460V 60 Hz 3 ph a a Wiring diagrams provided in the catalog are generic A unit specific As Built wiring diagram is located on the unit control panel ...

Page 119: ...l panel 1U1 1U2 CONNECTION FOR 24VAC CLASS 2 COMPRESSOR DISABLE VERIFY TEST JUMPER HAS BEEN REMOVED TO PREVENT INPUT TERMINAL 1TB2 7 AND 1TB2 8 CONTROL TIMING ERRORS CONTACTS RATED FOR CLASS 2 24V TERMINAL 1TB2 9 AND 10 ISOLATED GENERAL ALARM CONTACTS CONTACTS CLOSE WHEN CONTROL 1U1 AND 1U2 GOES INTO MANUAL LOCKOUT MODE CONNECT TERMINAL 11 TO 1TB2 1 2 AND TERMINAL 10 TO 1TB2 3 4 IF USING ZONE SENS...

Page 120: ...agrams 120 WSHP SVX01Q EN Figure 86 GEH_V 6 25 tons deluxe 24V 460V 60 Hz 3 ph a a Wiring diagrams provided in the catalog are generic A unit specific As Built wiring diagram is located on the unit control panel ...

Page 121: ...HP SVX01Q EN 121 Figure 87 EXH EXV deluxe 24V 460V 60 Hz 3 ph a ECM motor wiring diagram a Wiring diagrams provided in the catalog are generic A unit specific As Built wiring diagram is located on the unit control panel ...

Page 122: ...ams 122 WSHP SVX01Q EN Figure 88 GEH_V 6 to 25 tons Tracer ZN524 460V 60 Hz 3 ph a a Wiring diagrams provided in the catalog are generic A unit specific As Built wiring diagram is located on the unit control panel ...

Page 123: ...HP SVX01Q EN 123 Figure 89 EXH_V Tracer ZN524 460V 60 Hz 3 ph a ECM motor wiring diagram a Wiring diagrams provided in the catalog are generic A unit specific As Built wiring diagram is located on the unit control panel ...

Page 124: ...iring Diagrams 124 WSHP SVX01Q EN Figure 90 GEH_V 5 to 1 5 tons UC400 a a Wiring diagrams provided in the catalog are generic A unit specific As Built wiring diagram is located on the unit control panel ...

Page 125: ...Wiring Diagrams WSHP SVX01Q EN 125 Figure 91 GEH_V 2 to 5 tons UC400 a a Wiring diagrams provided in the catalog are generic A unit specific As Built wiring diagram is located on the unit control panel ...

Page 126: ...Wiring Diagrams 126 WSHP SVX01Q EN Figure 92 GEH_V 6 to 25 tons UC400 a a Wiring diagrams provided in the catalog are generic A unit specific As Built wiring diagram is located on the unit control panel ...

Page 127: ...t to exceed 18 months from shipment Extended Warranty The optional extended warranty is a second through fifth year warranty The time starts at the end of the standard 1 year coverage through the fifth year These extended warranties apply only to new equipment installed in domesticTrane Commercial Systems Group sales territories and must be ordered prior to start up ...

Page 128: ... increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results For more information visit www ingersollrand com Ingersoll Rand has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice We are committed to using environmentally conscious print ...

Reviews: