background image

WARNING

Explosion Hazard!

Failure to properly regulate pressure could result in a
violent explosion, which could result in death, serious
injury, or equipment or property-only-damage.

When using dry nitrogen cylinders for pressurizing units
for leak testing, always provide a pressure regulator on
the cylinder to prevent excessively high unit pressures.
Never pressurize unit above the maximum
recommended unit test pressure as specified in
applicable unit literature.

Removal and Installation

18

COM-SVN01D-EN

Pressure Testing

Use industry-standard and EPA-accepted techniques
for testing.

Pressure tests must be performed by qualified
personnel.

Use tools especially designed for leak testing.

Do not exceed the high-side and low-side pressures
listed on the unit nameplate.

If no test pressure value is listed on the nameplate of
the unit, a pressure of no more than 150 psig is
acceptable.

The CSHN compressor has an internal check valve.
When pressurizing the system, it is important to never
allow the low side pressure to exceed the high side
pressure by more than 5 bar (72 psig). Greater
pressure differential could result in compressor
damage. Also slowly raise the pressure over a
2-minute time period to allow sufficient time for
internal pressures in the compressor to equalize.

NOTICE

Overpressure Damage!

Do not pressurize the low side of the compressor by
more than 5 bar (72 psig) higher than the high side of
the compressor within less than two minutes. Failure to
follow these instructions could result in compressor
damage.

Pressure decay testing can be used to check for gross
leaks but will not be able to detect the location of a leak.

After pressurizing the system use an R-410A leak
detection device to detect and locate leaks.

Vacuum Testing and Evacuation

Use the procedure as described in the unit Installation,
Operation, and Maintenance manual (see

“Literature

Referenced,” p. 6

).

If no other information is available, use the following
information.

NOTICE

Compressor Motor Damage!

Never use the compressor as a vacuum pump. Never
meg-ohm test or apply power to the compressor while
it is in a vacuum. Failure to follow these instructions
could cause compressor motor damage.

WARNING

Hazardous Voltage w/Capacitors!

Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/tag
out procedures to ensure the power cannot be
inadvertently energized. Verify with an appropriate
voltmeter that all capacitors have discharged. Failure to
disconnect power and discharge capacitors before
servicing could result in death or serious injury.

Ensure that there is no voltage being applied to the
compressor terminals.

Evacuate the unit to 500 microns.

Hold vacuum for 30 minutes.

Rapid pressure rise indicates a leak; locate and repair
the leak.

Slow pressure rise indicates one of two possibilities:

A small leak, indicated by a continuous rise in
pressure.

Moisture in the system, indicated by a slow rise in
pressure and leveling-out at a pressure equivalent
to the moisture level. If this occurs, break the
vacuum with dry nitrogen and repeat evacuation
process to 500 micron.

Once system is leak-tight, connect compressor repeat
the vacuum procedure, break vacuum with dry
nitrogen and evacuate to 500 microns. The vacuum
should be able to be maintained for four hours. Isolate
the vacuum pump so that the vacuum gauge only
reads the system pressure.

Vacuum must be measured in the refrigeration system
and not at the vacuum pump.

Summary of Contents for CSHD

Page 1: ...on starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by a...

Page 2: ...nt that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the...

Page 3: ...gases and extremely corrosive acids WARNING Explosion Hazard Failure to follow these instructions could result in death or serious injury or equipment or property only damage Use only dry nitrogen wit...

Page 4: ...ed in this document are the trademarks of their respective owners Revision History Updated Model Number Descriptions chapter Updated Torque values table in General Information chapter Updated Oil chan...

Page 5: ...Inspections 10 Repair Recommendations 11 Mechanical Failure 11 Electrical Failure 12 Two Types of Motor Failures 12 Removal and Installation 13 Removal 13 Compressor Replacement Tandem and Trio Compr...

Page 6: ...tenance IOM manuals The following table lists these IOMs by unit type Unit Type IOM a a Installation Operation and Maintenance IOM manuals listed here are current as of Februaryl 2015 Check e Library...

Page 7: ...76 176 MBtu h CSHN 184 184 MBtu h CSHN1 240 240 MBtu h CSHN 250 250 MBtu h CSHN1 315 315 MBtu h CSHN 374 374 MBtu h CSHN CSHL Digit 8 Voltage J 200 230 60 3 K 460 60 3 380 415 50 3 D 575 60 3 X 380 60...

Page 8: ...it absorbs moistureveryreadily Therefore itisimportanttoproperly handle the oil POE Oil handling guidelines Always use the smallest container size required for the job requirements Always leave the o...

Page 9: ...transported in the upside position droppedortippedovercouldresultininternaldamageto the compressor and it is recommended that the compressor not be put into service Damage to compressor or packaging...

Page 10: ...part number Compressor is the correct voltage Compressor ship with items Restrictors for use with tandem and trio compressors Oil equalizer Teflon gaskets WARNING R 410A Refrigerant under Higher Press...

Page 11: ...em or trio assemblies the suction and discharge lines must NOT be modified except for the use of slip joint couplings Other modification may cause oil return issues and lead to compressor failure Cut...

Page 12: ...as a mechanical failure Severe If oil test kit is positive with strong pungent odor and dark oil drain and replace oil in all of the non failed compressors Reuse the compressor mounting isolators or...

Page 13: ...service technician to perform a safe and successful compressor replacement Removal WARNING Pressurized Burning Fluid Failure to follow these instructions could result in death or serious injury Befor...

Page 14: ...ndem or trio set 1 Only replace the failed compressor 2 On tandem or trio assemblies the suction and discharge lines must not be modified except for the use of slip joint couplings Other modifications...

Page 15: ...m due to POE oil Remove the rubber plugs only when ready to install the compressor Plug other compressor on tandem or trio compressors Before removing the oil equalizer connection cap place a can pan...

Page 16: ...osive and could lead to long term problems and equipment damage if not properly removed Tandem two compressors and trio combinations three compressors with uneven compressor combinations requires the...

Page 17: ...g diagram Ensure that the compressor model terminals are installed on the correct terminals see Figure 12 Proper torque for the terminal screws is 25 in lb Before starting the compressor check the ele...

Page 18: ...pressurizing the system use an R 410A leak detection device to detect and locate leaks Vacuum Testing and Evacuation Use the procedure as described in the unit Installation Operation and Maintenance...

Page 19: ...tion and discharge service valves close them during the charging procedure Water chiller units Always operate the chilled water pumps while charging the unit to prevent freezing the evaporator Verific...

Page 20: ...operating Do not overcharge the unit Recommended system full load superheats unless specified differently in the unit Installation Operation andMaintenancemanual see LiteratureReferenced p 6 is 16 F 2...

Page 21: ...mpressor superheat subcooling oil sump superheat voltage and amperage Check all of the following on a regular basis System operating conditions System refrigerant charge level Oil levels and oil color...

Page 22: ...g valve may be stuck and not switched properly bypassing from the high side to the low side of the system this situation is indicated by an extremely warm suction inlet to the compressor Model CSHN374...

Page 23: ...lywiredintothesystem safety circuit If the motor is believed to be incorrectly phased change two of the three wires PTC Overheat motor over temperature over current Compressor motor drawing too much c...

Page 24: ...PTC open replace compressor Resistance 0 ohms PTC shorted replace compressor Resistance 2750 ohm Wait until the motor has cooled down and resistance is less than 2750 ohms reconnect and try to reset...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Reviews: