14

Test Pins

J1

To Coil on 

EEV

J6

OPEN

CLOSE

TEST

J7

OPEN
CLOSE
TEST

STATUS LED 
(Green)

Fault LED 
(Red)

See Table 8

Suction Line 
Pressure 
Transducer Input

J10

See Table 7

Suction Line
Temperature
Sensor Input

See Table 6

Control Input 

24 VAC Stage/Mode

DC V TEST 

POINT

eeV CONTROL BOARd TeST POINTS

note:  Must be running in Heat Mode (Y1 or Y2 input, no O input, power input R & B)

Test Pins:   OPEN, CLOSE, TEST  (See EEV Board drawing for locations)

Close Valve test

 - Touch CLOSE pin to TEST pin.  

 

EEV drives closed (5 seconds max) and stays closed for 2 minutes.

 

 

1) Status LED will be flashing.

 

 

2) Gauges should indicate suction pressure dropping.  

• Valve is working.  
• LPCO may trip.

Note

:  If jumper is left on pins, any faults stored in memory will be cleared after 10 seconds.  The CLOSE VALVE TEST 

will clear after 2 minutes and will not reinitiate (requires a break and make to reinitialize).

Open Valve test

 - Touch OPEN pin to TEST pin.  

 

EEV drives open (5 sec max) and stays open for 30 seconds.

 

 

1) Status LED will be flashing.

 

 

2) Temperature probe should indicate superheat falling. 

• Valve is working. 

Note

:  If jumper is left on pins, the OPEN VALVE TEST will be cleared after 30 seconds and will not reinitiate (requires a 

break and make to reinitialize).

exit test Mode

 -   The Open Valve Test or Closed Valve Test can be cancelled by jumping to the opposite mode Test pin.  

The system will return to normal super heat control.  

Test mode will cancel if:

1) Unit enters Defrost
2) Stage-Delay occurs
3) Y1 or Y2 input(s) are lost

Summary of Contents for ComfortLink 4TWZ0060A1000A

Page 1: ...ON WITH ITS USE CAuTION RECONNECT ALL GROUNDING DEVICES ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING ELECTRICAL CURRENT ARE GROUNDED IF GROUNDING WIRES SCREWS STRAPS CLIPS NUTS OR WASHERS USED TO C...

Page 2: ...ms CHARGING METHOD This model has ComfortLink II and Charge Assist features Charge Assist can be used in cooling mode only For complete instructions on using Charge Assist please see page 4 2 Schemati...

Page 3: ...ambient temperatures 2 When charging for ambient temperatures above 120 F charge to 10 subcooling It is important to return when outdoor ambient temperature is between 55 F and 120 F to verify system...

Page 4: ...ash slowly Liquid Line Temperature Must be within range If this sensor is shorted or open This error condition causes an 11 flash on FAULT LED Liquid Line Pressure Must be above 90 psig If the liquid...

Page 5: ...n LED will be turned ON The CA control will then exit the charge assist cycle and return the control of the system to the Communicating Comfort Control The Status Green LED will be slowly flashing The...

Page 6: ...TM data Low Pressure Cut Out Fault Open outside of defrost Cycle Short lock out Wait Flashing Flash device count when in communication number of COMM products connected in system Rapid flashes followe...

Page 7: ...sist Tool BAYCAKT001AA ADD AMBER LED BLINKING CHARGING STABILIZING AMBER LED BLINKING RECOVER RED LED CA procedure allows 1 hour to get within 20 psi of Charged and 50 minutes to move 4 psi Otherwise...

Page 8: ...Z0060A1000AA 200 250 300 350 400 450 500 550 40 60 80 100 120 115 125 135 145 155 165 175 185 40 60 80 100 120 115 125 135 145 155 165 175 185 40 60 80 100 120 40 50 60 70 80 90 100 110 120 130 140 15...

Page 9: ...Heating Refrigeration Cycle Cooling Refrigeration Cycle Printed from D155711P01 Rev02 9 ReFRIGERATION CIRCUITS...

Page 10: ...er up 10 hours max if compressors remain OFF Sump Heat OFF When a compressor is running Sump Heat OFF For 30 minutes after compressor s have stopped running Sump Heat OFF When outdoor temperature goes...

Page 11: ...Sensors J6 J7 TABLE 3 Temp F Temp C THERMISTOR RESISTANCE OHMS Volts DC at plug J8 Only pin to pin 50 10 0 19405 2 22 55 12 8 17002 2 06 60 15 6 14930 1 90 65 18 3 13138 1 75 70 21 1 11586 1 61 75 23...

Page 12: ...ng 3 9 Flash Low superheat in Cooling Mode Indoor TXV stuck open or ID Fan failure 10 Flash Not used at this time 3 Monitor superheat and pressure 3 SH for 5 minutes with valve minimum position Monito...

Page 13: ...n Service Facts EEV Hunting Suction pressure moves up down Sensor are out of calibration 1 Verify sensors are accurate See Table 7 8 in Service Facts Verify temperature sensor is clipped tight to suct...

Page 14: ...ing LPCO may trip Note If jumper is left on pins any faults stored in memory will be cleared after 10 seconds The CLOSE VALVE TEST will clear after 2 minutes and will not reinitiate requires a break a...

Page 15: ...65 0 66 125 51 7 3298 0 60 130 54 4 2972 0 54 135 57 2 2683 0 50 136 57 8 2629 0 49 137 58 3 2576 0 48 138 58 9 2525 0 47 139 59 4 2474 0 46 140 60 0 2425 0 45 141 60 6 2377 0 45 142 61 1 2330 0 44 14...

Page 16: ...Trane www trane com Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice...

Reviews: