18
CVHE-SVN04M-EN
Weights
Single Compressor and Duplex Chillers: Models CVHE, CVHF, CVHG CDHF, and CDHG
Table 9. Compressor and motor weights
Model
NTON
CPKW
(a)
Volts
Hz
Motor Weight
Compressor and Motor
Weight
lb
kg
lb
kg
CVHE
190–270
242
6600
50
2558
1160
7294
3308
230–320
287
4160
60
2530
1147
7266
3295
300–420
379
6600
50
2767
1255
8185
3712
360–500
453
6600
60
3385
1535
8803
3992
CVHF
350–485
453
6600
60
3385
1535
8013
3634
350–570
588
480
60
2803
1271
7431
3370
620–870
957
2300
60
3862
1751
9900
4490
650–910
957
2300
60
3862
1751
9900
4490
1060–1280
1228
4160
60
4559
2067
10597
4806
1070–1300
1228
4160
60
4559
2067
10714
4859
1470–1720
1340
2400
60
5196
2356
13932
6319
CVHG
480–565
489
6600
50
3794
1720
10000
4535
670–780
621
6600
50
4685
2125
11311
5130
920–1067
621
6600
50
4685
2125
12151
5511
CDHF
(b)
1500–2000
745
460
60
3460
1569
9498
4308
2100–2500
1062
460
60
4296
1948
10334
4687
3500
1340
2400
60
5196
2356
13911
6309
CDHG
1250–1750
621
6600
50
4685
2125
11311
5130
2150
621
6600
50
4685
2125
12151
5511
Note:
All weights are nominal and ±10%.
(a)
Heaviest motor used; does not include the weight of the suction elbow.
(b)
For Duplex
™
chillers, weights shown are for individual components; multiply by two for total component weights (for Duplex chillers only).
Table 10.
Component weights
Model
Evap Shell Size
Control Panel
Purge
Oil Tank
Suction Elbow
(a)
Economizer
without Free
Cooling
Economizer
with Free
Cooling
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
CVHE
032
119
54
140
64
350
159
279
127
404
183
564
256
CVHE
CVHG
050
119
54
140
64
350
159
280
127
635
288
885
401
080
119
54
140
64
350
159
519
235
976
443
1296
588
CVHF
050
119
54
140
64
350
159
280
127
420
191
670
304
080
119
54
140
64
350
159
519
135
735
333
1055
479
142/210/250
119
54
140
64
350
159
722
327
878
398
1348
611
CVHG
142/210
119
54
140
64
350
159
722
327
1433
650
1903
863
CDHF
(b)
210/250D/250M/250X
119
54
140
64
350
159
683
310
878
398
1348
611
CDHG
210/250
119
54
140
64
350
159
1350
612
1433
650
1903
863
Note:
All weights are nominal and ±10%.
(a)
Suction elbow weights include flanges and assume largest compressor available for that size.
(b)
For Duplex chillers, weights shown are for individual components; multiply by two for total component weights (for Duplex chillers only)