CVHE-SVN04M-EN
19
Table 11.
Evaporator and condenser bundle weights
Model
Shell Size
Bundle
Size
(a)
Evaporator
Condenser
Shell
(b)
Waterbox
(c)
Shell
(d)
lb
kg
lb
kg
lb
kg
lb
kg
CVHE
032S
320
2778
1260
653
296
2458
1115
644
292
032L
320
3483
1579
653
296
3006
1363
644
292
CVHE
CVHF
CVHG
050S
700
4897
2221
1061
481
3526
(e)
1599
1328
602
050L
700
5984
2714
1061
481
2012
1328
602
080S
1400
7884
3283
2490
1129
5280
2394
2565
1164
080L
1400
9653
4066
2490
1129
6776
3073
2565
1164
142M
1420
11036
5005
3701
1679
N/A
N/A
5330
2418
142L
1420
11938
5414
3701
1679
10995
4987
5330
2418
142E
1420
12921
5860
3701
1679
N/A
N/A
5330
2418
210L
2100
14755
6692
6403
2904
14154
6420
7319
3320
250
2500
20068
9102
8343
3784
17200
7801
9144
4148
CDHF
CDHG
210D
2100
22437
10177
8382
(f)
3802
22635
10267
4050
250D
2500
24610
11162
10954
4969
25853
11726
11442
(g)
5190
250M
2500
28679
13008
10954
4969
29817
13524
5190
250X
2500
31902
14470
10954
4969
33486
15188
5190
Note:
All weights are nominal and ±10%.
(a)
Bundle weights are for the maximum bundle size for chiller family with TECU.035 tubes.
(b)
Evaporator shell weight includes: Evap Control Panel + Legs; waterbox weight is NOT included.
(c)
Based on two-pass marine, 300 lb (136 kg); includes supply and return.
(d)
Condenser shell weight includes: Con Oil Tank + Purge + Legs; waterbox weight is NOT included.
(e)
Condenser bundle is a 500.
(f)
Based on 1-pass marine, 300 lb (136 kg); includes supply and return.
Table 12.
Unit-mounted starters/Adaptive Frequency
™
™
drives
lb
kg
Low Voltage (less than 600 volts)
Wye Delta
557
252
Solid State
557
252
Adaptive Frequency Drive (less than 600 volts)
405 amp
1680
762
608 amp
1680
762
900 amp
3000
1360
1210 amp
3000
1360
Medium Voltage (2300–6600 volts)
Across the line
557
252
Primary Reactor
1586
719
Autotransformer
1639
743
Note:
All weights are nominal and ±10%.