Figure 103:
Notes concerning plate heat exchangers
-
pH-value: should be kept as high as possible; but at least 7,5
-
Cl2:
continuous
< 0,5 ppm near the plate heat exchanger inlet
maximum
< 2 ppm
-
Cl-
< 150 ppm, if the water is heated to
50-60°C
< 100 ppm, if the water is heated to
70-80°C
6.2 Connection of indirect adiabatic cooling
ETA-PAC-
AHU’s are equipped with an indirect adiabatic cooling device. Carry out connection to
Figure 104:
Indirect adiabatic cooling
6.3 Condensate drain
Each drain must be equipped with a siphon. Siphons are available as accessories from TRANE.
6.3.1 Standard siphons