Three-Way, Two-Position Control Valves

Normally open three-way, two-position
valves are rated for a maximum 25 psig
(207 kPa) pressure differential across the
valve. Normally closed three-way two-
position valves are rated for a maximum
15 psig (103 kPa) pressure differential
across the valve. All 3-way valve piping
packages include a bypass line  with a
balance fitting to set flow through the
bypass line. The balance fitting has a
maximum working pressure of 150 psig
(1,034 kPa). The valves are also available
with a maximum close-off pressure of 50
psig (345 kPa). The valve actuator is easily
removable for service without removing
the valve body from piping.

Modulating Control Valves

Two-way and three-way modulating
valves are rated for a maximum 50 psig
(345 kPa) pressure differential across the
valve. Modulating valves are available in
Cv values of 0.7, 1.5, 2.5 and 4.0.

All two-position and modulating control
valves have a maximum working
pressure of 300 psig (2,069 kPa). The
maximum entering water temperature of
the valve is 200 F (93 C).

Electric Heat Coil

Electric heating coils are available as the
total source of heating on all Force-Flo™
cabinet heaters except inverted models.
The electric heat coils are Nichrome
elements with an open-wire design.
Single stage coils are available on all
units and two-stage coils are available on
units with a Tracer ZN.520 controller.  The
electric heat operates at the same voltage
as the unit. Therefore, only a single-point
power connection is necessary.

All standard electric heat coils are UL
listed and interlocked with the fan motor

switch. Therefore, electric heat operation
is possible only when the fan is running. A
transformer is supplied to eliminate the
need for field installation of a step-down
transformer. A unit-mounted magnetic
contactor is supplied on all voltages. A
high temperature cutout with automatic
reset is provided as an integral part of the
elements to de-energize the electric heat
in the event of an overheat condition.

Filters

Filters are concealed from sight and
easily removable. Filters are located
behind an integral access door on
horizontal type units. Filters are either 1”
(25 mm) throwaway or 1”(25 mm)
pleated media throwaway. Pleated media
filters are Farr 30/30.

Fresh Air Damper

A fresh air opening with damper is a
factory-installed option. Dampers are
constructed of 18-gauge steel. Fresh air is
sealed off with gasket material when the
damper is set in the closed position.
Return and fresh air mixes when the
damper is open.

Manual Damper

The manual damper is field-adjustable to
allow zero to 100 percent fresh air. The
automatic two-position damper is
accompanied by a factory-installed and
wired two-position (spring-return)
actuator.

Auto Two-Position Damper

The auto two-position damper is factory
set at 25 percent when open. The damper
can be set in the field to allow from zero
to 50 percent fresh air.

Summary of Contents for CAB-PRC001-EN

Page 1: ...Air Terminal Devices Horizontal and Vertical Sizes 02 12 Force Flo CabinetHeater CAB PRC001 EN December 2000...

Page 2: ...ion and maintenance high quality and durability advanced controls Cleanable closed cell insulation non fiberglass Two three or four row coils Easy filter access without front panel removal Smaller uni...

Page 3: ...Features and Benefits 4 Selection Procedure 5 Model Number Description 5 General Data 7 Performance Data 18 Hot Water Coils 19 Steam Coils 22 Controls 24 Electrical Data 30 Dimensions and Weights 34...

Page 4: ...unit operation using Tracer Summit building management system with ZN 510 or ZN 520 To customize unit control Tracer Summit or Rover software will allow field modification of ZN 510 and ZN 520 default...

Page 5: ...package RH Extended End Pocket M With piping package LH Extended End Pocket Digits 10 11 Design Sequence M0 Digit 12 Inlets A Front Toe Space B Front Bar Grille C Front Stamped Louver D Bottom Stampe...

Page 6: ...t Mounted Fan Speed Switch K Wall Mounted Fan Speed Switch V Unit Mounted Fan Speed Switch w Setpoint Dial W Wall Mounted Fan Speed Switch w Setpoint Dial X Unit Mounted Fan Speed Switch w Wall Mounte...

Page 7: ...nlet Front Toe Space Fresh Air Bottom or Back Outlet Top Duct Collar Inlet Front Toe Space Front Bar Grille Fresh Air Bottom or Back Outlet Top Quad Grille Top Bar Grille Unit Configurations Inlet Fro...

Page 8: ...orizontal Concealed Unit Configurations Inlet Back Duct Collar Outlet Front Duct Collar Fresh Air N A Fresh Air N A Outlet Front Duct Collar Inlet Open Return No Filter Inlet Bottom Toe Space Fresh Ai...

Page 9: ...t Back Stamped Louver Outlet Front Quad Grille Front Bar Grille Fresh Air N A Outlet Front Quad Grille Front Bar Grille Fresh Air N A Inlet Back Duct Collar Outlet Bottom Stamped Louver Inlet Bottom S...

Page 10: ...ll Hung Cabinet Inlet Back Duct Collar Fresh Air Top or Back Inlet Bottom Stamped Louver Outlet Front Duct Collar Inlet Back Duct Collar Fresh Air N A Outlet Bottom Stamped Louver Outlet Bottom Stampe...

Page 11: ...ce Front Bar Grille Fresh Air Bottom or Back Outlet Top Quad Grille Top Bar Grille Unit Configurations Model H Vertical Recessed Inlet Front Stamped Louver Outlet Front Stamped Louver Fresh Air Bottom...

Page 12: ...12 Outlet Front Stamped Louver Model M Inverted Vertical Cabinet Inlet Front Stamped Louver Outlet Front Stamped Louver Model N Inverted Vertical Recessed Inlet Top Duct Collar Outlet Top Duct Collar...

Page 13: ...16x19 16x19 16x19 2 6 31x6 5 16x6 5 Motor Quantity 1 1 1 1 1 2 2 Filter Data 1 cm TA and Pl Media Quantity 1 1 1 1 1 1 1 Size In cm 87 8 x 191 8 87 8 x 191 8 87 8 x 241 8 87 8 x 335 8 87 8 x 421 8 87...

Page 14: ...f the Tracer ZN control options Two stage electric heat is controlled by the Tracer ZN 520 only Both control options use PWM pulse width modulation outputs to calculate the electric heat output based...

Page 15: ...ow control valve acts as both a flow setting device and a stop valve This valve allows water flow through the cabinet heater to be set quickly and accurately The manual circuit setter includes Schrade...

Page 16: ...General Data CAB PRC001 EN 16 Piping Packages Piping Package Options Automatic Circuit Setter C Manual...

Page 17: ...rge motor For other applications use TOPSS to determine the flowrate and make calculations using the formulas above Table GD 3 Modulating Valve Selections for Horizontal Concealed Units High Static Mo...

Page 18: ...d C Bottom Toe Space Front Duct Collar Horizontal Cabinet D Back Duct Collar Bottom Stamped Louver Bottom Stamped Louver Front Quad Grille Front Bar Grille Front Duct Collar Bottom Stamped Louver Back...

Page 19: ...minute 2 TMBH Total capacity MBH 3 GPM Gallons per minute 4 WPD Water pressure drop feet of water 5 Q ITD MBH kW Entering water temperature Entering air temperature when DT and GPM L s remain constan...

Page 20: ...3H 508 240 43 3 12 7 0 39 2 88 0 18 3 3 9 7 125 130 124 4H 483 228 47 2 13 8 0 43 3 14 0 20 4 4 13 3 125 130 124 8 2H 665 314 45 0 13 2 0 41 3 00 0 19 3 2 9 4 135 150 159 3H 623 294 54 3 15 9 0 49 3 6...

Page 21: ...s per minute 4 WPD Water pressure drop feet of water 5 Q ITD MBH kW Entering water temperature Entering air temperature when DT and GPM L s remain constant To determine heating capacities at a differe...

Page 22: ...07 10 1 3 0 0 07 60 95 65 3 Steam 277 130 12 5 3 7 0 08 13 3 3 9 0 08 70 80 83 4 Steam 346 163 16 6 4 9 0 11 17 6 5 1 0 11 95 96 104 6 Steam 538 254 25 1 7 4 0 17 26 6 7 8 0 17 110 154 165 8 Steam 702...

Page 23: ...sig Unit CFM TMBH TMBH 115V 230V 277V Size Coil L s TkW Q ITD TkW Q ITD Watt Watt Watt 2 Steam 251 119 10 4 3 0 0 07 11 0 3 2 0 07 145 145 145 3 Steam 326 154 13 4 3 9 0 09 14 2 4 2 0 09 140 140 140 4...

Page 24: ...troller Tracer ZN 510 Model Number Digit 30 F ZN 510 can be used as either a stand alone or communicating microprocessor controller Tracer ZN 520 Model Number Digit 30 G The ZN 520 controller can be u...

Page 25: ...user defined speed when the fan speed switch is in the auto position Low Medium High Continuous Fan Fan operates continuously while control valve option cycles to maintain setpoint temperature Fresh...

Page 26: ...cupancy Generic Input Analog Inputs Zone Temperature Setpoint Fan Mode Auto High Medium Low Entering Water Discharge Air Outside Air Generic Note The generic input and output are for use with a Tracer...

Page 27: ...hermistor Zone sensors operate on 24 VAC ZN 010 ZN 510 and ZN 520 Unit mounted zone sensor Digit 30 E and Digit 31 V Wall mounted zone sensor Digit 30 E and Digit 31 W Split mounted zone sensor unit m...

Page 28: ...simulta neous heating The ZN 510 or ZN 520 controller can share information between units on the same communication link using a twisted pair wire in the field Unit Features configuration must be modi...

Page 29: ...are three wire floating point valves equal percentage type Modulating valves are available in four Cv sizes 0 7 1 5 2 5 and 4 0 The valve responds to a 24V triac signal from the controller which deter...

Page 30: ...ard fuse sizes are 15 20 25 30 35 40 45 50 60 amps Electric heat MBH heater kW 3 413 Units Without Electric Heat To compute MCA and MFS see Tables ED 2 through ED 5 on page 31 for motor FLAs and Table...

Page 31: ...12 1 6 3 4 10 07 24 18 0 5 0 9 10 07 24 18 0 7 1 1 10 12 24 18 1475 1315 1240 1475 1285 975 Table ED 4 Free Discharge Motors on Units with Three and Four Row Coils 115Volt 208 230 Volt 277 480Volt RP...

Page 32: ...5 7 5 18 1 480 3 4 2 5 7 5 9 1 208 1 2 3 4 7 9 38 0 240 1 2 4 5 10 5 43 8 06 277 60 1 2 4 5 10 5 38 0 208 3 3 3 4 7 9 21 9 240 3 3 4 5 10 5 25 3 480 3 4 4 5 10 5 12 7 208 1 2 4 5 10 1 48 8 240 1 2 6 0...

Page 33: ...0 12 5 4 5 18 8 7 5 31 3 277 60 1 2 3 0 10 9 4 5 16 3 7 5 27 1 208 60 3 3 2 25 6 3 3 3 9 2 5 7 15 9 240 60 3 3 3 0 7 3 4 5 10 9 7 5 18 1 480 60 3 4 3 0 3 7 4 5 5 5 7 5 9 1 12 208 60 1 2 2 25 10 9 3 3...

Page 34: ...04 125 57 109 49 88 40 06 155 70 139 63 128 58 08 164 74 147 67 139 63 10 218 99 200 91 253 115 12 218 99 200 91 253 115 Table DW 2 Shipping Weights lbs kg Unit Cabinet Concealed Recessed Size Models...

Page 35: ...13 16 3 8 5 16 5 3 5 16 C 1 10 13 16 2 3 13 16 3 1 5 16 3 9 13 16 5 4 13 16 D 1 5 5 16 1 10 5 16 2 7 13 16 3 4 5 16 4 11 5 16 E 1 7 5 16 2 0 5 16 2 9 13 16 3 6 5 16 5 1 5 16 NOTE 1 Coil connections a...

Page 36: ...13 16 3 8 5 16 5 3 5 16 C 7 5 8 7 1 8 8 7 8 7 1 8 7 5 8 D 1 6 2 0 2 6 3 6 5 0 E 1 7 5 16 2 0 5 16 2 9 13 16 3 6 5 16 5 1 5 16 F 3 5 5 16 3 10 5 16 4 7 3 16 5 4 5 16 6 11 5 16 NOTE 1 Coil connections...

Page 37: ...16 5 3 5 16 C 1 10 13 16 2 3 13 16 3 1 5 16 3 9 13 16 5 4 13 16 D 1 7 3 8 2 0 3 8 2 9 7 8 3 6 3 8 5 1 3 8 E 1 6 1 8 1 11 1 8 2 8 5 8 3 5 1 8 5 0 1 8 F 1 7 5 16 2 0 5 16 2 9 13 16 3 6 5 16 5 1 5 16 NO...

Page 38: ...1 8 7 5 8 D 1 6 2 0 2 6 3 6 5 0 E 1 5 1 4 1 10 1 4 2 7 3 4 3 4 1 4 4 11 1 4 F 3 5 5 16 3 10 5 16 4 7 3 16 5 4 5 16 6 11 5 16 G 8 5 8 8 1 8 9 1 8 8 1 8 8 5 8 H 1 4 1 10 2 4 3 4 4 10 J 1 7 3 4 1 11 3 4...

Page 39: ...9 13 16 5 4 13 16 D 1 7 3 8 2 0 3 8 2 9 7 8 3 6 3 8 5 1 3 8 E 1 6 1 8 1 11 1 8 2 8 5 8 3 5 1 8 5 0 1 8 F 2 8 7 16 3 1 7 16 3 10 15 16 4 7 7 16 6 2 7 16 G 2 10 5 16 3 3 5 16 4 0 13 16 4 9 5 16 6 4 5 1...

Page 40: ...2 2 5 16 2 11 13 16 3 8 5 16 5 3 5 16 C 7 5 8 7 1 8 8 7 8 7 1 8 7 5 8 D 1 6 2 0 2 6 3 6 5 0 E 1 7 5 16 2 0 5 16 2 9 13 16 3 6 5 16 5 1 5 16 F 1 7 3 4 1 11 3 4 2 7 3 4 3 3 3 4 4 11 3 4 NOTE 1 Coil conn...

Page 41: ...3 9 13 16 5 4 13 16 D 1 5 5 16 1 10 5 16 2 7 13 16 3 4 5 16 4 11 5 16 E 3 11 4 3 5 3 5 5 1 2 7 5 1 2 F 2 6 2 6 2 6 2 9 1 2 2 9 1 2 G 2 3 8 2 3 8 2 3 8 4 1 8 4 1 8 H 3 6 4 0 4 9 5 3 7 3 J 2 2 1 2 2 2...

Page 42: ...11 13 16 3 8 5 16 5 3 5 16 C 7 5 8 7 1 8 8 7 8 7 1 8 7 5 8 D 1 6 2 0 2 6 3 6 5 0 E 1 7 5 16 2 0 5 16 2 9 13 16 3 6 5 16 5 1 5 16 F 3 5 5 16 3 10 5 16 4 7 13 16 5 4 5 16 6 11 5 16 NOTE 1 Coil connectio...

Page 43: ...13 16 3 8 5 16 5 3 5 16 C 7 5 8 7 1 8 8 7 8 7 1 8 7 5 8 D 1 6 2 0 2 6 3 6 5 0 E 1 7 2 0 2 9 1 2 3 6 5 1 F 1 7 3 4 1 11 3 4 2 7 3 4 3 3 3 4 4 11 3 4 G 8 5 8 8 1 8 9 7 8 8 1 8 8 5 8 H 1 4 1 10 2 4 3 4 4...

Page 44: ...3 5 16 C 1 10 13 16 2 3 13 16 3 1 5 16 3 9 13 16 5 4 13 16 D 2 3 8 2 3 8 2 3 8 4 1 8 4 1 8 E 3 11 4 3 5 3 5 5 1 2 7 5 1 2 F 2 6 2 6 2 6 2 9 1 2 2 9 1 2 G 2 2 1 2 2 2 1 2 2 2 1 2 2 3 1 2 2 3 1 2 H 3 6...

Page 45: ...Dimensions and Weights CAB PRC001 EN 45 Coil Connections Coil Connections Vertical Units Coil Connections Horizontal Units HR Hot Water Return HS Hot Water Supply Coil Connections Inverted Units...

Page 46: ...46 Fresh Air Opening Fresh Air Opening Locations Horizontal Units Models C D and E Fresh Air Opening Dimensions Horizontal Units Unit Size 02 03 04 06 08 10 12 A 1 6 1 11 2 8 1 2 3 5 5 0 B 1 9 5 16 2...

Page 47: ...Fresh Air Opening Locations Vertical Units Models A B F and J Fresh Air Opening Dimensions Vertical Units Unit Size 02 03 04 06 08 10 12 A 1 6 1 11 2 8 1 2 3 5 5 0 B 1 9 5 16 2 2 5 16 2 11 13 16 3 8 5...

Page 48: ...3 4 1 04 24 3 8 x 7 1 2 1 06 33 1 8 x 7 1 2 2 08 37 1 2 x 7 1 2 3 10 12 58 1 4 x 7 1 2 4 Wall Box CLEARANCE FOR DRAINAGE CONTINUOUS MORTAR RIBS TOP AND BOTTOM WOVEN ALUMINUM INSECT SCREEN 1 8 1 8 1 2...

Page 49: ...2 5 5 1 2 6 D 1 1 8 1 5 8 2 1 8 2 5 8 3 1 8 3 5 8 4 1 8 4 5 8 5 1 8 E 8 5 8 8 1 8 7 5 8 7 1 8 6 5 8 6 1 8 5 5 8 5 1 8 4 5 8 Projection Panel Dimensions Unit Size 02 03 04 06 08 10 12 A 3 11 4 3 5 3 5...

Page 50: ...re is 300 psig 2 069 kPa Maximum entering water temperature is 200 F 93 C Tubes and u bends are 3 8 10 mm OD copper Fins are aluminum and are mechanically bonded to the copper tubes Coil stubouts are...

Page 51: ...are available on units with a Tracer ZN 520 controller The electric heat operates at the same voltage as the unit Therefore only a single point power connection is necessary All standard electric heat...

Page 52: ...rotating the grilles 90 degrees The quad grille is constructed of a black plastic material NORYL SE 1 731 with a 15 degree angle on the discharge louvers Quad grilles are available on all cabinet sty...

Page 53: ...e around vertical and horizontal cabinet units Aluminum Wall Boxes Wall boxes have a clear anodized finish and include a single core wire mesh insect screen The frame is 10 gauge extruded aluminum all...

Page 54: ...ssure 400 psi 2 758 kPa Manual Circuit Setter Material Body Forged Brass Alloy Trim Forged Brass Alloy All Wetted Parts Brass Temperature 250 F MAX 121 C Working Pressure 300 psi 2 069 kPa Auto Circui...

Page 55: ...2 Way Two Position N C 25 psig 172 kPa 3 Way Two Position N O 25 psig 207 kPa 3 Way Two Position N C 15 psig 103 kPa 2 Way Modulating 50 psig 345 kPa 3 Way Modulating 50 psig 345 kPa All valves are av...

Page 56: ...e or e mail us at comfort trane com Literature Order Number File Number Supersedes Stocking Location The Trane Company has a policy of continuous product improvement and reserves the right to change d...

Reviews: