Electrical Data
32
CAB-PRC001-EN
Table ED-6. Two-Stage Electric Heat (Digit 18 = U)
Unit
1st Stage
Total
Total
Size
Volts
Hz
Ph
Wires
kW
kW
Amps/ph
208
1
2
0.75
2.25
10.9
240
1
2
1.0
3.0
12.5
02
277
60
1
2
1.0
3.0
10.9
208
3
3
0.75
2.25
6.3
240
3
3
1.0
3.0
7.3
480
3
4
1.0
3.0
3.7
208
1
2
1.5
4.5
21.7
240
1
2
2.0
6.0
25.0
03
277
60
1
2
2.0
6.0
21.7
208
3
3
1.5
4.5
12.6
240
3
3
2.0
6.0
14.5
480
3
4
2.0
6.0
7.3
208
1
2
1.9
5.7
27.5
240
1
2
2.5
7.5
31.3
04
277
60
1
2
2.5
7.5
27.1
208
3
3
1.9
5.7
15.9
240
3
3
2.5
7.5
18.1
480
3
4
2.5
7.5
9.1
208
1
2
3.4
7.9
38.0
240
1
2
4.5
10.5
43.8
06
277
60
1
2
4.5
10.5
38.0
208
3
3
3.4
7.9
21.9
240
3
3
4.5
10.5
25.3
480
3
4
4.5
10.5
12.7
208
1
2
4.5
10.1
48.8
240
1
2
6.0
13.5
56.3
08
277
60
1
2
6.0
13.5
48.8
208
3
3
4.5
10.1
28.2
240
3
3
6.0
13.5
32.5
480
3
4
6.0
13.5
16.3
208
1
2
6.0
13.5
65.0
240
1
2
8.0
18.0
75.0
10
277
60
1
2
8.0
18.0
65.0
208
3
3
6.0
13.5
37.6
240
3
3
8.0
18.0
43.3
480
3
4
8.0
18.0
21.7
208
1
2
6.8
15.0
72.3
240
1
2
9.0
20.0
83.4
12
277
60
1
2
9.0
20.0
72.3
208
3
3
6.8
15.0
41.7
240
3
3
9.0
20.0
48.2
480
3
4
9.0
20.0
24.1
Note: When both stages are on, the electric heat will operate only when fan is in high speed. All data based on
individual units.