LEDs and the 7-Segment Display

Interpreting the 7-Segment Display

The 7-segment display shows the operating status of the Tracer SC.

Normal startup sequence:

8, 7, 9, 5, 4, -L, dancing dashes

Shutdown sequence:

Press power button. LED displays 3, -, 2, - 1 - until the application shuts down.

Press the power button to turn power off.

Table 2.

7-segment display: Codes and interpretation

Red/Green LED 

7-segment display

Indicates...

Green

8

Processor in reset, or no functioning software. A persistent “8” means 
that service is required.

Green

7

Starting level 1 boot loader

Green

9

Starting level 2 boot loader 

Green

5

Entering operating system. A persistent “5” means the operating 
system is malfunctioning.

Green 

4 (this number remains for a few seconds) Booting operating system.

Green

–L

Loading and initializing main program.

Green 

“Dancing dash” dashes flash one at a time: 
top, middle, bottom

Normal operation

Green

 3, -, 2, -, 1, - 
(sequence repeats)

Power button was pressed and Tracer SC is shutting down. May take 10 
or more seconds.

Green

3, 2, 1
(sequence repeats)

Main program shutting down due to reboot command. In most cases, 
the main program will be restarted.

Flashing Red

7 F 

Mismatch between level 1 boot loader and hardware. Service is 
required.

Flashing Red

7 H 

Hardware failure. SC will probably need to be replaced.

Flashing Red

7 A

Missing level 2 boot loader. 

Flashing Red

7 U

Mismatch between level 2 boot loader and hardware. 

Green

Single digit during operation

Rotary switch was changed. The new setting of the changed switch is 
displayed on the 7-segment LED for several seconds.

U, P, d

Firmware update is in progress.

d, o, n, E

Updating of the operating system is finished. The Tracer SC can be 
powered off, the SD card removed, and the Tracer SC restarted. 

F, o, r, C, E 

Rotary switches set to 999; forced return to factory defaults in 
progress.

C, L, E, A, r

Tracer SC is restoring factory defaults (whether by force return, UI 
command, or at the beginning of a database restore operation). 

r

Database restore in progress.

Flashing Red

H, O, L, d

Main program is delayed due to multiple crashes (may take up to 4 
hours).

Red

F

Cannot load operating system. May be remedied by SD-card update 
with appropriate software version.

Flashing Green

U

 Power button was pressed when main program was not running/not 
responsive. SC is shutting down; wait for LEDs to turn off.

Summary of Contents for BMSC000AAA011000

Page 1: ...rdous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment obs...

Page 2: ...fTrane in the United States and other countries All trademarks referenced in this document are the trademarks of their respective owners Warnings Cautions and Notices Warnings cautions and notices are...

Page 3: ...Tree Component onto the Home Button 16 Drag Tree Nodes to Other Locations 16 Rename Tree Nodes 16 Editing the Navigation Tree 17 Adding a Custom Graphics Node to the Tree 17 Editing a Node on the Tree...

Page 4: ...Systems VAS Application 36 Chiller Plant Control CPC Application 36 Viewing System Status 37 Tools 38 Backup and Restore 38 Custom Graphics 39 Global Referencers 39 Programs 39 System Logs 39 Tracer E...

Page 5: ...BAS SVU025A EN 5 Troubleshooting with LEDs and the 7 Segment Display 44 Force Return to Factory Defaults 44 Troubleshooting Network Connections 45 PING 45 IPCONFIG 45 Web Browser Security Settings 45...

Page 6: ...help icon located on the global navigation bar How to UseThis Guide Although it is best practice to familiarize yourself with all aspects ofTracer SC it is not necessary to read this guide in any part...

Page 7: ...es and troubleshooting for wiring BACnet unit controllers to a Tracer SC system controller Tracer SC Air Systems Application Guide BAS APG007 EN Describes variable air volume strategies for variable a...

Page 8: ...th power supply module PM014 with U S outlet enclosure ordered separately BMSC000AAA011100 obsolete Tracer SC system controller with power supply module PM214 with U S outlet in enclosure BMSC000AAA01...

Page 9: ...Enclosure for DIN mounted controllers 230 VAC no outlet X13651560010 not shown Transformer service part S3090062462 4 IMC power cable S3090059562 not shown Large enclosure for DIN mounted controllers...

Page 10: ...10 BAS SVU025A EN Product Overview Figure 2 Service parts for theTracer SC 1 2 3 5 4 2 3 4 6 7...

Page 11: ...enario 2 Multi SC Facility OneTracer SC must have an application license in order to install equipment and facilitate control AdditionalTracer SCs do not require a license Ethernet port 1 must be used...

Page 12: ...nfiguration UI and the entireTracer SC help system Outdoor air conditions This information area displays the current outdoor air temperature outside of your facility Context sensitive help Click to op...

Page 13: ...s Area VAS Chiller Plant AlarmsTab To apply a table filter 1 From one of the above mentioned pages click the filter icon The Filter dialog box appears 2 From the Column drop down list select a column...

Page 14: ...utton is available onTracer SC pages in which certain actions can be taken on selected items To delete a report example 1 Select a report from the Reports page 2 Click the actions button and then sele...

Page 15: ...ion tree can be customized according to your preferences and facility needs The tree must be unlocked before any editing can be done Click the chain link icon located at the bottom of the tree when cl...

Page 16: ...hanges lock the navigation tree by clicking the chain link icon DragTree Nodes to Other Locations Nodes can be dragged and dropped to other locations on the tree When a node is dropped onto another no...

Page 17: ...w the instructions in the dialog box to complete the action Adding a Custom Folder to theTree 1 Click the add folder icon located on the edit bar A new folder appears at the bottom of the tree or belo...

Page 18: ...on on an Alarm 1 Click inside each row to select an alarm Selected rows will be highlighted 2 Click the actions button to refresh add or view comments acknowledge a comment export the alarm log or del...

Page 19: ...uipment Service Required Alarms that require the attention of service personnel These might include dirty filter notifications or sensor failures Critical These alarms require the immediate attention...

Page 20: ...types of standard reports forTrane equipment Site reports VAS commissioning reports Points reports Chiller reports Reporting features include Creating scheduled reports Scheduling reports to run duri...

Page 21: ...he report title b Create unique file name by adding a sequence number each time the report is run select this option to save the report after each run by adding a sequence number to the file name This...

Page 22: ...be printed and saved With the proper security access system users can configure create delete update and manage clear enable and disable data logs in the system A list of data logs can be accessed by...

Page 23: ...f data at 15 minute intervals The seven day window will always maintain data for the last seven days The maximum window for SC Version 3 6 is seven days for SC Version 3 7 the maximum window is 90 day...

Page 24: ...ined amount of time after the trigger condition is met and when collection begins For example seven days of data at a 15 minute intervals The seven day window will always maintain the last seven days...

Page 25: ...ch as Variable air volume VAV boxes Fan coils Unit ventilators Constant Volume roof top units RTU The Spaces list page Figure 1 contains the most frequently needed data for equipment of these types To...

Page 26: ...lick on a space name from the Spaces page On the Space Status page you can navigate to Alarms Data Logs and Applications that are specific to the equipment by clicking on the individual tabs New data...

Page 27: ...built up units modular climate changers that are either of the following types Variable air volume AHUs which modulate the supply air based on static or space temperature control Generic equipment not...

Page 28: ...e column of the Equipment list page shows an example of an equipment status page On the Equipment Status page you can navigate to Alarms Data Logs and Applications that are specific to the equipment b...

Page 29: ...s in a facility The Schedules page shown in figure 1 contains four tabs Active Schedules All Schedules All Exceptions and All Calendars Optimal Start Stop Optimal start and stop times can be defined f...

Page 30: ...and areas for the schedule then click Add to move to selected items 5 Click next to continue The Create Schedule ScheduleTimes page appears 6 Select a schedule default Each day is independent of the...

Page 31: ...ime in which the present schedule or the event releases control over to the next event based on priority Conceptually a scheduled release is very similar to a timed override For example after the dail...

Page 32: ...of three functions input output value In total there are nine point types Analog inputs These are typically values such as room temperature or air flow pressure generated by a sensor or device Inputs...

Page 33: ...each state rather than a numerical value Inputs points obtain their value from a selected referencer Input points are typically used to read values from other controllers such as LonTalk devices or u...

Page 34: ...3 a number less than 13 has advanced override capability Points appearing with the following icon on their right can be overridden Points that have been overridden appear with the following icons A us...

Page 35: ...x 3 Click Save to initiate the override Override present a user override is in effect for this point 1 Select one of following override options Release all manual overrides Select this option to end t...

Page 36: ...ify Timed override functions Variable Air Systems VAS Application The variable air system VAS coordinates the control of air handlers rooftop units and variable air volume terminal units TheTracer SC...

Page 37: ...ewing System Status Click on systems in the left navigation menu to open the Systems page To view status for a particular application Area VAS CPC click a system name which opens the associated status...

Page 38: ...at copy at a later time It is important to back up Tracer SCs in the event that a system failure occurs Backups should also be performed prior to upgrading software adding devices or adding new applic...

Page 39: ...d to respond to the value of the data point A global reference is made up of one trigger and one or more targets It allows you to read a piece of data from one place and then send to one or more place...

Page 40: ...I or II equipment BCI I IntelliPak I or II equipment LCI I VAV equipment Tracer UC400 unit controllers ReliaTel equipment LCI R Tracer UC400 programmable unit controller Voyager equipment LCI V Tracer...

Page 41: ...boot file had been successfully applied To power down theTracer SC press the power button The 7 segment display performs a shut down sequence 3 2 1 before theTracer SC powers down The LEDs and the 7...

Page 42: ...tion Link 2 communication L2 TX flickers green Data transmission L2 RX flickers yellow Data reception LonTalk communication Lon TX flickers green Data transmission Lon RX flickers yellow Data receptio...

Page 43: ...down due to reboot command In most cases the main program will be restarted Flashing Red 7 F Mismatch between level 1 boot loader and hardware Service is required Flashing Red 7 H Hardware failure SC...

Page 44: ...the Tracer SC To reset the Tracer SC press the power button to shut down and then press again to restart Contact the Trane Product Support team if this does not solve the problem F code displays on th...

Page 45: ...ettings To perform the test 1 Select Start Run 2 In Run type cmd Click Enter 3 In the cmd exe window type ipconfig Click Enter You will receive a detailed list of all hardware and software connections...

Page 46: ...olio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and product data improvement and...

Reviews: