NOTE: 

Air flow can be adjusted by discreetly control-

ling the W1, W2, & W3 inputs to the AFC with multi-

stage thermostats.   See additional notes on wiring 

diagram.

Example: TAM9A0C36 with BAYWACC08 

hydronic heating coil

                 W1 input = 396 cfm

                 W1 + W2 input = 792 cfm

                 W1 + W2 + W3 input = 1200 cfm

Placing a jumper across all W inputs will re-

sult in the maximum airflow for the combina-

tion of heating coil and air handler. 

Section 8a.  24 Volt Operation

AIRFLOW DEMAND IN 24 VOLT CONFIGURATION

COIL MODEL / AHU MODEL

W1

W1 + W2

W1 + W2 + W3

PWM CONTROLLED

BAYWAAA05SC1A w/TAM9A0A24

264

528

800

Ramped HP Airflow

BAYWABB07SC1A w/TAM9A0B30

330

660

1000

Ramped HP Airflow

BAYWACC08SC1A w/TAM9A0C36

396

792

1200

Ramped HP Airflow

BAYWACC08SC1A w/TAM9A0C42

462

924

1400

Ramped HP Airflow

BAYWACC08SC1A w/TAM9A0C48

528

1056

1600

Ramped HP Airflow

BAYWACC08SC1A w/TAM9A0C60

594

1188

1800

Ramped HP Airflow

BAYWACC11SC1A w/TAM9A0C60

660

1320

2000

Ramped HP Airflow

Airflow is based upon the heating demand from the comfort control based on the heat-pump airflow

Example: 4T outdoor unit x 400 HP Heating cfm/ton = 1600

Section 8b.  Communicating Operation

AIRFLOW DEMAND IN COMMUNICATING MODE

COIL MODEL / AHU MODEL

MAXIMUM CFM

SERIAL COMMUNICATING

BAYWAAA05SC1A w/ TAM9A0A24

800

Ramped HP Airflow

BAYWABB07SC1A w/ TAM9A0B30

1000

Ramped HP Airflow

BAYWACC08SC1A w/ TAM9A0C36

1200

Ramped HP Airflow

BAYWACC08SC1A w/ TAM9A0C42

1400

Ramped HP Airflow

BAYWACC08SC1A w/ TAM9A0C48

1600

Ramped HP Airflow

BAYWACC08SC1A w/ TAM9A0C60

1800

Ramped HP Airflow

BAYWACC11SC1A w/ TAM9A0C60

2000

Ramped HP Airflow

Airflow is based upon the heating demand from the comfort control based on the heat-pump airflow

Example: 4T outdoor unit x 400 HP Heating cfm/ton = 1600

About Trane and American Standard Heating and Air Conditioning

Trane and American Standard create comfortable, energy efficient indoor environments for residential applications.

For more information, please visit www.trane.com or www.americanstandardair.com

The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are 

committed to using environmentally conscious print practices.

© 2020

18-GJ37D1-6A-EN   04 Aug 2020  
Supersedes 18-GJ37D1-6   (May 2017)

MET

C

US

®

NR

TL LISTED

Summary of Contents for BAYWACC11SC1AA

Page 1: ...s installation must comply with NATIONAL STATE AND LOCAL CODES 18 GJ37D1 6A EN Model BAYWACC11SC1AA Table of Contents Section 1 Safety Considerations 2 Section 2 General Information 3 Section 3 Hydron...

Page 2: ...ITS USE s s WARNING ELECTRICAL HAZARD DISCONNECT ALL ELECTRICAL POWER INCLUDING REMOTE DISCONNECTS BEFORE INSTALLING OR SERVICING FOLLOW PROPER LOCKOUT TAGOUT PROCEDURES TO ENSURE THE POWER CAN NOT BE...

Page 3: ...m one of the side conduit entry points Section 2 General Information Water Coil Model Number Nomenclature Digit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Coil number B A Y W A C C 1 1 S C 1 A A A Brand B Bo...

Page 4: ...SAFET Y NR TL LIS TED MET UL 1995 CAN CSA C22 2 No 236 E212365 Section 3 Hydronic Coil Assembly Field Pipe Connections 7 8 OD 3 4 ID copper tubing Hydronic Coil 12 Field Provided Screws 1 2 long Coil...

Page 5: ...flanges On the front flange the gasket material must be at the inner edge to create an airtight seal Gasket Place gasket material on the inner edge of front side flange Hot Wat er Out Hot Wat er In C...

Page 6: ...g directions Section 5 Piping NOTE The hydronic coil can be installed in upflow downflow or horizontal positions When the air han dler is installed in the horizontal orientation an addi tional strap m...

Page 7: ...110 60251 127 9 28861 97 47528 113 66048 130 3 24485 91 41011 101 56072 116 6 29226 94 48327 108 64905 123 9 31291 95 51432 111 71149 126 3 26736 89 44387 98 60848 112 6 31913 92 52305 105 70434 119 9...

Page 8: ...Example 4T outdoor unit x 400 HP Heating cfm ton 1600 Section 8b Communicating Operation AIRFLOW DEMAND IN COMMUNICATING MODE COIL MODEL AHU MODEL MAXIMUM CFM SERIAL COMMUNICATING BAYWAAA05SC1A w TAM9...

Reviews: