70
ARTC-SVX001B-EN
Code (hex)
Fault / Aux. code
Cause
What to do
5691
Measurement circuit ADC
Measurement circuit fault.
Contact your local ABB
representative.
5692
PU board powerfail
Power unit power supply failure.
Contact your local ABB
representative.
5693
Measurement circuit DFF
Measurement circuit fault.
Contact your local ABB
representative.
5696
PU state feedback
State feedback from output phases
does not match control signals.
Contact your local ABB
representative.
5697
Charging feedback
Charging feedback signal missing.
Check the feedback signal coming
from the charging system
6181
FPGA version incompatible
Firmware and FPGA versions are
incompatible.
Reboot the control unit (using
parameter
96.08 Control board boot
) or by
cycling power. If the problem
persists, contact your local ABB
representative
6306
FBA A mapping file
Fieldbus adapter A mapping file read
error.
Contact your local ABB
representative.
6481
Task overload
Internal fault.
Reboot the control unit (using
parameter
96.08 Control board boot
) or by
cycling power. If the problem
persists, contact your local ABB
representative
6487
Stack overflow
Internal fault.
Reboot the control unit (using
parameter
96.08 Control board boot
) or by
cycling power. If the problem
persists, contact your local ABB
representative
64A1
Internal file load
File read error.
Reboot the control unit (using
parameter
96.08 Control board boot
) or by
cycling power. If the problem
persists, contact your local ABB
representative
64B2
User set fault
Loading of user parameter set failed
because
• requested set does not exist
• set is not compatible with control
program
• drive was switched off during
loading.
Ensure that a valid user parameter
set exists. Reload if uncertain.
64E1
Kernel overload
Operating system error.
Reboot the control unit (using
parameter
96.08 Control board boot
) or by
cycling power. If the problem
persists, contact your local ABB
representative
6581
Parameter system
Parameter load or save failed.
Try forcing a save using parameter
96.07 Parameter save manually
.
Retry.
65A1
FBA A parameter conflict
The drive does not have a
functionality requested by PLC, or
requested functionality has not been
activated.
Check PLC programming.
Check settings of parameter groups
50 Fieldbus adapter (FBA)
and
51
FBA A settings
.
6681
EFB comm loss Programmable fault:
58.14 Communication loss action
Communication break in embedded
fieldbus (EFB) communication.
Check the status of the fieldbus
master (online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31
on the control unit.